VISTA SERIES VISTA-32FB Commercial Fire and Burglary Partitioned Security System With Scheduling Installation and Setup Guide K3521V4 10/09 Rev A
ii
. Table of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information ............................................................................................................................................ ix Programming Field Settings for UL864 Compliance .......................................................................................... ix SECTION 1: General Description ......................................................
Table of Contents SECTION 6: Scheduling Options................................................................................................. 6-1 Time Window Definitions ..................................................................................................................................6-2 Open/Close Schedules Definitions ...................................................................................................................6-3 Scheduling Menu Mode ...............................
UL365 Police Station Connected Burglar Alarm.............................................................................................. A-2 UL1610 Central Station Burglary Alarm........................................................................................................... A-2 APPENDIX B : Summary of System Commands .......................................................................B-1 APPENDIX C: Specifications .............................................................................
List of Figures • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • FIGURE 1-1: ISOLATING FIRE DEVICES FROM BURGLARY DEVICES............................................................1-4 FIGURE 3-1: INSTALLING THE LOCK .................................................................................................................3-1 FIGURE 3-2: SEPARATION OF CIRCUITS .............................................................................................
Conventions Used in This Manual • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Before you begin using this manual, it is important that you understand the meaning of the following symbols (icons). UL These notes include specific information that must be followed if you are installing this system for a UL Listed application.
VISTA-32FB Installation and Setup Guide viii
UL864 (Commercial Fire) Compliance • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information The VISTA-32FB control panel provides features that allow the system to meet UL864 Commercial Fire requirements. To meet these requirements, follow the guidelines outlined in this section. • • • • • • • • • The reporting of bypassed points to the central station must be enabled in Report Code Programming mode.
VISTA-32FB Installation and Setup Guide Program feature or option Possible settings Permitted in UL864? Y/N Settings permitted in UL 864 ✱27 TEST REPORT INTERVAL Y Enter 0001-9999 for the test report interval in hours. Enter 0000 for test reporting. Must be set to “0024” (Maximum 24 hours) ✱28 POWERUP IN PREVIOUS STATE Y 0 = disable 1 = enable Must be set to “1” (enable). ✱37 DOWNLOAD COMMAND ENABLES N 0 = disable 1 = enable Must be set to “0” for all entries (disable).
Possible settings Program feature or option Permitted in UL864? Y/N Settings permitted in UL 864 1✱28 RF TRANSMITTER LOW BATTERY SOUND N 0 = disarmed state only 1 = both armed and disarmed states Must be set to “1” (both armed and disarmed states). 1✱29 RF TRANSMITTER LOW BATTERY REPORTING N 0 = disable 1 = enable Must be set to “1” (enable).
VISTA-32FB Installation and Setup Guide Program feature or option Permitted in UL864? Y/N Possible settings Settings permitted in UL 864 2✱18 ENABLE GOTO FOR THIS PARTITION (partition-specific) N 0 = disable 1 = enable Must be set to “0” (disable) for partition 1. 2✱21 SUPERVISION PULSES FOR COMMUNICATIONS DEVICE N 0 = disable 1 = enable Not used. Must be set to “00000” (disable).
Program feature or option Permitted in UL864? Y/N Possible settings Settings permitted in UL 864 3✱50 ZONE TYPE RESTORE ENABLES FOR TYPES 16-18 N 0 = disable 1 = enable Must be set to “1” (enable). 3✱59 ENABLE BELL 2 & AUXILIARY RELAY CHIME ANNUNCIATION N 0 = disable 1 = enable Must be set to “0” (disable) if Bell 2 or Aux Relay is used for Fire. 3✱60 BELL 2 & AUX RELAY TIMEOUT Y Enter 01-15 multiplied by 2 minutes. 00 = no timeout. Must be set to “3” (Minimum of 6 minutes).
VISTA-32FB Installation and Setup Guide xiv
S E C T I O N 1 General Description • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About the VISTA-32FB The VISTA-32FB is a two-partition, UL Listed Commercial Fire and Burglary control panel. The Control can also be used as a slave communicator in conjunction with an external fire alarm panel: For use as a slave communicator, refer to Section 11 of this manual.
VISTA-32FB Installation and Setup Guide System Communication • Provides supervision of the phone lines (main and backup) • Supports the 5140DLM optional backup dialer for the second phone line. • Supports ADEMCO Contact ID; ADEMCO High Speed; ADEMCO Express; and 3+1, 4+1, and 4+2 ADEMCO and Sescoa/Radionics Low-Speed formats. The system is shipped defaulted for Contact ID communication. It is the only format capable of uniquely reporting all 32 zones, as well as openings and closings for all 75 users.
Section 1 – General Description Guidelines for Wiring a System The installer must keep certain guidelines in mind while installing a system. The Vista-32FB contains an ECP bus and a polling loop bus for connecting Fire and Burglary devices. When installing a Fire ONLY system or Burglary ONLY system both busses may be used interchangeably. When installing a Commercial Fire and Burglary System all Fire devices must be isolated from the Burglary devices.
PRIMARY KEYPAD 6160CR-2 BLACK - BLACK - RED + USE CABLE 4142TR (SUPPLIED) YELLOW DATA GREEN DATA BLACK - RED + YELLOW DATA GREEN DATA BLACK - RED + ECP BUS 11 12 13 14 VISTA-32FB PANEL GREEN DATA RED + Figure 1-1: Isolating Fire Devices from Burglary Devices LOOP DEVICES THAT ARE USING ONLY 2-WIRE CONNECTIONS. 3. POLLING LOOP TERMINAL 29 CAN BE USED FOR POLLING MUST BE EITHER ALL FIRE OR ALL BURGLARY. NO COMBINATION OF FIRE/BURGLARY DEVICES IS PERMITTED. 2.
