Specifications
Command Set 3-9
3. 4. Read Configuration
@Description
Read the configuration of module on a specified address ID.
@Syntax
$(Addr)2<CR>
$
Command leading code
(Addr)
Address ID.
2
Command code for reading configuration
@Response
!(Addr)(OutputRange)(BaudRate)(DataFormat)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(OutputRange)
Current setting of analog voltage output,
refers to Table 3-1 for details.
(BaudRate)
Current setting of communication baud
rate, refers to Table 3-2 for details.
(DataFormat)
Current settings of checksum, integration
time and output data format, refers to
Figure 3-1 for details.
@Example
User command: $182<CR>
Response: !18320610<CR>
!
Command is valid.
18
Address ID.
32
Analog output range is 0 to 10V
06
Baud rate is 9600 bps.
10
The output data is in engineering units, slew rate is
1mA/sec, checksum is disable.