Instruction manual

49
10 GB Communication
Version
1.0
3
& Control Card Instruction Manual
PROGRAMSAMPLEDIVIDER instruction
Byte
7
6
5
4
3
2
1
0
1
-
2
Opcode
0x0
104
3
-
4
Length
0x0002
6
-
5
Sample Divide Value (MSB first)
Description:
Program the Sample Clock divide value. (Use the SAVESETTINGS
instruction to save changes to the EEPROM.)
SETSPAREIO instruction
Byte
7
6
5
4
3
2
1
0
1
-
2
Opcode
0x0
105
3
-
4
Length
0x0001
5
SpareIO
Description:
Set the Spare IO port. (Use the SAVESETTINGS instruction to save
changes to the EEPROM.)
SETXFP instruction
Byte
7
6
5
4
3
2
1
0
1
-
2
Opcode
0x0
106
3
-
4
Length
0x0001
5
0
0
0
0
0
0
0
CLK
Description:
Set the XFP port. (Use the SAVESETTINGS instruction to save changes
to the EEPROM.)
CLK: 0 – Disable reference clock for the XFP module
1 – Enable reference clock for the XFP module