User`s manual
MDL-DataManager™ Reference Guide Architectural Energy Corporation
Appendix A – Module Wiring Connections 32
Appendix A – Module Wiring Connections
Architectural Energy Corporation (AEC) stocks signal conditioning modules for use
with a wide array of AEC-supplied or third-party sensors. These different signal
conditioning modules allow the MicroDataLogger unit (MDL) to connect to nearly any
sensor or meter on the market based on the sensor or meter output signal. Each
separate sensor or meter to be used with the MicroDataLogger data acquisition
system will require a module to connect to the MDL to the sensor. It is important to
note that AEC carries a number of sensors that are pre-wired to modules for your use:
temperature, humidity, occupancy, and lite level.
General Signal
Measurement
Modules
A variety of plug-in modules are available for interfacing the MDL to a range of sensor
and transducer output signals. Most third-party sensors and transducers – including
those carried by AEC – can be used with the MDL.
The MDL-DataManager software enables the user to scale the signal being read and
assign an appropriate engineering unit of measure. Sensor or field wiring is connected
to the modules via a 4-circuit, plug-in, screw type terminal block. Current can be
measured directly using the 20 mA DC module. Signal conditioning modules for full-
scale ranges above 5 volts use a precision resistor divider to attenuate the input
signal.
Note:
The 20 mA DC signal conditioning module, model ADC-33-3, can be
damaged by transient voltages if it is connected to the current loop circuit
while the circuit is energized.
Screw
Part/Module Number
Pin
Designations for
ADC-33-3 (4-20mA)
1 – Signal Input
Wiring
VDC-19-3 (5V)
2 + Signal Input
VDC-29-3 (10V)
3 – 12 Vdc Return
4 + 12 Vdc Power Out
Part/Module Number
Pin
VAC-17-3 (333mV)
1 n/c
2 mV Input Low
3 mV Input Hi
4 n/c
Part/Module Number
Pin
COUNT-80-3 (pulse)
1 Switch (–)
2 Switch (+)
3 n/c
4 n/c
Part/Module Number
Pin
STATUS-81-3 (AC/DC)
1 n/c
2 n/c
3 Voltage Low
4 Voltage Hi
1 2 3 4
module
label
terminal block numbered left to right