Setup guide
Section 5 – Data Field Descriptions
5-5
FIELD
TITLE and DATA ENTRIES EXPLANATION
0
✴
✴✴
✴
480
Low Speed Format (Secondary)
0 = ADEMCO Low Speed
1 = Sescoa/Radionics
Enter the low speed format for the secondary telephone number.
0
✴
✴✴
✴
490
Checksum Verification
Enter two digits, one for the primary and one
for the secondary.
0 = disable
1 = enable
If enabled, the system for either or both primary/secondary formats sends a
verification digit to validate the message at the receiver without having to send
two message rounds. Selection is valid for 3+1, 4+1, and 4+2 reports.
0
✴
✴✴
✴
500
Sescoa/Radionics Select
0 = disable
1 = enable
If disabled, selects Radionics, which uses hexadecimal 0-9, B-F reporting.
If enabled, selects Sescoa, which uses only numeric reporting (0-9).
NOTE: The selection applies to both primary and secondary phone numbers.
0
✴
✴✴
✴
510
Dual Reporting
0 = disable
1 = enable
If enabled, all reports are to be sent to both primary and secondary phone
numbers. This is required for line security in UL1610/365 installations.
NOTE: If used with Spilt Reporting "1" option (1*34), alarms and alarm
restores go to both primary and secondary numbers, while all other reports go
to secondary only. If used with Split Reporting "2" option, alarms and alarm
restores go to both, open/close and test messages go to secondary only,
while all other reports go to primary. If used with Split Reporting “3” option, fire
alarms and fire restore signals go to both, all other reports go to secondary
only.
NOTE: For Remote Station Applications, where separate transmission circuits
are required for Fire, Supervisory (when applicable) and Trouble signals, Split
Reporting, option 3, must be enabled.
0
✴
✴✴
✴
520
Standard/Expanded Reporting
Primary
0 = disable
1 = enable
This field has six entries as follows: Alarm, Restore, Bypass, Trouble,
Open/Close, Low Battery. If enabled, expanded reports are sent to the
primary phone number if low speed format is selected in field *45.
NOTE: Expanded overrides 4+2 format.
0
✴
✴✴
✴
530
Standard/Expanded Reporting
Secondary
0 = disable
1 = enable
This field has six entries as follows: Alarm, Restore, Bypass, Trouble,
Open/Close, Low Battery. If enabled, expanded reports are sent to the
secondary phone number if low speed format is selected in field *47.
NOTE: Expanded overrides 4+2 format.
0
✴
✴✴
✴
560
Dynamic Signaling Delay
Enter 00-15 times 15 seconds.
Select the time the panel should wait for acknowledgment from the first
reporting destination before it attempts to send a message to the second
destination (first and second destinations are determined in field
✳57).
NOTES: A minimum of 45 seconds is recommended when the Communicator
is set to be the primary report path. If the delay were short (30 seconds or
less), the Communications Device does not have enough time to send the
acknowledgement back to the panel, therefore the report would be sent out
via the dialer.
If the acknowledgment is received before the delay time expires, no message
is sent to the second destination.
0
✴
✴✴
✴
570
Dynamic Signaling Priority
0 = Primary Dialer
1 = Communicator
Select the initial reporting path for central station messages.
0
✴
✴✴
✴
580
Communicator Central Station #1
Category Enable
0 = disable
1 = enable
This field has six entries as follows: Alarm, Trouble, Bypass, Open/Close,
System, and Test. If enabled, the reports are sent to the primary subscriber ID
of the Communicator.
0
✴
✴✴
✴
590
Communicator Central Station #2
Category Enable
0 = disable
1 = enable
This field has six entries as follows: Alarm, Trouble, Bypass, Open/Close,
System, and Test. If enabled, the reports are sent to the secondary subscriber
ID of the Communicator.