S E C T I O N 2 Partitioning • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Theory of Partitioning This system provides the ability to arm and disarm up to two different areas, as if each had its own control. These areas are called partitions. A Partitioned system allows the user to disarm certain areas while leaving other areas armed, or to limit access to certain areas to specific individuals.
VISTA-32FB Installation and Setup Guide Common Lobby Logic When an installation consists of a partition shared by users of other partitions in a building, that shared partition may be assigned as the "common lobby" partition for the system (program field 1*17). An example of this might be in a medical building where there are two doctors’ offices and a common entrance area (see example that follows explanation). The Common Lobby feature employs logic for automatic arming and disarming of the common lobby.
Section 2 – Partitioning Sequence #1: Office 1 Office 2 Lobby Action User #1: Disarms (Armed) Disarms User #2: (Disarmed) Disarms No Change User #1: Arms (Disarmed) No change User #2: (Armed) Arms Arms Sequence #2: Office 1 Office 2 Lobby Action User #2: (Armed) Disarms Disarms User #1: Disarms (Disarmed) (No change) User #2: (Disarmed) Arms No Change User #1: Arms (Armed) No Change Notice that in sequence #1, because Office #2 was the last to arm, the lobby also armed
VISTA-32FB Installation and Setup Guide Master Keypad Setup and Operation Although this system has two actual partitions, it provides an extra partition strictly for the purpose of assigning keypads as Master keypads for the system. Assigning any keypad to Partition 3 in Device Programming in the #93 Menu Mode makes that keypad a Master keypad. A Master keypad reflects the status of the entire system (Partitions 1-2) on its display at one time.
S E C T I O N 3 Installing the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring the control panel and all the peripheral devices. The control panel comes in two cabinet configurations; one for Commercial Fire only and one for Commercial Fire and Commercial Burglary with cabinet attack resistance considerations.
VISTA-32FB Installation and Setup Guide TELCO LINE DETAIL A NOT TO SCALE ZONE AND BELL WIRING MAKE SURE THAT TERMINAL 2 (XFMR SECONDARY WIRE) AND TERMINAL 3 (BELL WIRE) ARE TERMINATED AS SHOWN TO MAINTAIN 1/4" MIN. SPACING. FUSE TIE WRAP TO CABINET NOTE: NON POWER-LIMITED WIRING (AC, BATTERY) MUST BE SEPARATED FROM POWER-LIMITED WIRING (ZONES, BELLS, ECP, POLLING LOOP) BY 1/4-INCH (6.
Section 3 – Installing the Control Mounting the Control in the Attack-Proof Cabinet (Suitable for Commercial Fire/Commercial Burglary Applications) If you are installing a Vista-32FB in the attack-proof cabinet with the external transformer, follow the steps below. Step Action 1 Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using. DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED.
VISTA-32FB Installation and Setup Guide Mercantile Safe and Vault Listing Guidelines • Follow the guidelines given above for Mercantile Premises listing. • For safe and vault installations, a Listed tamper switch, must be installed on the cabinet backbox to protect the cabinet from being removed from the wall. This device must also be connected to zone 6. Commercial Fire Guidelines For Commercial Fire installations, the following requirements apply (See Figure 3-5).
Section 3 – Installing the Control CABINET PLATE DETAIL B INSTALLING NYLON STANDOFFS (2) CABINET PLATE CABINET PLATE PC BOARD MOUNTING SCREW DETAIL A SIDE VIEW OF ATTACHMENT SPACER DETAIL C SIDE VIEW, PC BOARD INSTALLATION USING SPACERS (3) AND MOUNTING SCREWS (3) fire_burg_cab-002-V1 Figure 3-6: Mounting the PC Board in Attack-Proof Cabinet Installing the Keypads • Up to 31 addressable keypads (addresses 00-30) may be used (you may need to use an auxiliary power supply if the 1A aux.
VISTA-32FB Installation and Setup Guide Commercial Fire Requirements For commercial fire installations, the primary fire keypad must be installed on panel Keypad Port 2 and mounted within 20 feet of the control panel. External wiring must be run in conduit. Additionally, you can install supplemental fire keypads and devices on ECP Port 1, using an ECP Isolator to separate all fire wiring from all burglary wiring (see Figure 3-8).
Section 3 – Installing the Control Installing External Sounders The VISTA-32FB provides two Notification Appliance Circuits. Each circuit is rated as Special Application for Fire and 10VDC – 14VDC, 1.7A max., power-limited for Burglary. NOTE: The total alarm current drawn from Auxiliary Power 1, Auxiliary Power 2, polling loop, Bell 1, and Bell 2 cannot exceed 2.3A for battery-independent operation.
