60 Extension Modules
5.8 PMC-7852G
5.8.1 Features
General:
One master has two HSL ports
One port can drive maximum 32 modules
One master can control maximum 63 slave I/O modules
Maximum wiring distance for each port: 200m (serial wiring from master to
last slave module)
Wiring:
Connector: RJ45 (on both master controller and slave modules)
Cable: Cat.5 100 Base/TX Ethernet cable, shielded preferred
Communications:
Multi-drop full-duplex RS-422 with transformer isolation scheme
Data Rate: 6Mbps
I/O refresh rate: 30.1 µs x numbers of slave I/O modules (min: 3; max: 63)
Communication model: single-master/multi-slave
Communication method: command – response
CRC12 and dedicate protocol for eliminating communication errors
5.8.2 Specifications
PCI Controller:
PCI local bus specification Rev. 2.1 compliance
Master Controller:
Master controller: ASIC
External Clock: 48MHz
Memory:
32KB SRAM – 12ns
Interface:
RS-422 with transformer isolation
Full duplex communication
Selectable transfer speed by dip switch (Default 6Mbps)
Two ports for one control master
Connector:
RJ45 connector x 4 (H1A, H1B, H2A, H2B for PMC-7852G)