ADEMCO VISTA-12A ADEMCO VISTA-12E Security Systems Installation and Setup Guide K10022-1V1 10/05 Rev.
ii
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Features and Installation Highlights .............................................................................................. 1-1 Capabilities ........................................................................................................................................ 1-1 Functions.................................................................................................................................
System Status Report Codes ............................................................................................................. 4-7 Miscellaneous System Fields............................................................................................................. 4-9 Pager Programming Fields................................................................................................................ 4-13 Miscellaneous System Fields.............................................................
S E C T I O N 1 Features and Installation Highlights • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This manual describes the installation of both the VISTA-12A and VISTA-12E. These units are identical except where noted. Capabilities • • • • Supports 2 independent partitions, which can protect two independent areas, as if each area had its own control. Supports 1 common area partition that allows either of the other two independent partitions to arm, while leaving a common area (ex.
Installation and Setup Guide Compatible Devices • • • • • • • • • • • Supports up to 8 Addressable Keypads: 6148/6150 Fixed-Word Display Keypads, 6164 Alpha Keypad, 6128RF/6128RFH/6150RF/6160RF Keypad/Transceivers, 6160V Voice Keypad Supports up to two (2) Touch Screen (AUI) Devices (Symphony, 6270), which are in addition to the standard eight (8) addressable keypads.
Mounting and Wiring the Control S E C T I O N 2 Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring this control and its peripheral devices. In the following subsections, procedures are listed in the left column, while notes and pertinent explanations are provided in the right column. 3.
Installation and Setup Guide Mounting the PC Board NOTE: The door of the metal cabinet may be removed to make it easier to install the PC board. Remove the door as follows: 4. Insert top of circuit board into slots at top of cabinet. Make sure that circuit board rests in slots as indicated in the diagram shown below. 1. With the cabinet laying on a flat surface, swing open the door to its full-open position. 5. Swing base of circuit board onto the raised cabinet tab and standoff. 2.
Mounting and Wiring the Control Notes Wiring to Keypads 1. 2. 3. Connect keypads to the control’s keypad terminals as shown on the Summary of Connections diagram. Determine wire size using the Wiring Run Chart below. If power supervision is required, refer to the Aux Power Supervision Connections paragraph at right. Set keypad addresses. Refer to the address setting instructions included with the keypads and set each keypad device address according to the chart at right.
Installation and Setup Guide Keypad Addresses Keypad Address no. 1 no. 2 no. 3 no. 4 16** 17 18 19 Keypads powered from supplies that do not have a backup battery will not function if AC mains power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output. Keypad Address no. 5 no. 6 no. 7 no. 8 20 21 22 23 ** The first keypad is address 16, which is always enabled and set for partition 1 with all sounds on.
Mounting and Wiring the Control Sounder (Siren) Connections Wiring the AC Transformer 1. Make sounder connections to alarm output terminals 3 (+) and 4 (–). For supervised output, continue with steps 2 and 3. 2. Cut the red Siren Supervision Jumper located above terminals 2 and 3 on the control board. 3. Connect a 2k ohm resistor across the terminals of the last sounder. Transformer: Connect the Transformer to terminals 1 and 2 on the control board.
Installation and Setup Guide Backup Battery Notes 1. Place the 12-volt backup battery in the cabinet. 2. After all connections to the control are completed and AC mains power has been applied, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed. Battery Saver Feature: The battery will disconnect from the system after its voltage decreases below 9VDC.
Mounting and Wiring the Control AUXILIARY DEVICE CURRENT DRAIN WORKSHEET DEVICE 6128RF Keypad/Transceiver 6150RF Keypad/Transceiver 6148 Fixed-Word Keypad 6150 Fixed-Word Keypad 6160 Alpha Keypad 6150V Fixed-Word Display Voice Keypad 6160V Alpha Display Voice Keypad 6164 Keypad w/4-Zone Expander and Relay 5881 RF Receiver 5883 RF Transceiver 4219 Zone Expander 4204 Relay Unit 4229 Zone Expander/Relay Unit TeleCommand CURRENT 90mA standby/120mA alarm 80mA standby/105mA alarm 30mA standby/55mA alarm 40mA sta
Installation and Setup Guide Notes Basic Wired Zones Normally Open Zones/Normally Open EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. Normally Closed Zones/Normally Closed EOLR Zones 1.
