Setup guide
VISTA-32FB Installation and Setup Guide
5-6
FIELD
TITLE and DATA ENTRIES EXPLANATION
0
✴
✴✴
✴
640
Alpha Numeric Pager Installed
Not Used. Must be set to “0”.
0
✴
✴✴
✴
650
Pager Phone Number for Alarms
Not Used. Must be set to “0”.
0
✴
✴✴
✴
660
Pager ID Number for Alarms
Not Used. Must be set to “0”.
0
✴
✴✴
✴
670
Pager Phone Number for
Supervision
Not Used. Must be set to “0”.
0
✴
✴✴
✴
680
Pager ID Number for Supervision
Not Used. Must be set to “0”.
0
✴
✴✴
✴
690
Pager Phone Number for
Bypasses
Not Used. Must be set to “0”.
0
✴
✴✴
✴
700
Pager ID Number for Bypasses
Not Used. Must be set to “0”.
0
✴
✴✴
✴
710
Pager Phone Number for
Opens/Closes
Not Used. Must be set to “0”.
0
✴
✴✴
✴
720
Pager ID Number for
Open/Closes
Not Used. Must be set to “0”.
0
✴
✴✴
✴
730
Pager Phone Number for System
Not Used. Must be set to “0”.
0
✴
✴✴
✴
740
Pager ID Number for System
Not Used. Must be set to “0”.
0
✴
✴✴
✴
750
Pager Phone Number for Test
Not Used. Must be set to “0”.
0
✴
✴✴
✴
760
Pager ID Number for Test
Not Used. Must be set to “0”.
*77
Auto Restore
0 = disable
1 = restore troubles only
2 = restore troubles and fire alarms
If set to 0 (disable), the operation is that restore reports will be sent to the CS
when the actual restoral on the zone occurs, however the keypad display will
remain showing the condition until a valid code is entered.
If set to 1 (restore troubles only), each trouble and supervisory condition
automatically clears the keypad display and stops the keypad beeping when
the zone returns to a “ready/normal” state. This applies to ALL trouble and
supervisory types. The system also sends the Trouble/Supervisory Restore
report to the central station, if programmed.
If a partition has more than one trouble/supervisory condition present at the
same time, the system automatically clears the keypad display of each zone
as it restores, but the keypad continues to beep until all the zones restore.
If set to 2 (restore troubles and fire alarms), silences and restores the keypad
when a trouble or fire alarm restores. If there are multiple alarms, it will only
restore when all zones are restored.
NOTES:
Must be set to “1” for Commercial Fire installations.
Option 2 is ONLY for use if the system is used as a slave communicator only,
and NOT if the system is used for Fire Alarm Detection.
0
✴
✴✴
✴
790
Zone Type Restores for Zone
Types 1-8
0 = disable
1 = enable
This field has eight entries, one for each zone type. Select the zone types that
will send Restore reports.