GSME-X22 EN Supplementary Instructions Manual Fire Gas Detector GSME® GTE Industrieelektronik GmbH | Helmholtzstr. 21, 38 – 40 41747 Viersen | Germany | +49 2162 3703-0 | info@gte.
Supplementary Instructions for GSME-X22 Article number: 400-2410-002 Index: EN21 Release date: 28.01.20 – Translation – Manufacturer: GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 41747 Viersen GERMANY Support hotline: +49 2162 3703-0 E-Mail: support.adicos@gte.
Abstract The Advanced Discovery System (in short: ADICOS) is used for early detection of fire scenarios in the industrial environment. It comprises different, independent detector units that enable interference-resistant fulfillment of the detection objective defined during planning via suitable layout and parameterization.
CONTENTS Contents 1 2 3 4 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Objective . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Explanation of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.3 Storing the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . .
AbOuT THIS MANuAl 1 1.1 About this manual Objective This manual describes the special requirements on installation, wiring, commissioning, and operation of ADICOS detectors for explosive atmospheres of ATEX zone 22. They are exclusively addressed to knowledgeable specialist personnel (–› Chap. 2, Safety instructions). 1.2 Explanation of symbols This manual features a continuous structure for best possible comprehension. The following labels are used.
SAfETY INSTRuCTIONS 2 Safety instructions ADICOS detectors for explosive atmospheres of ATEX zone 22 (short: ADICOS X22-Detectors) ensure operational safety assuming proper installation, commissioning, operation, and maintenance. for this purpose, it is absolutely required to completely read, understand, and follow this manual and the safety information contained. WARNING! Installation and operating errors can lead to fatal and severe injuries and damage to the industrial plant. − 2.
SAfETY INSTRuCTIONS 2.3 Personnel qualification Any work on ADICOS systems may only be performed by qualified personnel. Persons, who can perform work on electrical systems and recognize possible dangers based on their professional education, knowledge, and experience as well as knowledge of the applicable provisions, are considered qualified personnel. WARNING! Installation, commissioning, parameterization, and maintenance may only be performed by authorized and respectively trained personnel 2.
STRuCTuRE 3 Structure 3.1 Overview 3 2 100 4 5 1 100 4 No.
STRuCTuRE 3.2 Cable assignment Wire Color Signal Limit value contact 1 black 1 white Operating voltage 24 ... 40 V DC non-polarised 2 black Relay output X6 e Alarm NO1 2 white Relay output X6 a Alarm NO1 3 black Relay output X7 a fault NC 3 white Relay output X7 e fault NC 4 black 4 white M-bus max.
STRuCTuRE 3.3 Type plate information The type plate of the ADICOS X22-Detectors contains the following information: GTE Industrieelektronik GmbH Typ -X22 K.N. GS.xx.IR. xxx Bj. 20xx II 3D Ex tc IIIC T100°C Dc Ik IP 6X V/VA 21,6-40V DC/14VA Art. 400-2410-0xx °C -20 ≤ tamb ≤ 50 S/N NOTE! until 12-2014, some ADICOS X22-Detectors have been labeled as ADICOS Ex detectors.
INSTAllATION 4 4.1 Installation Mounting WARNING! ADICOS X22-Detectors must be mounted with closed enclosure.
COMMISSIONING 4.2 Wiring DANGER! The electronics of the ADICOS X22-Detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres.
MAINTENANCE: DETECTOR REPlACEMENT 7 Maintenance: Detector replacement DANGER! The electronics of the ADICOS X22-Detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres.
TECHNICAl DATA 8 Technical Data General Model: GSME-X22 Item No.: 408-2001-251 Enclosure dimensions: mm 128 x 100 x 100 (l x w x h) Weight: (icl. 7 meter cable): kg 2 Weight (excl. cable): kg Enclosure: 1,7 kg (incl. 7m cable) Aluminum die casting, powder-coated Electrical properties Rated Voltages: V DC 24 Voltage range: V DC 21,6 … 40 Max. Power consumption: (excl. heating): VA 3,5 Max. Power consumption: (incl. heating): VA 14 V/mA max. 40 V non-polarised / max.
APPENDIX: ADICOS MOuNTING PlATE NOTE! ADICOS X22-Detectors are rated Protection by enclosure “tc”.