VISTA-32FB Installation and Setup Guide ALARM INDICATING DEVICE TYPE 2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red 2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red 2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor 2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor 2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White 2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White 4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red 4-Wire
Section 3 – Installing the Control Mfg System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sens
VISTA-32FB Installation and Setup Guide Mfg System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor Wheelock Wheelock Wh
Section 3 – Installing the Control ALARM 7 8 10 11 12 GROUND AUX PWR #1 N.C. N.O. NOTES: USE NON-POLARIZED INDICATING DEVICES. WIRING IS NOT SUPERVISED. DO NOT EXCEED RATINGS OF THE SUPPLY USED. IF AUX. PWR. 1 OUTPUT IS USED, THE COMBINED ALARM CURRENT DRAIN FROM AUX. PWR. 2, BELL 1, AND BELL 2 CANNOT EXCEED 2.3A MAX. 9 POLE AUX RELAY FACTORY DEFAULTS ACTIVATES FOR ZONES 1-8 ALARMS (STEADY ALARM OUTPUT). NO TIMEOUT. + belloutput-005-V0 CAN DRAW POWER FROM AUX. PWR.
VISTA-32FB Installation and Setup Guide Main Dialer Connections To connect the main dialer, refer to the Summary of Connections diagram and perform the following steps: Step Action 1 Connect the main dialer to the telephone company lines using the RJ31X cable supplied. 2 If the dialer output is connected to telephone lines that have a telephone company MTU installed, cut the blue jumper (W6).
Section 3 – Installing the Control Wiring Burglary and Panic Devices to Zones 1-8 The maximum zone resistance is 100 ohms for zones 1, 2 and 8, and 300 ohms for all other zones (excluding the 2K EOL resistor). To wire burglary and panic devices to zones 1-8, connect sensors/contacts to the hardwire zone terminals (15 through 27). Connect N.C. and N.O. devices as follows: • Connect N.C. devices in series with the high (+) side of the loop.
VISTA-32FB Installation and Setup Guide ZONE 1 16 2_wiresmk-001-V0 SMOKE 2000 OHMS EOLR 15 2-WIRE SMOKE DETECTOR Figure 3-12: 2-Wire Smoke Detector on Zone 1 (for zone 2 use terminals 17 & 18) Using 4-Wire Smoke Detectors on Zones 1-8 You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary Power output without exceeding the output's rating (1A).
Section 3 – Installing the Control AUXILIARY RELAY 7 N.O. POLE 8 N.C. 9 Aux. Pwr 1 10 + + 11 Keypad Prt 1 12 BLK - – • • + 4-WIRE SMOKE DETECTORS + + - - EOL POWER SUPERVISION RELAY MODULE EOLR-1 CONTROL PANEL SHOWN POWERED. RELAY OPENS WHEN POWER IS LOST CONTROL PANEL ZONE TERMINALS OR POLLING LOOP EXPANDER ZONE TERMINALS (e.g.
VISTA-32FB Installation and Setup Guide 2000 OHMS EOLR ZONE 8 27 (+) 26 (-) LATCHING TYPE GLASS BREAK DETECTOR LOOP glass_conn-001-V0 GLASSBREAK DETECTOR Figure 3-14: Wiring Latching Glassbreaks to Zone 8 Installing V-Plex Devices The polling loop provides both power and data to the V-Plex devices, and is constantly monitoring the status of all zones enabled on the loop.
Section 3 – Installing the Control Model Number Type 998MX Serialized PIR Quest 2260SN IS2500SN Vplex-VSI Serialized PIR V-Plex PIR V-plex Short Isolator NOTE: If using the new 5193SD/SDT V-Plex smoke detectors (or older 5192SD/SDT with the maintenance DIP sw enabled) the "Smart" option must be selected in zone programming or when they enroll unpredictable results may occur if the smoke goes into a High Sen or Low Sens condition.
VISTA-32FB Installation and Setup Guide Using the 4297 Polling Loop Extender The 4297 Polling Loop Extender may be used to provide additional polling loop current, to extend the polling loop wire run length, and/or to provide individual electrically isolated polling loops. Refer to Figures 3-16 and 3-17, to follow. ! DO NOT use the 4197 Polling Loop Extender module with the VISTA-32FB.
Section 3 – Installing the Control Wireless Zone Expansion The following table lists the receivers that may be used and the number of zones they support. UL • • The 5881ENHC RF Receiver is listed for Commercial Fire and Commercial Burglary applications. The 5883H is UL Listed for Commercial Fire applications only. All other RF receivers are not UL Listed for Commercial applications. For Commercial Fire installations the Receiver(s) must be mounted in a 5800BOX.
VISTA-32FB Installation and Setup Guide Take note of the address you select for the RF receiver, as this address must be enabled in the system’s Device Programming in the #93 Menu Mode. To install the RF receiver, perform the following steps: Step Action 1 Mount the receiver, following the advisories stated previously. NOTE: Must be mounted in a 5800Box Enclosure for Fire applications. 2 Set the DIP switches in the receiver for the address (01-07). See Figure 3-19.
Section 3 – Installing the Control 5800 Series Transmitter Setup • Transmitters have built-in serial numbers that must be enrolled in the system using the #93 Menu Mode Programming, or via the downloader. • Some transmitters can support more than one “zone” (loops or inputs) (e.g., 5817CB). Each loop must be assigned a different zone number. Transmitter Supervision Supervised RF transmitters send a check-in signal to the receiver at 70–90 minute intervals.
VISTA-32FB Installation and Setup Guide UL • • • • • • Relays should not re-energize until the panel is fully reset. For Commercial Fire installations, only one notification appliance module may be used, and only one notification appliance output (A or B) may be used on that module. If the 4204CF relay is enabled for a NAC, it must follow the action of the NAC on the panel. Relays (aux and 4204's) cannot be used for off-premises signaling.