Mounting and Wiring the Control Notes Smoke Detectors • 4-Wire Smoke Detectors Connect 4-wire smoke detectors (up to 16, depending on detector current drain) to any zone from 2-8 as shown on the next page. This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger 17 to reset power (also required for fire verification).
Installation and Setup Guide Notes 4219/4229 Expansion Zones • Connect each module to the control’s keypad terminals. If power supervision is required, use the Trigger • Module terminals as described in the Aux Power Supervision Connections paragraph in the Wiring to Keypads section (page 2-3). Assign the module a device address of 08 using its DIP switches. The device address determines • the zone numbers being used, as shown below. 1. 2. Expander Module Addresses Zones… Device Address… 17-24 08 3. 4.
Mounting and Wiring the Control 6164 Keypad Expansion Zones 1. 2. 3. 4. Connect each keypad to the control’s keypad terminals. If power supervision is required, use the Trigger Module terminals as described in the Aux Power Supervision Connections paragraph in the Wiring to Keypads section (page 2-3). Using the keypad’s program mode, assign the keypad a unique keypad address (16-23), and assign a device address of 08 that provides expansion zones 17-20. Connect sensors to the keypad’s zone terminals.
Installation and Setup Guide Installing the RF Receiver Use one of the following receivers: RF Receiver Number of Zones 5881ENL up to 8 (including keyfob buttons) 5881ENM up to 16 (including keyfob buttons) 1. 2. 3. Set Device Address to “00” as described in its instructions (set all switches to the right, “off” position). Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal range of 67m.
Mounting and Wiring the Control Installing a 5800TM Module Notes 1. • 2. Mount the 5800TM next to the RF receiver (between one and two feet from the receiver’s antennas) using its accompanying mounting bracket. Do not install within the control cabinet. Connect the 5800TM to the control panel’s keypad connection terminals as shown on the Summary of Connections diagram and set to address 28.
Installation and Setup Guide 8-PIN TRIGGER CONNECTOR 3 4 5 6 7 8 (GREEN) 1 OUTPUT 18 4. • Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see Output Device Programming section). KEY 3. • Use *56 Menu mode to program the keyswitch zone and assign it zone type 77. (RED) 2. Connect the 4146 keyswitch's normally open momentary switch to a zone’s terminals (zones 2-8).
Mounting and Wiring the Control Connecting Relay Modules 1. 2. 3. 4. Mount either remotely or in the control panel. Connect to control’s keypad terminals using the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs. If power supervision is required, use the Trigger Module terminals as described in the Aux Power Supervision Connections paragraph in the Wiring to Keypads section (page 2-3). Set the module’s device address according to the table at right.
Installation and Setup Guide Powerline Carrier Devices Notes 1. Install up to 4 powerline carrier devices (if no relays are used) according to the instructions included with each. • 2. Connect the Powerline Interface Modulator to the Trigger Module connector using SA4120XM-1 cable as shown below. 3. Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode.
Mounting and Wiring the Control Trigger Module and On-Board Triggers Notes IMPORTANT: Make all wiring connections to the Trigger Module before mounting the module to the PC board. • 1. Connect field wiring to the desired trigger terminal on the trigger module (TRIG 1 = output 17; TRIG 2 = output 18) and the VTRIG +12V terminal. For supervised trigger operation, refer to the following: Trigger Voltage/Aux Power Supervision To supervise trigger voltage and/or aux power: A.
Installation and Setup Guide V48A-V48E-001-V0 ABLE) Figure 11. Trigger Module Phone Line Connections VISTA-12E Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram. Wire colors represent the colors of the cable to the RJ31X jack. VISTA-12A Plug the phone line plug into the modular phone connector mounted on the PC board.
Mounting and Wiring the Control Notes Audio Alarm Verification Connections (AAV, “Listen-In”) • Refer to the connection diagram below. Connections use one of the on-board triggers. • Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250 Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80 Menu mode (select zone type “60”). For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7, and program the zone as zone type 81 (*56 Menu mode). E.g.
Installation and Setup Guide 2-20
S E C T I O N 3 Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation. Programming can also be performed remotely from the installer’s office/home, using an IBM compatible personal computer, a CIA/CIA-EU modem, and Compass downloading software.
Installation and Setup Guide Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or *58 Expert Programming mode. Refer to those sections for detailed procedures. The system can control three independent areas of protection (known as partitions) for use by independent users, if desired.
