Datasheet
CAN Bus Repeater/Isolator
l Extension of the CAN network
l Galvanic isolation
l Increasing of the nodes number
l Different baud rates selectable
l Independent of the used protocol
Ideal solution for the extension of your CAN network. Ideal for galvanic
isolation. For use in motors and devices with electromagnetical
interferences.
Usable as repeater for the following lines: CANopen, Devicenet and
generic standard ISO 11898. The internal data processing will be
carried by a 16-bit microprocessor. The double sided programming of
the data transfer rate is possible, where the maximum baud rate is
limited to a maximum of 1MBit. It is possible to install multiple repeaters
in a single network. The unit can be easily mounted on a standard DIN
rail.
Standard: ISO 11898
Communication ports: 2 x CAN 2.0
Max. distance: 5.000 m for 10 kbps;
25 m for 1Mbps.
Baud rate: 10 k, 20 k, 50 k, 62,5 k, 100 k, 125 k,
250 k, 500 k, 800 k, 1.000 k
Galv. isolation: >2000 VDC
DIP-switch: Selction of different baud rates
LED’s: 1 x power supply
2 x signal
Supply: 24 VDC , 200mA;
12/18 VAC , 200mA , 50/60 Hz
Operating temperature: -20 °C to 70 °C
Humidity: 10 % to 80 % , non condensing
CE-Conformity: EN 61000-6-2
FCC Standard part of class A
Dimensions: 120 x 23 x 107 mm (D x W x H)
Weight: approx. 200 g
Mounting: Mounting on DIN rail
Schematics:
.
Order details
Type Order-no.
CAN Bus Repeater for CAN 2.0A, CANopen HD67117
CAN Bus Repeater for CAN 2.0B HD67181
Dimensions in mm
Copyright by Wachendorff Prozesstechnik GmbH & Co. KG, Industriestraße 7, D-65366 Geisenheim, Tel.: 06722/9965-20, Fax: -78, Stand: 16.03.2011.
All information without guarantee and subject to change.
Wachendorff Prozesstechnik GmbH & Co. KG
Industriestrasse 7
D-65366 Geisenheim
Tel.: +49 (0) 67 22 / 99 65 - 20
Fax: +49 (0) 67 22 / 99 65 - 78