Setup guide

Installation and Setup Guide
3-6
Zone Type Description
Type 06
24-hour Silent Alarm
Usually assigned to a zone containing an emergency button.
Sends a report to the central station but provides no keypad display or
sounding.
Type 07
24-hour Audible Alarm
Assign to a zone that has an emergency button.
Sends a report to the central station, and provides an alarm sound at the
keypad, and an audible external alarm.
Type 08
24-hour Auxiliary
Alarm
Assign to a zone containing an emergency button, or to a zone containing
monitoring devices such as water or temperature sensors.
Sends a report to the central station and provides an alarm sound at the
keypad. (No siren output is provided.)
Type 09
Supervised Fire
Provides a fire alarm on short circuit and a trouble condition on open
circuit. A fire alarm produces a pulsing siren output.
This zone type is always active and cannot be bypassed.
Type 10
Interior w/Delay
Provides entry delay (using the programmed entry time), if tripped when
the panel is armed in the Away mode.
Entry Delay 1 begins whenever sensors in this zone are violated,
regardless of whether or not an entry/exit delay zone was tripped first.
Bypassed when the panel is armed in the Stay or Instant modes; if
armed in Night-Stay mode, zones assigned to zone list 05 (night-stay
zone list) are not bypassed when system armed in Night-Stay mode.
Type 12
Monitor Zone
Works as a dynamic monitor of a zone fault/trouble (not alarm). In the
case of a short/open, the message, "*ALARM*-24 Hr. Non-Burg. -#XXX "
(where XXX is the zone number) will be sent to the Central Station. The
system keypad will display aCHECK” message indicating the
appropriate zone (but keypad beeping does not occur). Upon restoral of
the zone, the message, "*RESTORE*-24 Hr. Non-Burg. -#XXX " will be
sent to the Central Station.
The “CHECK” message will automatically disappear from the keypad
dynamically, when the zone restores; a user code + off sequence is not
needed to reset the zone.
Faults of this zone type are independent of the system, and can exist at
the time of arming without interference.
Since this is a “trouble” zone type, do not use this zone type with relays
set to activate upon “alarm.”
Type 14
24 Hour Gas Monitor
Assigned to any zone with a gas detector.
The siren output will pulse when this zone type is alarmed.
Always active and cannot be bypassed.
Type 15
24 Hour
Medical/Personal
Emergency
Usually assigned to a zone containing an emergency button.
Sends a report to the central station (Contact ID event code “100”) and
provides an alarm sound at the keypad (no bell output is provided).