Setup guide
VISTA-32FB Installation and Setup Guide
3-10
Mfg
Alarm Indicating
Device Type Model
Candela
Setting Horn Setting
Max # of
Devices
System Sensor Horn, Strobe12/24V PC2RHK 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC2W 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC2WH 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC4R 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC4RH 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC4RK 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC4RHK 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC4W 15 Temporal - High 10
System Sensor Horn, Strobe12/24V PC4WH 15 Temporal - High 10
System Sensor Strobe12/24V SR 15 Temporal - High 10
System Sensor Strobe12/24V SRH 15 Temporal - High 10
System Sensor Strobe12/24V SRK 15 Temporal - High 10
System Sensor Strobe12/24V SRHK 15 Temporal - High 10
System Sensor Strobe12/24V SW 15 Temporal - High 10
System Sensor Strobe12/24V SWH 15 Temporal - High 10
System Sensor Strobe12/24V SCR 15 Temporal - High 10
System Sensor Strobe12/24V SCRH 15 Temporal - High 10
System Sensor Strobe12/24V SCRK 15 Temporal - High 10
System Sensor Strobe12/24V SCRHK 15 Temporal - High 10
System Sensor Strobe12/24V SCW 15 Temporal - High 10
System Sensor Strobe12/24V SCWH 15 Temporal - High 10
System Sensor Speaker SP200W - NA NA
System Sensor Speaker SP201R - NA NA
System Sensor Speaker SP201W - NA NA
System Sensor Speaker/Strobe SP2C2415 15 NA 10
System Sensor Speaker/Strobe SP2C241575 15/75 NA 10
System Sensor Speaker/Strobe SP2C2430 30 NA 10
System Sensor Speaker/Strobe SP2C2475 75 NA 8
System Sensor Speaker/Strobe SP2C2495 95 NA 6
System Sensor Speaker/Strobe SP2C24115 115 NA 5
System Sensor Speaker/Strobe SP2C24177 177 NA 3
System Sensor Speaker/Strobe SP2R1224M - - -
Wheelock Horn Strobe 12V, 4W MT-121575W 15 Continuous/Hi 4
Wheelock Horn Strobe 12V, 2W AS-121575W 15 Continuous/Hi 6
Wheelock Strobe 12V RSS-121575W 15 na 6
Wheelock Horn Strobe 12V, 2W NS-121575W 15 Hi 7
Wheelock Horn 12V/24V NH-12/24 na Hi 80
Wheelock Horn 12V AH-12 na Hi 9
Wheelock Horn 12V/24V MT-12/24,MT4-12/24 na Continuous Horn 10
Wheelock Bell 12V MB-G6-12,MB-G10-12 na na 9
Supervising the Notification Appliance Circuits
To wire the NAC using the supervision feature, install a 2K EOL resistor (Model 2EOL, supplied) across the last
notification appliance on each Notification Appliance Circuit to be supervised.
Auxiliary Relay Connections
The VISTA-32FB provides a built-in Form C relay with contacts rated at 28VAC/VDC, 2.8A. The relay may be
programmed (field 3✳61) for one of the following functions:
• Alarm Activation
• Trouble/Supervisory Activation
• 4-Wire Smoke Detector Reset
• Battery Saver
Alarm Activation
(3
✳61 = 1 or 4) Steady activation in response to an alarm.
If field 3
✳61 = 1, the auxiliary relay remains active until Aux. Relay Timeout expires or until User Code + OFF is
entered. This option can be used to provide an unsupervised Notification Appliance Circuit for supplementary strobes,
sounders, etc. when wired to the Aux Power 1 or a separate power supply, see Figure 3-10.
If field 3
✳61 = 4, the auxiliary relay remains activated until User Code + # + 67 is entered. By default, the relay is set
to activate on alarm zones 1-8 with no timeout (field 3✳61 = 1).
When field 3
✳61 = 1, the auxiliary relay can be programmed to give a brief activation for confirmation of arming ding
(field 3✳57) or Chime Mode (field 3✳59).