Setup guide

A-1
APPENDIX A
Regulatory Agency Statements
••••••••••••••••••••••••••••••••••••••••••••••••
UL Installation Requirements
U
L
This system may be used in installations that require UL2050 compliance.
Commercial Burglary Requirements
1. All partitions must be owned and managed by the same person(s).
2. All partitions must be part of one building at one street address.
3. The audible alarm device(s) must be placed where it/they can be heard by all partitions.
4. The control cabinet must be protected from unauthorized access. This can be done by installing a
tamper switch on the cabinet door (supplied with the attack-proof cabinet). Wire the selected device to
zone 6. Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07)
response. The 24-hour alarm response must be used for multiple partitioned systems.
UL864/NFPA Local Fire
1. Configure at least one Notification Appliance Circuit for supervision and wire polarized fire alarm
indicators to it.
2. Size the battery for 24-hour backup.
UL864/NFPA Central Station and Remote Station Fire
1. Size the backup battery for 24-hour standby time.
2. For central station service, you may use the 7845i-ent communications device alone, the main dialer
with a communications device, or the main dialer with the 5140DLM Backup Dialer Module. For remote
station service, you must use the main dialer with the 5140DLM Backup Dialer Module.
3. When the main dialer is used, enable it (field 3*30) and connect it to a telephone line. Assign a 24-hour
trouble response (type 19) to system Zone 974 to enable main dialer supervision. The control panel will
activate the trouble trigger when it detects a main dialer supervision fault.
4. When the backup dialer is used, install it on the control panel’s PCB shield as indicated in the Summary
of Connections diagram. Enable it (field 3*30) and connect it to a separate telephone line. Assign a 24-
hour trouble response (type 19) to system Zone 975 to enable backup dialer supervision.
5. When the dialer is used, program it to send fire alarm, fire supervisory (if used), trouble, AC loss, low
battery, normal dialer test, and off-normal dialer test reports. Field *27 must be set to "024" maximum
so that test reports are sent at least once every 24 hours.
6. If a secondary number is programmed, set the maximum number of dialer retries to 3, 4, or 5 in field
3*21.