Section 3 – Installing the Control Installing 4101SN Relay Modules The 4101SN V-Plex Single Output Relay Module is a serial number polling loop output device. The 4101SN features the following: The position of the relay is supervised, but not the actual external contact wiring. • • • • Form C relay contacts rated at 2A, 28VAC/VDC with contact supervision. One class B/style B EOLR-supervised auxiliary input zone. Operating power and communication with control panels via the V-Plex polling loop.
VISTA-32FB Installation and Setup Guide Wiring for the Remote Keyswitch To install the Honeywell 4146 keyswitch, perform the following steps: Step Action 1 Connect the Honeywell 4146 to the panel as shown in Figure 3-22. 2 If you are using the tamper, make sure it is connected to a zone. (ARMED) RED 820 OHMS TO OUT 1 (J2 PIN 7) TO GND (J2 PIN 8) (READY) GREEN 820 OHMS TO OUT 5 (J2 PIN 6) TO ZONE 8 + (TERM 27) 2000 OHMS TO ZONE 7/ZONE 8 - (TERM 26) TAMPER SWITCH (N.C.) LOCK SWITCH (N.O.
Section 3 – Installing the Control Operation The VISTA-32FB features Dynamic Signaling Delay and Dynamic Signaling Priority message reporting when a Communications Device is used. These message outputs are accessed through data fields ✱56 and ✱57, respectively. The Dynamic Signaling feature is designed to reduce the number of redundant reports sent to the central station.
VISTA-32FB Installation and Setup Guide Trouble Messages The following messages are displayed on the 6160/6160CR-2 when a problem exists on the Communications Device: 1. “LRR Battery”: The battery connected to the Communications Device is low. 2. “PLL out of Lock”: The Communications Device has an internal fault and cannot transmit any messages. 3. “Early Power Detect”: RF power is detected without a valid transmission. 4. “Power Unattained”: Full RF power was never attained. 5. “Frwd.
Section 3 – Installing the Control Use the following instructions for wiring the 18VAC secondary winding of the internal transformer. To connect the internal transformer to the control, perform the following steps: Step Action 1 Open the control panel cover. 2 Connect the blue 16AWG wire from the transformer at the control panel to terminals 1 and 2. 3 Connect the green 16 AWG wire (ground) at the control panel ground terminal 30. 4 Replace the front cover of the control panel.
VISTA-32FB Installation and Setup Guide 1. In Worksheet 1, enter devices used on the polling loop. Calculate total current draw on the polling loop. Worksheet 1: Total Polling Loop Current Draw Polling Loop Device Current # of Units Total Polling Loop Subtotal (terminals 28 & 29 – 128mA) ✳ ✳The total current cannot exceed 128mA. If total load exceeds 128mA, then a 4297 Loop Extender Module can be used.
Section 3 – Installing the Control 3. In Worksheet 3, enter devices used on Auxiliary Power 2. Calculate standby and alarm currents, then add to get Auxiliary Power 2 current subtotal. Worksheet 3: Auxiliary Power 2 Current Load Total Current Device Model # Device Current X # of Units Auxiliary Power 2 Subtotal (pin 5 on keypad port 2) Standby Alarm 400mA max. 400mA max. 4. In Worksheet 4, enter devices connected to the Bell 1 Output.
VISTA-32FB Installation and Setup Guide 5. In Worksheet 5, enter devices connected to the Bell 2 Output. Calculate alarm currents, then add to get the Bell 2 Output current subtotal. Worksheet 5: Bell 2 Output Current Load Total Current Device Model # Device Current X # of Units Standby Alarm XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX Bell 2 Output Subtotal (terminals 5 & 6 – 1.7A max.) 6.
Section 3 – Installing the Control The total control standby load must be limited to 1A for 24-hour standby time using a 12V, 34.4AH battery connected to the control. Determining the Size of the Standby Battery For burglary installations requiring 4-hour standby time followed by 15-minutes alarm time, use a 12AH battery to support all loads up to and including the maximum system load (e.g., 1A standby/2.7A alarm total control panel load).
VISTA-32FB Installation and Setup Guide 9. Connect the battery, referring to Figure 3-25. The standby battery is automatically tested for 10 minutes every 4 hours, beginning 4 hours after exiting Programming mode. In addition, entry into the Test mode initiates a battery test. The VISTA-32FB also runs a 5second battery test every 60 seconds to check if the battery is connected.
S E C T I O N 4 Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Program Modes There are two programming modes for the VISTA32FB. These are the Data Field Program Mode and the #93 Menu Mode. The Data Field Program Mode is where many system options are programmed. The #93 Menu Mode is an interactive mode that requires a 2line alpha keypad (6160/6160CR-2). The factory-loaded defaults (✳97) enable keypad addresses 00-01 only.
VISTA-32FB Installation and Setup Guide Programming System-Wide Data Fields Values for some programming fields are system-wide (global), and some can be different for each partition (partition-specific). The partition-specific programming fields are automatically skipped when programming the global fields. If the system has only one partition, the partition-specific fields are not automatically skipped.
Section 4 – Programming Below are the main menu selections. For details refer to the VISTA-32FB Programming Guide. MAIN MENU OPTIONS ZONE PROG? 1 = YES 0 = NO 0 EXPERT MODE? 1 = YES 0 = NO 0 For programming the following: • Zone Number • Zone Response Type • Partition Number for Zone • Dialer report code for zone • Input Device Type for zone (whether RF, polling loop, etc.) • Enrolling serial numbers of 5800 Series transmitters and serial polling loop devices into the system.
