Specifications

VMEbus Address
Adept MV Controller User’s Guide, Rev C 139
12.3 VMEbus Address
Each VFI module must have a unique VMEbus address. If you use only one force sensor
or if your VFI modules are factory-installed, your V
+
system should already be configured
properly. If you add VFI modules to a controller, you will have to set the correct address.
The address is set at DIP switch S1 and jumper J1 on the VFI module.
The switch and jumper settings on the VFI module should be set as listed in Table 12-1.
These are necessary to establish proper communication with other modules on the
backplane. Confirm the switch and jumper settings before you proceed with installation.
When you add multiple force sensors to an existing system, you must use the
CONFIG_C
utility program to specify which sensor is force sensor number 1, which is number 2, and
so on. See the AdeptForce VME User's Guide for more information on this process.
Table 12-1. Address Settings for VFI Module
Drawing of Settings Description of Settings
Address above is B7 = 10110111
S1 address settings for multiple VFI boards:
Sensor 1 (servo board 8): B7=10110111
Sensor 2 (servo board 9): B8=10111000
Sensor 3 (servo board 10): B9=10111001
Sensor 4 (servo board 11): BA=10111010
Jumper the pins shown on jumper J1 when VFI board
has 128K ROM with 1K boot page.
1 2 3 4 5 6 7 8
off
S1
JP1