Setup guide
Section 5 – Data Field Descriptions
5-11
FIELD
TITLE and DATA ENTRIES EXPLANATION
1
✴
✴✴
✴
560
AC 60Hz or 50Hz
0 = 60Hz
1 = 50Hz
Select the frequency for the AC.
Must be set to 0 for U.S. and Canadian installations.
1
✴
✴✴
✴
570
Enable 5800 RF Button Global
Arm
0 = disable
1 = enable
If enabled, the system arms/disarms in accordance with the button’s user’s
global-arming settings.
Must be 0 for Commercial Fire and Commercial Burglary installations.
1
✴
✴✴
✴
580
Enable 5800 RF Button Force
Arm
0 = disable
1 = enable
If enabled, allows the RF button user to force a bypass of all faulted zones
when arming the system.
NOTE: When attempting to arm the system, the keypad beeps once after the
button is pressed if any faulted zones are present. The user should then
press the button again within 4 seconds to force-bypass those zones and arm
the system.
1
✴
✴✴
✴
600
Zone 5 Audio Alarm Verification
0 = disable
1 = enable
If enabled, zone 5 is used for 2-way audio (AAV).
Must be 0 for commercial fire and burglary installations.
NOTE: Zone 5 cannot be used as protection zone.
1
✴
✴✴
✴
700
Event Log Types
0 = disable
1 = enable
This field has five entries as follows: Alarm, Check, Bypass, Open/Close, and
System. If enabled, the system logs those events into the event log.
1
✴
✴✴
✴
710
12/24 Hour Type Stamp Format
0 = 12-hour
1 = 24-hour
Select the type of time stamping for the event log.
1
✴
✴✴
✴
720
Event Log Printer On-Line Mode
0 = disable
1 = enable
If enabled, the system prints the events as they occur.
If disabled, the system prints the log only upon request.
1
✴
✴✴
✴
730
Printer Baud Rate
0 = 1200
1 = 300
Select the baud rate for the serial printer.
NOTE: Must be 1 if using the alphanumeric pager interface.
1
✴
✴✴
✴
740
Relay Timeout XXX Minutes
Enter 000-127 times 2 minutes (000-254).
This is used for #80 Menu Mode Time-Driven event relay command numbers
“04/09” and
Output Programming
in the
#93 Menu Mode Programming
output
command “56.”
1
✴
✴✴
✴
750
Relay Timeout YYY Seconds
Enter 000-127 seconds.
This is used for #80 Menu Mode Time-Driven event relay command numbers
“05/10” and
Output Programming
in the
#93 Menu Mode Programming
command “57.”
1
✴
✴✴
✴
760
Control Relay (partition-specific)
01-96 = relay number
00 = relay not used.
If enabled, the assigned relay closes for 2 seconds when the user enters his
code and presses 0.
Must be 00 for Commercial Fire and Burglary installations.
NOTE: See
SECTION 3: Installing the Control
for enhanced access control
capabilities.
1
✴
✴✴
✴
770
Log First Maintenance Signal
0 = disable
1 = enable
If enabled, the system logs the first maintenance signal from each smoke
detector. If disabled, no logging occurs.
2
✴
✴✴
✴
000
Number of Partitions
Enter 1-2.
Enter the number of partitions used in the system.
2
✴
✴✴
✴
010
Daylight Saving Time Start/End
Month
0 = disable
1 = enable
Enter the months (00-12) in which daylight saving time starts and ends.
Enter 00, 00 if daylight saving time does not apply to the user’s region.
Standard setting for U.S. is 03, 11.