Setup guide

VISTA-32FB Installation and Setup Guide
3-14
ZONE 1
2-WIRE SMOKE
DETECTOR
SMOKE
2000 OHMS
EOLR
15
16
2_wiresmk-001-V0
Figure 3-12: 2-Wire Smoke Detector on Zone 1 (for zone 2 use terminals 17 & 18)
Using 4-Wire Smoke Detectors on Zones 1-8
You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary Power output without
exceeding the output's rating (1A).
Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be
momentarily interrupted using either the auxiliary relay or a 4204 Relay Module.
Compatible 4-Wire Smoke Detectors
Use any UL Listed 4-wire smoke detector that is rated for 12VDC operation and that has alarm reset time not exceeding
6 seconds. Some compatible 4-wire smoke detectors are listed below
DETECTOR TYPE MANUFACTURER MODEL #
4-Wire Photoelectric Smoke Detector DSC FSA-410B
4-Wier Photoelectric Smoke Detector w/Heat Detector DSC FSA-410BT
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector DSC FSA-410BST
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector DSC FSA-410BRT
4-Wire Photoelectric Smoke w/Aux. Relay, Sounder & Heat Detector DSC FSA-410BRST
End of Line Power Supervision Relay for FSA-410 Series Smoke Detectors DSC RM-2
Polarity reversal module for FSA-410 series Smoke Detectors DSC PRM-4WC
4-Wire Photoelectric Smoke Detector System Sensor 4W-B
4-Wire Photoelectric Smoke Detector w/Heat Detector System Sensor 4WT-B
4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector System Sensor 4WTA-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector System Sensor 4WTR-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Heat Detector System Sensor 4WTAR-B
4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Isolated Heat Detector System Sensor 4WITAR-B
4-Wire Photoelectric Air Duct Smoke Detector, Extended Air Speed Range System Sensor DH100ACDCLP
4-Wire Ionization Air Duct Smoke Detector System Sensor DH100ACDCI
Wiring 4-Wire Smoke Detectors
U
L
Power to 4-wire smoke detectors must be supervised with an EOL device (use a System Sensor EOLR-1) relay
module connected as shown in
Figure 3-13
).
A combination of heat detectors and smoke detectors is not permitted on a zone programmed for fire verification.
Fire installations require the use of a synchronization module to synchronize the sounders and strobes on the
system.
To wire 4-wire smoke detectors to zones 1-8, perform the following steps:
Step Action
1 Select 4-wire smoke detectors (see list of compatible detectors shown previously in this section).
2 Connect detectors (including heat detectors, if used) across terminals of the zone selected. All detectors must
be wired in parallel. See Figure 3-13.
3
Connect the EOLR at the last detector in the loop across the zone’s terminals. You must connect the
EOLR across the loop wires at the last detector.