Setup guide

VISTA-32FB Installation and Setup Guide
5-14
FIELD
TITLE and DATA ENTRIES EXPLANATION
3
140
Waterflow Alarm Silence Option
0 = silenced by User Code + OFF
1 = silenced when zone restores
Select how the Waterflow zone type will be silenced.
NOTES:
This feature may be set to 1 only by permission of the local authority.
For an output of a 4204CF to be silenced when 3*14=1, all Type 17
(Waterflow) zones activating the output must be put into a Zone List, and that
Zone List must be the STP condition of the 4204CF fire output. In addition to
the STP ZL, you also need an STP ZT of 22 in order to silence via code + off
in the event the zone does not restore.
Since a Type 17 zone is processed as a FIRE alarm, it will activate outputs
programmed for STT ZT 17, 16, 09, and 39. The only way to have individual
output activations (e.g. ZT17 versus ZT09) is to use zone lists.
NOTE: Must be set to 0 for Commercial Fire installations.
3
160
Zone Types 17 & 18 Delay
Enter 01-15 times 2 seconds
Enter 00 for no delay
Select the delay time for zone types 17 and 18. The zone must be faulted for
entire delay time before an alarm or supervisory condition occurs. This may
prevent alarms due to minor fluctuations in waterflow.
Maximum combined delay of 3*16 and 3*18 cannot exceed 90 seconds for UL
installations.
NOTE: Must be set to 00 for Commercial Fire installations.
3
170
Zone 6 Alternate Function Enable
0 = disable
1 = enable
If enabled, zone 6 may be used as a tamper zone (bell and cabinet tampers).
If used, the zone will annunciate in accordance with response type, rather
than a ground fault when a ground fault is detected.
3
180
Extended Delay for Zone Types
17 & 18
0 = no extended delay
1 = multiply delay by 4
This option allows the delay programmed in field 3
16 for Waterflow and
Supervisory zones to be extended by four times.
NOTE: Must be set to 0 for Commercial Fire installations.
3
190
Auxiliary Input Alternate
Function Enable
0 = disable
1 = enable
If enabled, pins 5 and 9 on the J2 connector function as Printer RXD and
DTR, respectively. If disabled, they function as fire alarm trigger and
Communications Device Xmit Okay. See the chart at field 3*20 for the J2
trigger configurations.
NOTE: If field 3*19 is enabled, you cannot use a Communications Device
connected to the J2 trigger.
3
200
Trigger Outputs Function
Selection
0 = remote keypad sounder
1 = keyswitch LEDs
Select the function of the J2 trigger outputs. See chart below.
J2 Pin
Field 3*19 = 0
Field3*20 = 0
Field 3*19 = 0
Field3*20 = 1
Field 3*19 = 1
1 Panic Alarm Panic Alarm As selected in field 3*20
2 Trouble Trouble As selected in field 3*20
3 Burglary Alarm Burglary Alarm As selected in field 3*20
4 Fire Supervisory Fire Supervisory As selected in field 3*20
5 Fire Alarm Fire Alarm Printer RXD
6 Remote Console Sounder Keyswitch Ready LED As selected in field 3*20
7 Open/Close Keyswitch Armed LED As selected in field 3*20
8 Ground Ground Ground
9 Communicator Xmit Okay Communicator Xmit Okay Printer DTR
3
210
Maximum Number of Dialer
Attempts
Enter the number of dialing attempts 1-8.
Select the maximum number of dialer attempts for the system.
NOTE: Must be 3, 4, or 5 for NFPA 72 compliant systems if a secondary
phone number is programmed.
3
300
Dialer Selection
0 = disable
1 = enable
This field has two entries, one for each dialer (main and backup). Enter 1 if the
dialer is being used.
NOTE: If 3*30 is disabled (0, 0), the panel does not report at all via a
Communications Device.