Instruction manual

56
10 GB Communication
Version
1.0
3
& Control Card Instruction Manual
SETCTCLKDIV instruction
Byte
7
6
5
4
3
2
1
0
1
-
2
Opcode
0x0
122
3
-
4
Length
0x0002
5
-
6
Clock Divide Value (MSB..
LSB)
Description:
Set the Clock Divide Value of the CAM Timer module. Divide value
must be greater than 1. (Use the SAVESETTINGS instruction to save changes
to the EEPROM.)
SETCTTIMER instruction
Byte
7
6
5
4
3
2
1
0
1
-
2
Opcode
0x0
123
3
-
4
Length
0x000
D
5
Timer (1..10
)
6
-
9
Delay (MSB..LSB)
10
-
11
On (MSB..LSB)
12
-
13
Off (MSB..LSB)
14
-
17
Number of Pulses (MSB..LSB)
Description:
Set the timer parameters of the CAM Timer module. (Use the
SAVESETTINGS instruction to save changes to the EEPROM.)
Note: The first 4 bits (bit 31..28) of the 32-bit Number Of Pulses
parameter are the channel enable bits.