Specifications

Command Set 3-19
3. 13. 20mA Calibration
@Description
Stores the current output value as 20 mA reference at the
specified analog output module. (only 6021)
@Syntax
$(Addr)1<CR>
$
Command leading code (1 character)
(Addr)
Address ID (2 characters)
1
Function Code, 20 mA calibration (1 character)
@Response
!(Addr)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
@Example
User command: $061<CR>
Response: !06<CR>
To perform the 20 mA calibration for analog input module at
address ID 06H.
Note : Analog output module should be trimmed to the correct
value by “Trim Calibration” command before to execute “20
mA Calibration”. Refers to Chapter 5 “Analog Output
Calibration” for details .