Setup guide
VISTA-32FB Installation and Setup Guide
3-22
U
L
• Relays should not re-energize until the panel is fully reset.
• For Commercial Fire installations, onl
y
one notification appliance module ma
y
be used, and onl
y
one notification
appliance output (A or B) may be used on that module.
• If the 4204CF relay is enabled for a NAC, it must follow the action of the NAC on the panel.
• Relays (aux and 4204's) cannot be used for off-premises signaling.
• In Commercial Fire installations, the 4204CF cannot be used to drive sounders in the same physical area as
sounders connected to the alarm outputs of the control panel.
• Output devices are not intended for overriding automatic building and fire functions.
To install the relay modules, see Figures 3-20 and 3-21 and perform the following steps:
Step Action
1
Set the 4204 or 4204CF’s DIP switches for a device address 01-15.
Do not use an address being used by another device (keypads, RF receivers, etc.).
2 Mount the 4204 and 4204CF modules per the instructions provided with them.
3 Connect the module’s wire harness to the control (11, 12, 13 and 14). Plug the connector on the harness to
the module.
When mounting remotely, homerun each module to the control. The table below shows the maximum wire
run lengths. Refer to the instructions provided with the 4204CF for its maximum permissible wire lengths.
Wire Gauge Maximum Length
#22 125 feet
#20 200 feet
#18 300 feet
#16 500 feet
4204 ADDRESS SETTINGSSWITCH
NUMBER
("—" means "OFF")
0
1
1 2 3 4 5 6 7 8 9 101112131415
2
ON — ON — ON — ON — ON — ON — ON — ON —
3
ON ON ——ON ON ——ON ON ——ON ON ——
4
ON ON ON ON ————ON ON ON ON ————
5
ON ON ON ON ON ON ON ON ————————
12345
➞
➞
➞
➞
➞
➞
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
OFF ON
TB1
4204
TB2
4-PIN
CONSOLE
PLUG
12
11
10
9
8
7
6
5
4
3
2
1
RELAY
2
RELAY
1
RELAY
3
RELAY
4
TYPICAL
(SHOWN "OFF")
EITHER OR BOTH
CAN BE USED
DATA IN FROM
CONTROL
(–) GROUND
DATA OUT
TO CONTROL
(+) 12V
YEL
BLK
GRN
RED
SWITCH SHOWN
FOR ADDRESS "0"
DIP SWITCH FOR
SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING
TAMPER
COVER
TAMPER
(REED)
SWITCH
13 14 15 16
4204-01-V1
NOT USED
Figure 3-20: 4204 Relay Module
4204CF ADDRESS SETTINGS
SWITCH
NUMBER
("—" means "OFF")
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2
ON — ON — ON — ON — ON — ON — ON — ON —
3
ON ON ——ON ON ——ON ON ——ON ON ——
4
ON ON ON ON ————ON ON ON ON ————
5
ON ON ON ON ON ON ON ON —————— ——
12 3 4 5
OFF ON
DIP SWITCH:
WHITE AREAS DENOTE SWITCH HANDLES
POSITION 1
ENABLES/DISABLES COVER TAMPER
ON = TAMPER DISABLED; OFF = TAMPER ENABLED
SHOWN DISABLED (AS SHIPPED).
POSITIONS 2-5
DETERMINE 4204CF'S ADDRESS:
CONTROL'S INSTRUCTIONS SPECIFY ADDRESS TO
USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED).
COVER TAMPER (REED) SWITCH
DIP SWITCH
FOR SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING TAMPER
4-PIN CONSOLE
PLUG
12VDC; SUPPLIES POWER TO MODULE CIRCUITRY (INCLUDING APPLIANCE OUTPUT
RELAY COILS). CURRENT DRAIN AT 12V IS: 25mA + (80mA PER ACTIVE OUTPUT).
DATA IN FROM CONTROL
DATA OUT TO CONTROL
GROUND
POLARIZED
NOTIFICATION
APPLIANCES
CONNECT TO A POWER-LIMITED 12V REGULATED
UL1481 LISTED POWER SUPPLY.
ALARM POLARITY SHOWN
EACH OUTPUT PROVIDES
STYLE Y SUPERVISION
NOTIFICATION
APPLIANCE
OUTPUT B
2K EOLR
EOL20
NOTIFICATION
APPLIANCE
OUTPUT A
2K EOLR
EOL20
EACH OUTPUT RATED 1.2A MAX
4204CF
4204CF-004-V1
EITHER OR BOTH
CAN BE USED
NOTIFICATION APPLIANCE AND CONSOLE DATA
OUTPUTS ARE POWER-LIMITED.
ALL POWER-LIMITED WIRING MUST BE SEPARATED
FROM NON-POWER-LIMITED AND HIGH-VOLTAGE
WIRING BY 1/4" (6.4mm).
ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED
WHEN POWERED BY THE CONTROL PANEL.
NFPA-72 COMPLIANT.
RED
GRN
BLK
YEL
NC
NC
NC
NC
NC
NC
TB2
FOR UL COMMERCIAL FIRE INSTALLATIONS, ONLY ONE NOTIFICATION APPLIANCE
MODULE MAY BE USED, AND ONLY ONE NOTIFICATION APPLIANCE OUTPUT (A or B)
MAY BE USED ON THAT MODULE.
TB1
13
16
1
2
8
7
12
10
11
9
6
5
4
3
1514
Figure 3-21: 4204CF Relay Module