Programming Overview Keypads Keypads are identified by predefined addresses (starting at address 16) as follows: Address Keypad Program Field 16 keypad 1 • always enabled for partition 1, all sounds enabled. 17 keypad 2 • data field *190 18 keypad 3 • data field *191 19 keypad 4 • data field *192 20 keypad 5 • data field *193 21 keypad 6 • data field *194 22 keypad 7 • data field *195 23 keypad 8 • data field *196 NOTE. First keypad is address 16 To enable keypads: 1.
Installation and Setup Guide Pager Programming The system can send various reports to up to 2 pagers. To program pager reporting, do the following: 1. Enter the appropriate information in the following data fields: *160, *163 Pager Phone Numbers (for pagers 1and 2 respectively) *161, *164, Pager Prefix Characters (for pagers 1 and 2 respectively) *162, *165, Pager Reporting Options by Partition† (for pagers 1 and 2 respectively) 2. 3. 4. 5. 6.
Programming Overview Zone Type Definitions You must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Zone Type Type 00: Zone Not Used Type 01 Entry/Exit Burglary #1 Type 02 Entry/Exit Burglary #2 Type 03 Perimeter Burglary Type 04 Interior Follower Type 05 Trouble when Disarmed/ Alarm when Armed Description Program a zone with this zone type if the zone is not used.
Installation and Setup Guide Zone Type Type 06 24-hour Silent Alarm Type 07 24-hour Audible Alarm Type 08 24-hour Auxiliary Alarm Type 09 Supervised Fire Type 10 Interior w/Delay Type 12 Monitor Zone Type 14 24 Hour Gas Monitor Type 15 24 Hour Medical/Personal Emergency 3-6 Description • Usually assigned to a zone containing an emergency button. • Sends a report to the central station but provides no keypad display or sounding. • Assign to a zone that has an emergency button.
Programming Overview Zone Type Type 16 Fire w/Verification Type 20: Arm-Stay (BR RF devices only) Type 21: Arm-Away (BR RF devices only) Type 22: Disarm (BR RF devices only) Type 23 * No Alarm Response Description • Provides a fire alarm when zone is shorted, but only after alarm is verified. • System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit within 90 seconds triggers fire alarm. • Provides a trouble response when zone is open.
Installation and Setup Guide Zone Type Type 82 Blockschloss Types 90-93 Configurable Description • Used with special Blockschloss lock and key. • System arms 5 seconds after the key is fully turned (arms MAXIMUM); key can then be removed. • When armed, the Blockschloss zone is shorted. An open circuit on this zone causes trouble condition. • If zones are “not ready,” the key will not turn fully and the system will not arm. • Contact ID report code is 409.
Programming Overview Data Field Programming Procedures (cont’d) Task Procedure Entering Data When the desired field number appears, simply enter the digits required. The keypad beeps three times after the last digit is entered and automatically displays the next data field in sequence. If entering less than the maximum digits available (e.g., phone number field), enter the desired digits, then press [∗] to end the entry. Review a Data Field Press [#] + [Field Number].
Installation and Setup Guide Table of Device Addresses This Device Uses Address Reports as†† RF Receiver 00 100 AUI 1 01 101 AUI 2 02 102 Alternative Communication 03 103 Media (ACM) † Telecommand Voice Module 17-23 117-123 Zone Expanders** (4219/4229): zones 17 - 24 08 108 Relay Module (4204/6164): Keypads: keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8 5800TM Module 13 113 16 17 18 19 20 21 22 23 28 116 117 118 119 120 121 122 123 n/a Enabled By… *56 zone programming: input d
S E C T I O N 4 Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order. Field numbers are listed in the left column followed by a “Title and Data Entries” column, which lists the valid entries for each field. Experienced installers can simply follow this column when programming the data fields.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION *25 Arming Prevention Override If no override is selected, system will not be able to be armed when there is either a supervision failure, system low battery, AC mains loss, or a tamper condition.