VISTA-32FB Installation and Setup Guide Following is a list of commands used while in the Menu Mode: #93 Menu Mode Programming Commands #93 Enters Menu Mode. [✳] Serves as [ENTER] key. Press to have keypad accept entry. [#] Backs up to previous screen. 0 Press to answer NO. 1 Press to answer YES. 00, or 000+[✳] Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option.
Section 4 – Programming Communication Defaults *45 PRIMARY FORMAT [1] ADEMCO Contact ID *46 LOW SPEED FORMAT (Prim) [0] ADEMCO Low Speed *47 SECONDARY FORMAT [1] ADEMCO Contact ID *48 LOW SPEED FORMAT (Sec.) [0] ADEMCO Low Speed *49 CHECKSUM VERIFICATION [0] [0] *50 No checksum Primary SESCOA/RADIONICS SEL.
VISTA-32FB Installation and Setup Guide Type 01: Entry/Exit #1 Burglary Provides entry delay whenever the zone is faulted and the system is armed in the AWAY or STAY mode. When the panel is armed in the INSTANT or MAXIMUM mode, no entry delay is provided. Exit delay begins whenever the control is armed, regardless of the arming mode selected. These delays are programmable. Assign this zone type to zones that are used for primary entry to and exit from the facility.
Section 4 – Programming Type 17: Fire Waterflow Provides a trouble condition on open circuit and an alarm on a short circuit that remains longer than the programmed time delay (fields 3✳16 and 3✳18). The alarm can be silenced by either an entry of User Code + OFF or when the zone restores (field 3✳14). This type is always active and can only be bypassed by the Installer code or the Master code, (field 3✳85). Type 18: Fire Supervisory Provides a supervisory response on a short circuit.
VISTA-32FB Installation and Setup Guide Step Using the a Relay to Unlock A Door This control can be programmed so that a user can trigger a relay for 2 seconds (e.g., to unlock a door) by entering the User Code + [ 0 ]. To program a relay for this purpose, perform the following steps:: Step Action 1 Enter Output Programming in the #93 Menu Mode. Action 2 Program the output type as 1, or 2. 3 For type 1, program the ECP address and relay number. 4 For type 2, program the house and unit codes.
S E C T I O N 5 Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order. Field numbers are listed in the left column, followed by a “Title and Data Entries column, which lists the valid entries for each field. Experienced installers can simply follow this column when programming the data fields.
VISTA-32FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 0✴ Bell 1 Timeout Defines the length of time the Bell 1 Output and the keypad’s sounder will sound for all audible alarms. Must be a minimum of 16 minutes for UL commercial burglary installations and a minimum 6 minutes for Commercial Fire installations. 130 0✴ 150 0✴ 160 Enter 01-15 multiplied by 2 minutes. 00 = no timeout. Keyswitch Assignment Enter 1-2 partition keyswitch is being used.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 0✴ Test Report Interval If a test report is desired, enter a test code in Report Code Programming in #93 Menu Mode. Set first test report time in field *83. Maximum Test report interval is 024 for Commercial Fire and UL Commercial Burglary installations.
VISTA-32FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 0✴ Download Command Enables Enabling a function means that you are able to perform that function via the ADEMCO Compass Downloading software. Functions are as follows: Dialer Shutdown; System Shutdown; Not Used; Remote Bypass; Remote Disarm; Remote Arm; Upload Program; and Download Program. For UL Commercial Burglary and Fire installations, all entries must be 0.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 0✴ Low Speed Format (Secondary) Enter the low speed format for the secondary telephone number. 0✴ Checksum Verification 0✴ Sescoa/Radionics Select 0✴ Dual Reporting 480 490 500 510 0 = ADEMCO Low Speed 1 = Sescoa/Radionics Enter two digits, one for the primary and one for the secondary.
VISTA-32FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 0✴ Alpha Numeric Pager Installed Not Used. Must be set to “0”. 0✴ Pager Phone Number for Alarms Not Used. Must be set to “0”. 0✴ Pager ID Number for Alarms Not Used. Must be set to “0”. 0✴ Pager Phone Number for Supervision Not Used. Must be set to “0”. 0✴ Pager ID Number for Supervision Not Used. Must be set to “0”. 0✴ Pager Phone Number for Bypasses Not Used. Must be set to “0”.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 0✴ Zone Type Restores for Zone Types 9, 10 & 14 This field has three entries, one for each zone type. Select the zone types that will send Restore reports. Restores must be set to “1” for Commercial Fire installations.
VISTA-32FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 1✴180 Affects Lobby (partition-specific) If enabled, causes lobby partition to disarm when this partition disarms. NOTE: This partition must be armed before lobby can be armed. Must be set to “0” (disable) for partition 1. 1✴190 Arms Lobby (partition-specific) 0 = disable 1 = enable 0 = disable 1 = enable If enabled, arming this partition causes the system to attempt to arm the lobby partition.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 1✴220 Cross Zoning Pair One Select the first pair of cross zones, which must both be faulted within a 5minute period to cause an alarm. Must be set to 000,000 for Commercial Fire and Burglary installations.
VISTA-32FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 1✴350 Access Control Dialer Enables There are six entries for this field as follows: Trace, Trouble, Not Used, Bypass, System, and Alarm. If Trace is enabled, access grant/denial events sent to the central station. For the other events, if enabled, a report is sent to the central station. 0 = disable 1 = enable Not Used.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 1✴560 AC 60Hz or 50Hz Select the frequency for the AC. Must be set to 0 for U.S. and Canadian installations.
