Specifications

Connecting AC Power
Adept MV Controller User’s Guide, Rev C 49
7. Change the two external fuses (F3 and F4) on the power entry module from the
200-240V to the 100-120V value; see fuse information in Table 4-5 and the label
below the power entry module.
8. Mark or alter the ID label to indicate the controller is now configured for
100-120 VAC.
9. Connect the AC power cord and the controller is ready to operate.
Figure 4-2. Adept MV Controller with Back Panel Open
Remove these screws
(two on each side) to
fold down the back
panel.
Configuration
Jumper Block
F1
F2
F5
1 5 9 13 17 21 25 29 33 37
2 6 10 14 18 22 26 30 34 38
3 7 11 15 19 23 27 31 35 39
4 8 12 16 20 24 28 32 36 40
Numbering pattern on jumper block