Data Field Programming Zone Sounds & Timing FIELD TITLE and DATA ENTRIES EXPLANATION *31 Single Alarm Sounding Per Zone (per armed period) 0 = no limit on alarm sounding per zone 1 = limit alarm sounding to once per arming period for a given zone Select whether a zone going into alarm should sound more than once per armed period. *32 Fire Alarm Sounder Timeout Select whether fire alarm sounding expires after sounder timeout or remains until manually turned off.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION *38 Confirmation Of Arming Ding Entry 1 for each partition selects whether arming from wired keypads causes siren ding. Confirmation of arming is an external sounder “ding” that follows the time selected in entry 2 for “ding at siren.” Ding occurs when closing reports is sent, or when exit delay expires. *39 Entry 1: 0 = no; 1 = yes, 1-second ding (ding if armed from wired keypad) Entry 2: Enter 0-15 from table below.
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION *42 Secondary Phone No. If you enter fewer than 30 digits, exit by pressing [∗]. To clear entries from field, press ∗42∗. See backup reporting note for field ∗41. Don’t fill unused spaces. *43 Part. 1 Primary Subs. Acct. No. *44 *45 *46 *47 *48 *49 Enter up to 30 digits. 0–9, # + 11 for ‘✱’, # + 12 for ‘#’, # + 13 for a pause (2 seconds) Enter digits 0–9; # + 11 for B, # + 12 for C, # + 13 for D, # + 14 for E, # + 15 for F. Part.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION *50 Burglary Dialer Delay 0 = no dial delay 1 = 15 seconds 2 = 30 seconds 3 = 45 seconds Provides delay of “BURGLARY ALARM” report to the central station, which allows time for the subscriber to avoid a false alarm transmission. This delay does not apply to zone type 24 alarms (silent burglary) or to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent as soon as they occur.
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION *55 Dynamic Signaling Priority Intended for use with Alternative Communication Media reporting. You must also enable field ∗29, ECP Contact ID Output for ACM. Select the initial reporting destination for messages as follows: Primary Dialer First selected (0): • If acknowledged before delay expires (see ∗54), then message will not be sent to ECP output.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION *59 Exit Error Report Code After arming the system, zones remaining open after exit delay expires cause an alarm sound at the keypad and external sounder (keypad also displays “EXIT ALARM”), and entry delay begins. Disarming before the end of the entry delay stops the alarm sounding and no message is sent to the central station. The keypad will display “CA” (fixed-word) or “ALARM CANCELED” (alpha display).
Data Field Programming FIELD *69 TITLE and DATA ENTRIES EXPLANATION Alarm Restores Alarm restore message will be sent upon condition selected. Send restore code (if fault cleared): 0 = at siren timeout (if restored) or at disarm (whether restored or not) 1 = dynamically as the fault clears 2 = only after a disarm *70 Alarm Restore Report Code 0 = disable; 1-F = see description above ∗59 Sent when an alarm zone is restored to its nonfaulted condition or at the times selected in field *69.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION *84 Auto-Stay Arm If enabled, the system will automatically change AWAY or MAXIMUM modes to STAY and INSTANT modes respectively if the entry/exit door is not opened and closed within the exit delay time after a user arms in AWAY mode from a wired keypad (non-RF device). An Opening report followed by an Armed Stay report is sent to the Central Station.
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION *87 Misc. Fault Delay Time Used with zones assigned to a configurable zone type with fault delay on (selected in alarm/trouble processing prompt), and sets a zone response time of 15 seconds to 15 min.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES *91 Miscellaneous Options Entry 1 – AAV and Exit Delay Restart: 0 = none 4 = using Audio Alarm Verification (AAV) unit 8 = Enable Exit delay restart/reset †† Multiple choice example: for both AAV and Exit delay restart, enter # + 12 (4 + 8).
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION *94 Download Phone Number Enter the phone number of the downloading computer. Do not fill unused spaces. End field by entering ∗. To clear entries from field, press ∗94∗. *95 Ring Count For Downloading Enter up to 30 digits as follows: 0–9, # +11 for “∗”, # + 12 for “#”, # + 13 for a pause.
Installation and Setup Guide FIELD *161 TITLE and DATA ENTRIES Pager 1 Characters Enter up to 16 characters EXPLANATION Up to 16 optional characters may be sent as a prefix to the 7-digit system status code sent to pager #1 (if used). Phone number in field *160 must have been entered. If fewer than 16 characters, exit by pressing [∗] and next field number. To clear entries from this field, press ∗161∗.
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION *164 Pager 2 Characters See field ∗161 for explanation. If fewer than 16 characters, exit by pressing [∗] and next field number. To clear entries, press ∗164∗. *165 Pager 2 Report Options *166 Pager Delay Option for Alarms Enter up to 16 characters see pager 1 reports, field *162 for entries, except use zone list 10.
