Specifications

Command Set 3-23
This analog output module return the latest output value is 2.000
mA at address 08H, if data format is engineering units and the
signal range is 0~20mA.
3. 17. Current Readback
@Description
Read the estimated current output value at the specified analog
output module. .
@Syntax
$(Addr)8<CR>
$ Command leading code. (1-character)
(Addr) Address ID. (2-character)
6
Function code of last value readback.
(1-character)
@Response
!(Addr)(Data)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(Data)
The current analog output value, the data
format depends on module configuration.
@Example
User command: $088<CR>
Response: !0802.000<CR>
This analog output module return the latest output value is 2.000
mA at address 08H, if data format is engineering units and the
signal range is 0~20mA.