Setup guide

System Communication and Operation
6-5
ADEMCO Contact ID
®
ADEMCO and Robofon Contact ID
®
Reporting takes the following format:
CCCC(CCCCCC) Q EEE GG ZZZ where:
CCCC(CCCCCC) =4-digit or 10-digit Customer (subscriber) ID
Q = 1-digit Event qualifier, where: E = new event , and R = restore
EEE =3-digit (hexadecimal) Event code (see central office receiver manual for a
complete list of event codes)
GG = 2-digit Partition Number (system messages show “00”)
ZZZ = 3-digit Zone/contact ID number reporting the alarm, or user
number for open/close reports. System status messages (AC
Loss, Walk Test, etc.) contain zeroes in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
Code Definition
100 Medical Emergency (sent upon zone type
15 faults)
110 Fire Alarm
121 Duress
122 Alarm, 24-hour Silent
123 Alarm, 24-hour Audible
131 Alarm, Perimeter
132 Alarm, Interior
134 Alarm, Entry/Exit
135 Alarm, Zone Type 5
143 Alarm, Expansion Module
144 Sensor Tamper Alarm
145 ECP Module Cover Tamper Alarm
146 Silent Burglary Alarm
150 Alarm, 24-Hour Auxiliary/Monitor zone
162 Gas Alarm
301 AC Mains Power
302 Low System Battery/Battery Test Fail
305 System Reset (Log only)
309 Battery Fail
321 Siren Supervision Failure
333 Trouble, Expansion Mod. Supervision
341 Trouble, ECP Cover Tamper
344 RF Receiver Jam Detect
351 Telecom Line Fault
353 Alternative Comm. Media Trouble
354 Failure to Communicate (log only)
373 Fire Loop Trouble
374 Exit Error Alarm
380 Trouble Zone Type 5
381 RF Sensor Supervision
382 Supervision Auxiliary Wired Zone
(sent after code 333 is sent)
383 RF Sensor Tamper and Double-Balanced
Zone Tamper
384 RF Sensor Low-battery
Code Definition
393 Clean Me (ESL smoke detectors only)
401 Disarmed, Armed AWAY,
Armed MAXIMUM
403 Scheduled Arm/Disarm AWAY
406 Cancel by User
407 Remote Arm/Disarm (Downloading)
408 Quick Arm AWAY
409 Keyswitch Arm/Disarm AWAY
412 Successful Download/Access (see field
*53 to enable code)
441 Disarmed/Armed STAY/INSTANT,
Quick-Arm STAY/INSTANT
442 Keyswitch Arm/Disarm STAY
461 Wrong Code Entry (keypad lockout
activated; see field *188 to enable code)
570 Bypass
601 Manually Triggered Dialer Test
602 Periodic Dialer Test
606 Audio Alarm Verification (AAV) to Follow
607 Walk Test Entered/Exited
623 Event Log 80% Full
625 Real-Time Clock was Changed (log only)
626 Time/Date Inaccurate (see field *53 to
enable code)
627 Program Mode Entry (log only)
628 Program Mode Exit (log only)
641 Senior Watch Trouble (up and about)
750 -
789
Reserved for Configurable Zone Type
report codes (check with central station
when using these codes)
801 Override Tamper Arming (log only)
802 Override Low Battery Arming (log only)
803 Override AC Loss Arming (log only)
804 Override Supervision Arming (log only)
999 Zone Type 23 Fault (log only)