Installation and Setup Guide FIELD *176 *177 *178 TITLE and DATA ENTRIES EXPLANATION Siren Options Select desired options.
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION *180 Zone Bypass Limit Select the maximum number of zones that can be bypassed. Each partition individually uses this entry. *181 AC and Clock Display Options 0 = unlimited zone bypasses in each partition 1-7 = number of zone bypasses allowed in each partition 8 = zone bypass disabled (no zones can be bypassed) 0-15 = desired options based on chart at right.
Installation and Setup Guide FIELD *186 *187 *188 TITLE and DATA ENTRIES EXPLANATION Display Options Select the desired keypad display options. Entry 1: If enabled, only the first zone that went into alarm is displayed. Pressing the READY key will scroll once through the other zones that went into alarm, then the first zone in alarm will again be displayed.
Data Field Programming AUI Enable FIELD TITLE and DATA ENTRIES EXPLANATION *189 AUI Device 1 and 2 Enable (for Touch Screen Style Keypads) The System supports up to two touch screen style keypads (e.g., Symphony Advanced User Interface, and 6270 Touch Screen Keypad). Enter each AUI’s home partition. 0 = disabled 1 = partition 1 2 = partition 2 3 = common partition NOTE: Use of AUI does not affect the number of standard keypads supported.
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION *197 Exit Time Display Interval If enabled, keypads display the exit delay time remaining after arming the system, with display updates at the interval selected (i.e. if the exit delay is 30 seconds and “2” is selected in this field, the keypad display refreshes every 2 seconds, displaying 30, 28, 26, 24, etc.).
S E C T I O N 5 Menu Mode Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming (∗ ∗56 and ∗58 Menu Modes) ∗56 Zone Programming is used to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter serial numbers, and identify the type of loop input device(s).
Installation and Setup Guide PROMPT Zn ZT P RC In: L 17 00 1 10 RF: 1 VALID ENTRIES EXPLANATION Summary Screen A summary display appears. “IN: L” appears for wireless zones and indicates input type and loop. “IN: AD” appears for wired expansion zones (AW) and indicates the module’s address (AD), which is based on the zone number. “HW: RT” appears for basic wired zones and indicates configuration (EOL, NO, NC, zone doubling, double-balanced) and response time selection.
Menu Mode Programming PROMPT 02 Response Time 1 17 INPUT TYPE RF TRANS 3 VALID ENTRIES EXPLANATION Response Time (RT) This prompt appears only for basic wired zones 01-06 (zone 02 is used as an example in display). NOTE: If zone doubling is being used, the response time set for zones 01-06 automatically applies to each zone’s associated doubled zone. 0 = 10mSec 2 = 700mSec 1 = 400mSec 3 = 1.
Installation and Setup Guide PROMPT 17 INPUT S/N: L A022-4064 1 17 INPUT S/N A022-4064 L ? VALID ENTRIES EXPLANATION Serial number Entry and Loop Number Entry Used only when enrolling wireless transmitters. a. Transmit two open/close sequences. If using a button-type transmitter, press and release the button twice, but wait about 4 seconds before pressing the button the second time. OR b. Manually enter the 7-digit serial number printed on the label of the transmitter.
Menu Mode Programming PROMPT XMIT TO CONFIRM PRESS ✱ TO SKIP VALID ENTRIES EXPLANATION Confirmation Option This prompt will only appear if you answered “Yes” at the first prompt in this section. The system will enter a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate the loop input or button that corresponds to this zone.
Installation and Setup Guide ∗58 Expert Programming Mode Procedures This method is designed for use by installers with previous experience in programming ADEMCO control panels. This mode is also used to program wireless keys using pre-defined templates. Start Expert Programming mode by pressing ∗58 while in Data Programming mode.
Menu Mode Programming PROMPT Zn ZT P RC IN: L 10 00 1 10 RF 1 10 INPUT S/N: AXXX-XXX L – VALID ENTRIES EXPLANATION Zone Programming A summary screen with the selected zone’s current programming appears.
