Setup guide
Section 5 – Data Field Descriptions
5-13
FIELD
TITLE and DATA ENTRIES EXPLANATION
2
✴
✴✴
✴
210
Supervision Pulses for
Communicators
0 = disable
1 = enable
Silent Panic/Duress, Supervisory, and Trouble.
If enabled, causes the control to send periodic short pulses on the J2
communicator triggers to the communications device. The communications
device uses these pulses to determine that its connection to the control is still
intact.
Must be set to “00000” for Commercial Fire and Burglary installations.
Not Used.
2
✴
✴✴
✴
220
Display Fire Alarms of Other
Partitions (partition-specific)
0 = disable
1 = enable
If enabled, allows fire alarms that occur on other partitions to be displayed at
this partition’s keypad(s).
NOTE: Must be disabled “0” for partition 1 in Commercial Fire installations.
2
✴
✴✴
✴
230
Display Burg, Panic and CO
Alarms for Other Partitions
(partition-specific)
0 = disable
1 = enable
If enabled, allows burglary, panic and CO alarms that occur on other partitions
to be displayed at this partition’s keypad(s).
NOTE: Must be disabled “0” for partition 1 in Commercial Fire installations.
2
✴
✴✴
✴
240
Display Troubles of Other
Partitions (partition-specific)
0 = disable
1 = enable
If enabled, allows troubles that occur on other partitions to be displayed at this
partition’s keypad(s).
NOTE: Must be disabled “0” for partition 1 in Commercial Fire installations.
3
✴
✴✴
✴
000
Check or TRBL Display
0 = CHECK
1 = TRBL
Select whether the system should display CHECK or TRBL when a trouble
condition occurs.
3
✴
✴✴
✴
010
Event Display Lock
0 = disable
1 = enable
If enabled, the system locks the display on the first fire alarm. Press
✳ to
display the next fire alarm in the system. If disabled, the system scrolls all
alarms automatically.
When 3*01 is Enabled, the following priorities go into effect:
The First event to occur is locked on the display; subsequent events will be
displayed in priority order:
Priority 1: Life Safety: ZT 06, 07, 09, 16, 17, and Duress override all other s
below
Priority 2: Property Safety: ZT 01, 02, 03, 04, 05, 10 override all other s below
Priority 3: Supervisory: ZT 14, 18, 19 and Fire Trouble override all other s
below
Priority 4: System: AC Loss, Low Bat, Line Cut, etc. do not override any other
events
NOTE: Must be set to “1” for Commercial Fire Installations.
3
✴
✴✴
✴
120
Zone Type 18 Delay Use
0 = disable
1 = enable
If enabled, use the delay time programmed in field 3
✳16.
3
✴
✴✴
✴
130
Fire Supervisory Response to
Open/Short (Applies to Zone
Type 18)
0 = disable
1 = enable
If “0” is selected, the system will respond with a trouble on open, and a
supervisory on short.
If “1” is selected, the system will respond with a supervisory on open, and a
supervisory on short.
Must be set to “0” for Commercial Fire and Commercial Burglary installations.