Setup guide
Mounting and Wiring the Control
2-19
Audio Alarm Verification
Connections (AAV, “Listen-In”)
Refer to the connection diagram below.
Connections use one of the on-board triggers.
Suggested AAV Module:
ADEMCO UVS (shown) or Eagle 1250
Notes
• Set field *91 for AAV and program the
appropriate output (output 17 or 18) using
*80 Menu mode (select zone type “60”).
• For voice session monitoring, connect an
EOLR zone to UVCM module terminals 6
& 7, and program the zone as zone type 81
(*56 Menu mode).
E.g., Using output 18 for the trigger,
program an output function in *80 Menu
mode as:
ZT = 60, P = 0, Action = 1, Device = 18
ON ON
12345678 12345678
1234567891011
29 30 31 32 33 34
NOTE:
REFER TO UVCM MODULE
INSTRUCTIONS FOR
CONNECTIONS TO AUDIO
SPEAKERS AND MICROPHONE.
UVCM
MODULE
ZONE
TERMINALS
EARTH
GROUND
RED (R)
GREEN (T)
GREY (R)
BROWN (T)
TRIGGER
CONNECTOR
OUTPUT 18
EOL
RING
TIP
OPTIONAL
MONITORING ZONE
CONNECTION
(USE ZONE TYPE 81)
FALLING VOICE TRIG
GND
+12VDC IN
SWITCH
BANK 2
SWITCH
BANK 1
SWITCH BANK 2
SWITCH BANK 1
AUXILIARY
AUDIO LEVEL
ADJUSTMENT
TRIM POT
aav_uvcm-003-V0
CONTROL
INCOMING
PHONE LINE
TO
PREMISES
HANDSET
5
1 = ON
2 = ON
3 = OFF
4 = ON
5 = ON
6 = ON
7 = ON
8 = ON
1 = OFF
2 = OFF
3 = OFF
4 = OFF
5 = OFF
6 = OFF
7 = OFF
8 = ON
23
24
25
+12VDC
GND
4
5
21
22
RJ31X
Figure 12. Connection of AAV Unit