VISTA-32FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 2✴020 Daylight Saving Time Start/End Weekend Enter the start and end weekends for daylight saving time as follows: 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last. Standard setting for U.S. is 2, 1. 0 = disable 1 = enable 2✴050 2✴060 2✴070 2✴080 Auto-Arm Delay (partitionspecific) This is the time between the end of the arming window and the start of autoarm warning time (field 2*06).
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 2✴210 Supervision Pulses for Communicators 0 = disable 1 = enable Silent Panic/Duress, Supervisory, and Trouble. If enabled, causes the control to send periodic short pulses on the J2 communicator triggers to the communications device. The communications device uses these pulses to determine that its connection to the control is still intact. Must be set to “00000” for Commercial Fire and Burglary installations. Not Used.
VISTA-32FB Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION 3✴140 Waterflow Alarm Silence Option Select how the Waterflow zone type will be silenced. NOTES: 0 = silenced by User Code + OFF 1 = silenced when zone restores This feature may be set to 1 only by permission of the local authority.
Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES EXPLANATION 3✴310 Backup Dialer TouchTone or Rotary Select the dialing method for the backup dialer.
VISTA-32FB Installation and Setup Guide 5-16
S E C T I O N 6 Scheduling Options • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • UL • • • You must program Bypass and Auto-Arm Fail reports for UL installations. Auto-disarming is not permitted in UL installations. You must not program Random Scheduling of Time Driven Events for UL installations. General The scheduling features allow certain operations to be automated, such as arming, disarming, bypassing of zones, and activating relay outputs.
VISTA-32FB Installation and Setup Guide This option is set in partition-specific field 2*10. If field 2*10 is set, we highly recommend setting field 2*11, as well. This field allows the partition to be disarmed outside the arm/disarm time windows only if the partition is in alarm. Exception Reports This option allows the reporting of openings and closings to the central station only if the arming and disarming occurs outside of the predetermined opening and closing time windows.
Section 6 – Scheduling Options Using the #80 Menu Mode, the installer can program open/close schedules by assigning a time window to a day of the week (windows are entered as 2-digit entries) Mon Tue Wed Thu Fri Sat Sun Hol Op/Cl Op/Cl Op/Cl Op/Cl Op/Cl Op/Cl Op/Cl Op/Cl 01/04 01/04 01/04 01/04 01/05 02/03 00/00 00/00 NOTE: 00 is entered for those days on which the store is closed.
VISTA-32FB Installation and Setup Guide Example of Open/Close Exception Reporting & Scheduling The following chart gives an example of how the Open/Close by Exception reporting works. 6:01PM 5:59AM 6AM 9AM 9:01AM 3:59PM 4PM 6PM Early Opening reports are sent if system is manually disarmed before opening window begins. Early and Late Opening and Closing reports are programmable options in Report Code Programming in the Programming Guide.
Section 6 – Scheduling Options Steps to Program Scheduling Options This section contains examples of the worksheets only. For complete worksheets, see the Programming Guide accompanying this Installation and Setup Guide. In order to use #80 Scheduling Menu Mode, use the worksheets to do the following: 1. Define time windows (up to 20) 2. Define the daily open/close schedules (one schedule per day, per partition) 3. Define the holidays to be used by the system (up to 16) 4.
VISTA-32FB Installation and Setup Guide Time Windows he system provides 20 time windows that are defined with start and stop times. These windows are used for various open/close and access schedules, as well as for output controls, and are the basis of the scheduling system. These windows are shared between both partitions. Time Windows Worksheet The following worksheet is an example of the worksheet found in the Programming Guide.
Section 6 – Scheduling Options Part Mon Op Tues Cl Op Cl Wed Op Cl Thur Op Cl Fri Op Sat Cl Op Sun Cl Op Hol Cl Op Cl 1 2 Open/Close Schedule Programming After entering Scheduling Menu Mode, press [0] until the “O/C Schedules?” prompt appears. PROMPT EXPLANATION Enter 1 to program opening and closing schedules. O/C Schedules ? 1 = YES 0 = NO 0 Partition # ? 01-02, 00 = Quit 01 Enter the appropriate partition number for which the following open/close schedules will apply.
VISTA-32FB Installation and Setup Guide Holiday Schedule Programming After entering Scheduling Menu Mode, press [0] until the “Holidays ?” prompt appears. PROMPT EXPLANATION Holidays ? 1 = YES 0 = NO Enter 1 to program holiday schedules. 0 HOLIDAY NUMBER ? 01-16,00=Quit 01 Enter the 2-digit holiday number (01-16) to be programmed and press [✳] to accept entry. Enter 00 + [✳] at the “Holiday Number?” prompt to quit the holiday menus and display the “Quit ?” prompt.
Section 6 – Scheduling Options Relay Commands Action Code Action Action Specifier 01 Relay On Relay # 02 Relay Off Relay # 03 Relay Close for 2 seconds Relay # 04 Relay Close XX minutes (set in field 1*74) Relay # 05 Relay Close YY seconds (set in field 1*75) Relay # 06 Relay Group On Relay Group # 07 Relay Group Off Relay Group # 08 Relay Group Close for 2 seconds Relay Group # 09 Relay Group Close XX minutes (set in field 1*74) Relay Group # 10 Relay Group Close YY seconds (
VISTA-32FB Installation and Setup Guide Time-Driven Event Programming The following menu items must first be programmed in Output Programming in the #93 Menu Mode: Enter Relay No. Output Group Restriction Output Type Zone No. ECP Address Relay No. (reference identification number) (if applicable) (V-Plex, 4204/4204CF) (V-Plex) (4204/4204CF) (4204/4204CF) After entering Scheduling Menu Mode, press [0] until the “Timed Events ?” prompt appears.
