Setup guide

Section 3 – Installing the Control
3-15
+
-
-
+
-
+
EOL
POWER
SUPERVISION
RELAY
MODULE
EOLR-1
4-WIRE SMOKE
DETECTORS
2000
OHM
EOLR
HEAT
DETECTOR
+
BLK
+
-
CONTROL PANEL
ZONE TERMINALS
OR POLLING LOOP
EXPANDER ZONE
TERMINALS
(e.g. 4208SNF)
12
11
10
9
N.O.
POLE
N.C.
Aux. Pwr 1
CONTROL
P
ANEL
SHOWN POWERED.
RELAY OPENS WHEN
POWER IS LOST
AUXILIARY RELAY
8
7
+
Keypad Prt 1
4_wiresmk-005-V0
Figure 3-13: 4-Wire Smoke Detectors
Zone 6 Tamper Configuration
Zone 6 may be used as a tamper loop for the VISTA-32FB Cabinet Door Tamper Switch.
Assign zone 6 to a burglary partition. Program it for day trouble/night alarm (zone type 5) when only one burglary
partition is used. Program it for 24-hr. audible alarm (zone type 7) when more than one burglary partition is used.
Enable the Zone 6 Alternate Tamper Function (program field 3
17.
Using 2-Wire Latching Glassbreaks on Zone 8
Zone 8 can support 2-wire glassbreak detectors. The zone provides enough standby current to power up to 50 2-wire
glassbreak detectors meeting the requirements listed below.
Compatible Glassbreak Detectors
Use detectors that meet the following ratings:
Standby Voltage: 5VDC13.8VDC
Standby Resistance:
Greater than 20k ohms (equivalent resistance of all detectors in parallel)
Alarm Resistance:
Less than 1.1k ohms (see note below)
Alarm Current:
2mA10mA
Reset Time:
Less than 6 seconds
NOTES:
You can use detectors that exceed 1.1k ohms in alarm, provided they maintain a voltage drop of less than 3.8 volts in
alarm.
The IEI 735L Series detectors have been tested and found to be compatible with these ratings.
The alarm current provided by zone 8 supports only one glassbreak detector in the alarmed state.
Do not use other N.O. or N.C. contacts when using glassbreak detectors on zone 8. Other contacts may
prevent proper glassbreak detector operation.
To wire 2-wire latching glassbreak detectors to zone 8, perform the following steps:
Step Action
1 Select compatible 2-wire glassbreak detectors that meet the requirements stated previously.
2 Connect detectors across zone 8 (terminals 27 and 28). See Figure 3-14.
3
Connect the EOL resistor at the last detector in the loop across the zone’s terminals. You must connect the
EOL resistor across the loop wires at the last detector.