User`s guide

Registers Format
21
3.5 Mode and Interrupt Control Register
The Mode and Interrupt control register is a write-only register. This
register control the AD operating modes and the IRQ level of the
ACL-8111. The AD operation modes include the AD clock source
and the AD data transfer method.
Address : BASE + 11
Attribute: write only
Data Format:
Bit 7 6 5 4 3 2 1 0
BASE+11
X IR2
IR1
IR0
X M2
M1
M0
Where M0, M1, and M2 are mode selection:
M2
M1
M0
Description
0 0 0 Software trigger with program polling
0 0 1 (No interrupt generated)
0 1 0 External trigger with program polling
0
1 1 External trigger with interrupt polling
(With End-of-conversion “EOC” interrupt)
1 0 0 Internal time pacer trigger and polling
(No interrupt generating)
1 0 1 Not Used
1 1 0 Internal timer pacer trigger with interrupt data
transfer
(With End-of-conversion “EOC” interrupt)
1
1 1 Not Used
Note: The external trigger signal comes from the DI 0 (pin-1 of CN2).
Where IR0, IR1, and IR2 are interrupt IRQ level settings:
IR2
IR1
IR0
IRQ Level
0
0
0
IRQ2
0
0
1
Not Used
0
1
0
IRQ2
0
1
1
IRQ3
1
0
0
IRQ4
1
0
1
IRQ5
1
1
0
IRQ6