Section 6 – Scheduling Options ACTION CODES EXPLANATION 50=Off-Normal Reminder Action 50 No action specifier is required for this action since the condition that this occurs for are system-wide. PROMPT EXPLANATION 01 Time Window ? 00:00 00:00 01 Enter the time window number (01-20) for which this timed event is to occur. As the number is keyed in, the actual time that has been stored for the time window number is displayed. Press [✳] to accept entry.
VISTA-32FB Installation and Setup Guide PROMPT EXPLANATION MON A1 Window 1? 00:00 00:00 Enter the first time-window number (01-20) for this access schedule for the displayed day. As the number is keyed in, the actual time that has been stored for the window is displayed. Press [✳] to continue. 00 MON A1 Window 2 ? 00:00 00:00 00 Enter the second time-window number from 01-20 for this access schedule for the displayed day.
Section 6 – Scheduling Options Temporary Schedules Programming Enter User Code + [#] + 81 to enter this mode. PROMPT EXPLANATION Mon DISARM WIND. 00:00AM 00:00AM This prompt is for entering the start and end times of the disarm (opening) window for Monday. Upon entry of this mode, the cursor is positioned on the tens of hours digit of the start time of the disarm window. Enter the desired hour. Press [✳] to move to the minutes field. The minutes are entered in the same manner.
VISTA-32FB Installation and Setup Guide Entering 00 as the output number deletes the timer (Timer 06, in this example) and displays an output descriptor of “None.” Output devices are programmed via #93 Menu Mode. PROMPT EXPLANATION 06 ON TIME ? 07:00 PM The cursor is positioned on the tens of hours digit of the ON time. Enter the desired hour. Press [✳] to move to the minutes field. The minutes are entered in the same manner.
S E C T I O N 7 Downloading Primer (Remote Downloading is not a UL Listed feature) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information Downloading allows the operator to remotely access, program, and control the security system over normal telephone lines, IP, or GSM Communicators. Anything that can be done directly from the keypad can be done remotely, using ADEMCO’s COMPASS downloading software.
VISTA-32FB Installation and Setup Guide Getting On-Line with a Control Panel At the protected premises, the control panel must be connected to the existing telephone line (refer to the SECTION 3: Installing the Control). No programming of the panel is required before downloading to an initial installation unless you are performing an unattended download.
Section 7 - Downloading Primer Direct-Wire Downloading The VISTA-32FB can be downloaded without using a modem or telephone line by using a 4100SM Serial Module and Compass Downloading Software. The direct-wire downloading connection is to be temporary, and is not part of the permanent installation. Directwire downloading is meant as a tool for the installer during the installation process.
VISTA-32FB Installation and Setup Guide 7-4
S E C T I O N 8 Setting the Real-Time Clock • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information This system provides a real-time clock, which must be set in order for the system’s event log to keep track of events by time and date. It must also be set in order to execute scheduling programs (Time-Driven events). Use a 6160/6160CR-2 alpha keypad to set the real-time clock, or set the clock via the downloader software.
VISTA-32FB Installation and Setup Guide 8-2
S E C T I O N 9 User Access Codes • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information The VISTA-32FB system allows a total of 75 security access codes to be allocated. Each security access code is identified by a user ID number. Regardless of the number of partitions each code has access to, it occupies only one user slot in the system. If a particular code is not used in all partitions, that user ID number cannot be used again.
VISTA-32FB Installation and Setup Guide Level 6: Duress Codes • Sends a silent alarm to a central monitoring station if the user is being forced to disarm (or arm) the system under threat (system must be connected to a central station).
Section 9 – User Access Codes Adding a Master, Manager, or Operator Code Enter Installer Code†+ [8] + new user no. (02-75) + new user’s code †Or Master or Manager Code, but the code must be a During user code entry, normal key depressions at other keypads in a partition are ignored. However, panic key depression causes an alarm and terminates user entry. higher level of authority than the code being changed (e.g.
VISTA-32FB Installation and Setup Guide Changing a Master, Manager, or Operator Code Enter Installer Code*+ [8] + new user no. (02-75) + new user’s code *Or Master or Manager Code, but the code must be a higher level of authority than the code being changed (e.g. a Manager Code can add an Operator-level Code, but cannot add a Master or another Manager Code). PROMPT EXPLANATION User Number = 03 NEW USER? The system detects that the user number is already assigned, and prompts if this is a new user.
S E C T I O N 1 0 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Battery Test When AC power is present, the VISTA-32FB runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery test every 4 hours to check on the battery’s condition. If the VISTA-32FB finds that the battery voltage is low (less than approximately 11.
VISTA-32FB Installation and Setup Guide PROMPT EXPLANATION AUTO-TEST DET? Enter 1 (YES) to have the system automatically test all polling loop points with a fire response type 9 or 16. Other fire zones will have to be tested manually. Enter 0 (NO) to test every point manually. The next prompt will be displayed. 0=NO 1=YES For true detector sensitivity tests, and for compliance with fire codes, you must enter 0 (NO) to this question. LOG RESULTS? 0=NO 1=YES C.S.