Installation and Setup Guide PROMPT 10 XMIT TO CONFIRM PRESS ✱ TO SKIP Entd Rcvd A022-4063 A022-4064 VALID ENTRIES EXPLANATION Confirm The prompt to confirm appears. This prompt will only appear if the first prompt after entering ∗58 was answered “Yes.” To confirm, activate the loop input or button that corresponds to this zone. The system checks for a duplicate. If a duplicate exists, a long error beep will sound. Press [#] to back up and re-enter the serial and/or loop number.
Menu Mode Programming PROMPT L T 01 23 02 22 03 04 21 23 VALID ENTRIES EXPLANATION Template Display 4. When [∗] is pressed, the selected template will be displayed. Top line of display represents loop numbers, bottom line represents zone type assigned for each loop. 5. Press [∗] to accept template. [∗] to continue Partition PARTITION 1 1 = partition 1 2 = partition 2 3 = partition 3 6. Enter the partition in which the key is to be active. 7. Press [∗] to continue.
Installation and Setup Guide PROMPT XMIT TO CONFIRM PRESS ✱ TO SKIP VALID ENTRIES EXPLANATION Confirm 13. If “Yes” was entered at the SET TO CONFIRM? prompt previously (see first prompt following entry into the •58 Expert Programming Mode), the display on the left will appear. Confirm serial and loop numbers by activating the wireless key. [∗] to continue IMPORTANT: When confirmed, the key is not active until it is assigned to a user number (using the assigning attributes command, attribute “4”).
Menu Mode Programming Wireless Key Predefined Default Templates 5804 Wireless Key Transmitter 5804BD 2-Way Wireless Key Transmitter For 5804 TEMPLATE 1 Loop 1 2 3 4 TEMPLATE 2 Loop 1 2 3 4 TEMPLATE 3 Loop 1 2 3 4 For 5804BD Function No Response Disarm Arm Away No Response Function No Response Disarm Arm Away Arm Stay Function 24-hour audible Disarm Arm Away Arm Stay Zone Type TEMPLATE 4 23 22 21 23 Zone Type TEMPLATE 5 23 22 21 20 Zone Type Loop Function 1 2 3 4 No Response No Response Arm
Installation and Setup Guide About Output Device Programming (*79/*80 Menu Mode) Output Devices: The system supports up to 4 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 6 “outputs” are assigned to system-wide output numbers (01-06 and 17-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
Menu Mode Programming 79 Menu Mode PROMPT ENTER OUTPUT NO. 00 = QUIT xx 17 OUT NORM LOW 0 = NO 1 = YES 0 XX OUTPUT TYPE DELETE 0 VALID ENTRIES EXPLANATION Device Output Number This is the logical (or reference) relay number as used in the system. Relays and X-10 devices are numbered 01-04; the on-board triggers are numbered 17 and 18 and can be programmed for inverted output. Use the worksheet on the Programming Form (printed separately) to organize device numbers.
Installation and Setup Guide *80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 12 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components Component Description Output Function No.
Menu Mode Programming PROMPT 01 A E P Trig ?00 0 0 – ZL=1 VALID ENTRIES EXPLANATION Summary Screen This screen displays a summary of the current output programming (for this example, Zone List has been selected-this is the default screen). A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type [∗] to continue NOTE: A question mark in the summary screen indicates that the device number shown has not been mapped. Use *79 Menu mode to map the device.
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Zone Type If zone type was selected, this screen appears. Otherwise skip to the next row. Enter the desired zone type associated with this output number. See below for a list of available zone types.
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION Zone Number If zone number was selected, this screen appears. Enter the desired zone number associated with this output number. Press [∗] to continue. Enter the zone event that will activate this output. “C” 01 Enter Zn No. 12 01 Enter Event Restore 0 0 = restore; 1 = alarm 2 = fault; 3 = trouble Press [∗] to continue to the “Output Action” prompt 01 Output Action Close for 2 sec 1 Enter Output No.
Installation and Setup Guide Zone List Programming Zone List programming involves: 1. Selecting an appropriate zone list number; 2. Adding the desired zone numbers to be included in that list. Start Zone List Program Mode by pressing ✱81 while in Data Programming mode. The following prompts are displayed: *81 Menu Mode PROMPT Zone List No. (00 = Quit) 01 01 Enter Zn Num.
Menu Mode Programming Programming Function Keys Function key programming involves: 1. Assigning the function key number and partition; 2. Selecting the desired function for that key. Start Function Key Programming mode by pressing ∗57 while in Data Programming mode. The following prompts are displayed: Press Key to Pgm 0 = Quit 0 VALID ENTRIES EXPLANATION Function Key Press the desired function key (A-D) you want to program.
