Setup guide

Section 5 – Data Field Descriptions
5-7
FIELD
TITLE and DATA ENTRIES EXPLANATION
0
800
Zone Type Restores for Zone
Types 9, 10 & 14
0 = disable
1 = enable
This field has three entries, one for each zone type. Select the zone types that
will send Restore reports.
Restores must be set to 1 for Commercial Fire installations.
0
830
First Test Report Time
Enter 00-07the for day (01 = Monday)
Enter 00-23 for the hour
Enter 00-59 for the minutes
Enter the day and time that the first Test report shall be transmitted. Enter 00
in all locations if the Test report is to be sent immediately upon exiting. Enter
00 in the day location if the report is to be sent at the next occurrence of the
time that is set.
0
840
Swinger Suppression (partition-
specific)
Enter 01-15.
Enter 00 for unlimited reports
This option limits the number of messages (alarms or troubles) sent for a
specific zone in an armed period. The system automatically resets the
shutdown for a zone after 48 hours if there are no trips on any zone.
Must be 00 for Commercial Fire and Burglary installations.
0
850
Enable Dialer Reports for Panics
& Duress (partition-specific)
0 = disable
1 = enable
This field has four entries as follows: Zone 995, 996, 999, and Duress Enable
for each partition that the panics and duress reporting is desired.
NOTE: Non-zero report code must be assigned to zone 992 (duress) to
enable Duress reporting.
0
870
Entry Warning (partition-specific)
0 = 3 short beeps
1 = slow continuous beeps
Select the type of warning for the entry delay period.
0
880
Burglary Alarm Communicator
Delay (partition-specific)
0 = no delay
1 = 16-second delay
Select the delay, if any, for burglary alarm communications.
Must be 0 for UL installations.
0
890
Alarm Restore Report Timing
0=Instant will send upon disarm or if zone
is restored.
1=Restore is sent at bell timeout if zone is
restored, if not it is sent at disarm
2=Restore is sent at disarm whether the
zone is restored or not.
Select the time when restore reports are sent after an alarm.
This field applies only to Burglary zone types. It does not apply to Fire or
Panic zone types.
Must beset to 2” for Commercial Burglary installations.
0
900
Secondary Subscriber Account
Number (partition-specific)
Enter 00-09; B-F (11-15)
Enter a 3- or 4-digit (depending on report format) primary subscriber account
number. Each number requires a 2-digit entry so as to allow entry of
hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data
only in the first three locations, and enter * in the fourth location.
NOTE: This field
must
be programmed if a secondary phone number is used
(field *34). This account number can be the same as the primary account
number.
1*12
Program Notification Signal
0 = no
1 = yes
If enabled, sends signal to central station indicating the system has been put
in programming mode.
Must be 1 for Commercial Fire installations.
1*13
System Sensor Reversing Relay
0 =use neither Zone 1 or Zone 2 inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2 inputs.
Selects zones for system sensor reversing relay.
Not Used.
1
170
Lobby Partition
0 = none
1-2 = partition number
Select the Common Lobby Partition.