Setup guide
Section 5 – Data Field Descriptions
5-9
FIELD
TITLE and DATA ENTRIES EXPLANATION
1
✴
✴✴
✴
220
Cross Zoning Pair One
Enter 001-032
Enter 000,000 to disable
Select the first pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1
✴
✴✴
✴
230
Cross Zoning Pair Two
Enter 001-032
Enter 000,000 to disable
Select the second pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1
✴
✴✴
✴
240
Cross Zoning Pair Three
Enter 001-032
Enter 000,000 to disable
Select the third pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1
✴
✴✴
✴
250
Cross Zoning Pair Four
Enter 001-032
Enter 000,000 to disable
Select the fourth pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1
✴
✴✴
✴
260
Panic Button or Speedkey
For A, B, C keys:
00 = panic function
01-32 = macro number
For D key:
00 = to select a macro to execute when key
is pressed
01-32 = macro number
Select for the A, B, and C keys whether the system performs a panic or a
speedkey function when the key is pressed.
Select for the D key whether the system performs a specific macro or if the
user will select a macro when the key is pressed.
1
✴
✴✴
✴
280
RF Transmitter Low Battery
Sound
0 = disarmed state only
1 = both armed and disarmed states
Select when the RF transmitter low-battery condition should display and
audible beep annunciate on the keypad.
Must be 1 for Commercial Fire and UL Commercial Burglary installations.
1
✴
✴✴
✴
290
RF Transmitter Low Battery
Reporting
0 = disable
1 = enable
If enabled, the system sends a Trouble message for RF transmitter low-
battery condition to the central station.
NOTE: The Trouble message will be sent for a transmitter supervision failure,
independent of this selection.
Must be 1 for Commercial Fire and UL Commercial Burglary installations.
1
✴
✴✴
✴
300
RF Receiver Supervision Check-
in Interval
Enter 02-15 times 2 hours (4-30 hours).
00 = disable receiver supervision.
Select the check-in monitoring interval for the RF receiver(s).
Failure of a receiver to receive any RF signal within the time entered results in
the activation of the response type programmed for zone 990 for the first
receiver and zone 988 for the second receiver and their related
communication reports.
Maximum is 2 (4 hr) for Commercial Fire and UL Commercial Burglary
installations.
1
✴
✴✴
✴
310
RF Transmitter Check-in Interval
Enter 02-15 times 2 hours (4-30 hours).
00 = disable transmitter supervision.
Select the check-in monitoring interval for the RF transmitters.
Failure of an individual transmitter to send a supervision signal within the time
entered will result in a trouble response and related communication report.
Maximum is 2 (4 hr) for Commercial Fire and UL Commercial Burglary
installations.
1
✴
✴✴
✴
330
TouchTone with Rotary Backup
0 = disable
1 = enable
If enabled, the system reverts to rotary dialing if communicator is not
successful in dialing using TouchTone DTMF on first attempt.
1
✴
✴✴
✴
340
Communicator Split Reporting
0 = Split Reporting disabled
1 = Alarm, Alarm Restore, and Cancel
reports to primary, all others to secondary
2 = Open/Close and Test reports to
secondary, all other reports to primary
3 = Fire Alarms and Fire Restores to
primary, all others to secondary
Select the type of split reporting for system communication.
NOTE: See *51 for split/dual reporting combinations.
NOTE: Split reporting should not be used with Dynamic Signaling.