Installation and Setup Guide PROMPT Key "A" Func Zone 95 00 VALID ENTRIES EXPLANATION Define Key Function Enter the desired function for this key, 00 to 12, from the options listed.
Menu Mode Programming PROMPT Sel Zone Des=0 Part = 1 VALID ENTRIES EXPLANATION Select Descriptor Type This prompt selects whether you are entering zone descriptors or entering partition descriptors. Pressing [0] goes to the next prompt to let you enter zone descriptors. Pressing [1] lets you program a partition descriptor.
Installation and Setup Guide Configurable Zone Type Programming (*83 Menu Mode) Start Configurable Zone Type Programming Mode by pressing ∗83 while in Data Programming mode. PROMPT Enter Zone Type (00=quit) 90 VALID ENTRIES EXPLANATION Zone Type Number Enter the configurable zone type number being programmed. 90-93 = zone type [∗] to continue Enter the desired zone attributes.
Testing the System PROMPT 90 TRBL SOUND 0 VALID ENTRIES EXPLANATION Trouble Sounding Select type of sounding upon trouble conditions on zones assigned to this zone type.
Installation and Setup Guide PROMPT ENTER SCHED NO. 00=QUIT 00 VALID ENTRIES EXPLANATION Schedule Number Enter the desired schedule number. 01-04 = end-user schedules 05-08 = installer-only schedules [∗] to continue Enter Event ENTER EVENT NOTE: Events 07 and 10 cause the keypad to beep every 30 seconds when messages are displayed. Stop the beeps by user code + OFF.
Testing the System PROMPT VALID ENTRIES START SMTW TFS HH MMA M 0 0 1 0 0 0 0 W ARNING DLY TIME 00 Start Time 01-12 (00-23) † = hour 00-59 = minute 0 = AM; 1 = PM (if applicable) Days = place “1” under days [∗] to continue Warning Delay Time 01-15 = arm warning delay time in minutes [∗] to continue STOP SMTW TFS HH MMA M 0 0 1 0 0 0 0 Stop Time 01-12 (00-23) † = hour 00-59 = minute 0 = AM; 1 = PM (if applicable) Days = place “1” under days [∗] to continue REPEAT OPTION 0-4 X Repeat Option 0 = do
Installation and Setup Guide 5-26
S E C T I O N 6 System Communication and Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Panel Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful transmission consists of both the method of communication between the control panel and the Central Station receiver; and the actual way the information is sent and displayed at the Central Station.
Installation and Setup Guide The following table describes each format in greater detail. FORMAT TYPE DESCRIPTION 3+1 and 4+1 Standard Formats 3+1 and 4+1 Expanded Formats Comprises a 3- (or 4-) digit subscriber number and a single-digit report code (e.g., Alarm, Trouble, Restore, Open, Close, etc). Comprises a 3- (or 4-) digit subscriber number and a two-digit report code. The first digit is displayed on the first line.
System Communication and Operation ** Characters in parenthesis are included in Robofon 8 format.
Installation and Setup Guide Robofon 8 Format Robofon 8 format send 0 data in a pulsed frequency format in the following protocol: B0 B1 B2 B3 B4 B5 B6 Par First bit 1 Last Bit Tone = 0, No tone = 1 Freq = 1000Hz ± 5Hz ‘U’ N1 N2 N3 N4 N5 N6 N7 N8 First Byte ETX chk Last Byte 50 baud (20ms / bit) 200ms / char, 11 chars / message (‘U’ = 55h and ETX = 03h) Physical format Logical format • 1000 Hz +/- 5Hz pulsed signaling • Tone = logical 0 • Silence = logical 1 • Speed is 50 baud, 2
System Communication and Operation ADEMCO Contact ID® ADEMCO and Robofon Contact ID® Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ where: CCCC(CCCCCC) =4-digit or 10-digit Customer (subscriber) ID Q = 1-digit Event qualifier, where: E = new event , and R = restore EEE =3-digit (hexadecimal) Event code (see central office receiver manual for a complete list of event codes) GG = 2-digit Partition Number (system messages show “00”) ZZZ = 3-digit Zone/contact ID number reporting the alarm, or
Installation and Setup Guide Security Codes The system supports up to 16 security codes, which can each be assigned one of 5 authority levels. The authority level determines the functions each code can perform as follows: Authority Levels (authority levels can be assigned to users 3-49 only; users 1 and 2 cannot be changed) Level Installer User No.