Section 10 – Testing The System Armed Burglary System Test • • Alarm messages are sent to the central station during the armed tests. Notify the central station that a test will be in progress. A display of “COMM FAILURE” indicates a failure to communicate (no kissoff by the receiver at the central station). If this occurs, verify that the phone line is connected, the correct report format is programmed, etc.
VISTA-32FB Installation and Setup Guide Trouble Conditions Supervisory Messages Other System Messages Display Description Display Description SUPV + Zone Number This indicates that a fire supervisory condition exists on the zone number displayed. This means that the operation of the fire alarm system may be compromised. COMM FAILURE Indicates a failure occurred in the telephone communication portion of your system.
Section 10 – Testing The System To the Installer Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory operation of any alarm system. The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainting the user with the proper operation and limitations of the alarm system and its component parts.
VISTA-32FB Installation and Setup Guide 10-6
S E C T I O N 1 1 Using the Vista-32FB as a Slave Communicator • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • To use the Vista-32FB as a Slave Communicator connected to a Fire Alarm System, follow the setup below. Wiring Wire the Vista-32FB as shown in Figure xx below. Be sure to tag the wires at the Terminal Box to identify their connections between the Fire Alarm Panel and the Vista-32FB.
VISTA-32FB Installation and Setup Guide Sending Vista-32FB System Troubles to the Fire Alarm Panel If using an alpha keypad on the Vista-32FB that is mounted next to the Main Fire System Operator Interface, it is not necessary to send Vista-32FB troubles to the Fire Alarm Control.
A P P E N D I X A Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • UL Installation Requirements UL This system may be used in installations that require UL2050 compliance. Commercial Burglary Requirements 1. 2. 3. 4. All partitions must be owned and managed by the same person(s). All partitions must be part of one building at one street address.
VISTA-32FB Installation and Setup Guide UL609 Local Mercantile Premises/Local Mercantile Safe & Vault 1. All zones must be configured for EOLR supervision (*41=0). If 4190SN V-Plex devices are used, set field *24 to "0" to enable tamper detection. 2. Attach a Listed door tamper switch to protect the cabinet door. Wire the selected device to Zone 6. Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response.
FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
VISTA-32FB Installation and Setup Guide CANADIAN EMISSIONS STATEMENTS This Class B digital apparatus complies with Canadian ICES-003 NOTICE The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
A P P E N D I X B Summary of System Commands • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • User Code Commands Add A User Code = User Code + 8 + New User Number + New User’s Code Change a Code = User Code + 8 + User Number + New User’s Code Delete a User’s Code = Your User Code + 8 + User Number to Be Deleted + Your Code Again View User Capability = User’s Code + [✳] + [✳] Set Real-Time Clock (Installer, Master Only) = Code + [#] + 63 Programming Com
VISTA-32FB Installation and Setup Guide B-2
A P P E N D I X C Specifications • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Physical: 18"H X 14-1/2"W X 4.3"D Electrical: Primary Power: From ADEMCO No. 1451 Transformer with enclosure; rated 18VAC, 72VA. Backup Battery: Alarm Power: Aux. Standby Pwr Total Power Standby Time: Fusing: 12VDC, 12AH min to 34.4AH max lead acid battery (gel type). 12VDC, 1.7A max. for each Notification Appliance Circuit. 12VDC, 1A max.
VISTA-32FB Installation and Setup Guide C-2
A P P E N D I X D Contact ID Event Codes • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • TABLE OF CONTACT ID EVENT CODES Code 110 111 113 121 122 123 124 125 131 132 133 134 135 140 142 150 200 301 302 305 306 308 309 310 313 320 321 322 332 333 338 339 342 343 344 351 352 354 373 374 380 381 382 383 384 385 386 389 401 403 Definition Fire Alarm Smoke Alarm Waterflow Alarm Duress Silent Panic Audible Panic Duress Access Grant Duress Egress Grant Perime
VISTA-32FB Installation and Setup Guide D-2
Index • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • #93 Menu Mode Programming ................................... 4-2 Auto Disarming............................................................ 6-1 #93 Menu Mode Programming Commands ............... 4-4 Auto Trouble Restore.................................................. 5-6 12/24 Hour Type Stamp Format................................ 5-11 Auto-Arm Delay ..................................................
Console Input (CS) Type 09........................................ 4-7 Contact ID .................................................................... 1-2 CONTACT ID EVENT CODES......................................D-1 Contacting Technical Support ................................. 10-5 Control Panel as Stand-Alone Access Control......... 4-8 Control Relay ............................................................. 5-11 Conventions Used in This Manual ..........................
LINE SEIZE...................................................................C-1 List of Figures.................................................................vi LO BAT ....................................................................... 10-4 Lobby Partition ............................................................ 5-7 Log First Maintenance Signal................................... 5-11 LOG RESULTS?......................................................... 10-2 Long Range Radio ECP Programming ......
SYSTEM LO BAT ....................................................... 10-4 System LoBat”........................................................... 10-1 System Messages ..................................................... 10-4 System Zone Bypass Inhibit..................................... 5-15 System-Wide Data Fields............................................ 4-2 Telco Handoff .............................................................. 7-3 Telephone Line Connections ...................................
WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. • Intrusion detectors (e.g.
For the latest warranty information, please go to: www.honeywell.
2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2009 Honeywell International Inc. www.honeywell.