Specifications

1-14 Introduction
1. 5. Overview of NuDAM-6054
What is NuDAM-6054 ?
NuDAM-6054 provides 15 isolated digital input channels. All of the
input channels are common power type and one of them is using the
same pin with default (use jumper to choose). The isolation voltage is
up to 5000 Vrms. It is suitable to use NuDAM-6054 in industrial
environment with the dangerous of high voltage electric shock.
Features of NuDAM-6054
15 bits digital inputs with isolation protection and common power
5000 Vrms isolation voltage
Programmable host watchdog timer for host failure protection
Internal watchdog timer for device failure protection
Easy programming by software
Easy installation and wiring
Specifications of NuDAM-6054
² Interface
Interface : RS-485, 2 wires
Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 115.2K
(115.2K only for firmware reversion above A4.00)
² Input
Channel numbers : 15 isolation common power input channels
(the fifteenth channel is the same with default pin, but can use
jumper to choose).
Input type : source type .
Effective distance: 500 m.
Common external voltage: 24V.
² Watchdog Function
Module internal watchdog timer : 150msec
Power failure threshold : 4.65 V
Host programmable watchdog :100 ms ~ 25.5 sec
² Power
Power supply : +10V to +30V
Power consumption : 0.4 W