Specifications
Command Set 3-17
The command sets the analog output to be 16 mA at address
06H, if the data format is configured as engineering units and
0~20mA output range.
User command: #08+020.00<CR>
Response: ><CR>
The command sets the analog output to be 4 mA at address 08H,
if the data format is configured as % of FSR and 0~20mA output
range.
4mA = 20mA x 20.00%
User command: #097FF<CR>
Response: ><CR>
The command sets the analog output to be 5 V at address 09H, if
the data format is configured as hexdecimal format and output
range of 0~10V.
5 V = 7FF / FFF x 10V
User command: #08A-05.000<CR>
Response: ><CR>
The command sets the analog output port A to be –5 V at address
08H.