Setup guide

VISTA-32FB Installation and Setup Guide
3-4
Mercantile Safe and Vault Listing Guidelines
Follow the guidelines given above for Mercantile Premises listing.
For safe and vault installations, a Listed tamper switch, must be installed on the cabinet backbox to protect the
cabinet from being removed from the wall. This device must also be connected to zone 6.
Commercial Fire Guidelines
For Commercial Fire installations, the following requirements apply (See Figure 3-5).
System components mounted inside the cabinet must be placed so that all power-limited wiring is separated from all
non-power-limited wiring (AC and battery) by a minimum of ¼-inch (6.4mm).
Non-power-limited wiring that exits the control panel (i.e., transformer wiring) must be run in conduit.
All unused knockouts must be plugged.
All wiring that exits the control panel must be strain-relieved (e.g., tie-wrapped).
WIRES MUST BE
RUN IN CONDUIT
PC
BOARD
BATTERY BATTERY
ZONE
WIRING
TELCO
LINE
fire_burg_cab-003-V0
FROM
TRANSFORMER
PLATE
TIE WRAPS
TIE WRAPS
TIE WRAPS
NOTE: ALL POWER-LIMITED
WIRING MUST BE SEPARATED
FROM NON-POWER LIMITED
AND HIGH VOLTAGE WIRING
BY 1/4-INCH (6.4 mm)
Figure 3-5: Commercial Fire Installation Using Attack-Proof Cabinet
Installing the Control's Circuit Board
To install the circuit board in the cabinet, perform the following steps:
Step Action
1
Confirm the Mounting Plate is installed securely in the cabinet (Figure 3-6, Detail A). Install the nylon
standoffs (supplied) into the top corner holes of the mounting plate (Detail B.) Insert the top of the circuit
board onto the two standoffs at the top of the mounting plate.
2
Place the board flat and secure to the mounting plate with the three accompanying screws and spacers as
shown (Detail C.)
NOTES:
Make sure that the tabs on the side of the plate did not pop out during shipping and are inserted into the
appropriate slots.
Make sure that the mounting screws are tight. This ensures that there is a good ground connection between the PC
board and the cabinet.
Dress field wiring away from the microprocessor (center) section of the PC board. Use the mounting plate brackets
on the left and right sidewalls of the cabinet for anchoring field wiring using tie wraps (Figure 3-3).These steps are
important to minimize the risk of panel RF interference with television reception.