Specifications
VMEbus Address
Adept MV Controller User’s Guide, Rev C 77
6.5 VMEbus Address
Each 040 module in an Adept MV controller must have a unique module address. The
address is set on Jumper block J22 on the 040 PC board (see Figure 6-3 for location of
jumpers). Table 6-4 shows the jumper settings for multiple processor modules.
If you are using both 040 and 030 processor modules, each module must have a unique
address. You cannot set an 040 and an 030 to the same address. For example, if you have
an 040 and an 030 installed, one of them must be set as module #1 and the other as module
#2. See section 6.7 for additional information.
6.6 040 Jumper Settings
The table below shows the jumper settings for J1 and J20. See Figure 6-3 for the location of
the jumpers.
a
“In” means that the removable jumper is installed across the two indicated pins. “Out”
means the jumper is not installed.
Table 6-4. Address Settings for the 040 Processor Module
Module
Number
Jumper Block J22 – Jumper Status
a
1–2 3–4 5–6 7–8 9–10 11-12 13–14 15–16
1 (main proc)InInInInOutInInIn
2 (auxiliary)OutInInInOutInInIn
3 (auxiliary) In Out In In Out In In In
4 (auxiliary) Out Out In In Out In In In
Table 6-5. Jumper Settings for 040 Processor Module
Jumper number Jumper Setting
J1 (SCON) In for main processor
(module #1)
Out for auxiliary processor
(module #2, 3, or 4)
J20 Standard setting is to install
jumpers across pins 1 to 3 and
pins 2 to 4.