System Communication and Operation Arming Mode AWAY STAY NIGHT-STAY SUMMARY OF ARMING MODES Features for Each Arming Mode Exit Delay Entry Delay Perimeter Armed Yes Yes Yes Yes Yes Yes Yes Yes Yes INSTANT MAXIMUM Yes Yes No No Yes Yes Interior Armed Yes No only those zones listed in Night-Stay zone list No Yes Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual.
Installation and Setup Guide Keypad Commands (cont’d) Function Description Disarming Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to press OFF; entering the security code alone disarms the system. Bypassing Zones Enter code + BYPASS [6] + zone number(s). Can bypass while system armed/disarmed. Forced (Quick) Bypass To automatically bypass all faulted zones, use the “Quick Bypass” method. Enter code + BYPASS + [#], then wait for all open zones to be displayed.
System Communication and Operation Follow-Me Feature This feature lets users enter up to three phone numbers (system-wide) that the system will call in the event of an alarm in any partition at the protected premises, thus alerting the user to the alarm. • When an alarm occurs, the system reports the alarm to the central station (and pagers, if programmed), then, if programmed, dials the first follow-me phone number and proceeds as follows: 1.
Installation and Setup Guide From a FIXED-WORD KEYPAD: User code + [#] + [6] [2] • The first follow-me phone number (if one exists) is displayed one digit at a time. When done, the keypad beeps twice then displays the number “1,” indicating phone number 1. • To display phone numbers 2 or 3, press “2” or “3” respectively. The selected phone number will be displayed one digit at a time followed by two beeps when done. The number “2” or “3” will then be displayed, indicating the selected phone number.
System Communication and Operation Various System Trouble Displays Alpha Display Fixed Disp. Meaning ALARM CANCELED CA Appears if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open and the zone was not auto-bypassed), but the system was disarmed during the Entry Delay time. The alarm sounder and keypad sounder stop when the system is disarmed. No message will be transmitted to the central station.
Installation and Setup Guide Various System Trouble Displays (cont’d) Busy-Standby dl If this remains displayed for more than 1 minute, the system is disabled. Modem Comm CC The system is in communication with the central station for change of function or status verification. no display no display Power Failure If there is no keypad display at all and the LEDs are unlit, operating power (AC and battery) for the system has stopped and the system is inoperative.
S E C T I O N 7 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test:Checks that all zones have been installed properly. Dialer Test: Checks that the phone connection to the central station is working properly. Go/No Go Test: Checks that transmissions can be received from transmitters. Should be performed before permanently mounting transmitters.
Installation and Setup Guide Checking Zones Using One-Man Walk Test (Sniffer Mode) Use this mode to test all zones (wired and wireless) that have been programmed. Make sure all partitions are disarmed before trying to enter this mode, since this is a system-wide command. 1. Press [Installer code] + [#] + 3. NOTE: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode. If so, wait a few minutes, and try again.
Testing the System Dialer Communication Test 1. Enter Installer Code + 5 [TEST], then press “1” at the prompt to start the Dialer Test. 1=DIAL, 0=WALK (no special display on Fixed-Word keypads) The following will be displayed (accompanied by 2 beeps) if test is successful: PHONE OKAY (“Cd” displayed on Fixed-Word Display Keypads) A Contact ID report will also be sent (code 601) If the dialer test is unsuccessful, the following is displayed: COMM FAILURE 2.
Installation and Setup Guide 7-4
S E C T I O N 8 Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SECURITY CONTROL 1. 2. Physical: 318mm x 368mm x 76mm Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA minimum transformer RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH minimum (sealed lead acid type). Charging Voltage: 13.8VDC. ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V sirens or can drive one or two 702 (series ) self-contained 20-watt sirens. Do not connect two 702s in parallel.
Installation and Setup Guide COMPATIBLE DEVICES Keypads: Wireless Receivers: Zone Expansion: Relay Module: Internet/Intranet Communicator: EUREKA Network Interface: 8-2 6128RF, 6148, 6150, 6150RF, 6150V, 6160V, 6164 5881ENL: accepts up to 8 transmitters 5881ENM: accepts up to 16 transmitters 5881ENH: accepts up to system maximum transmitters 5883M: accepts up to 16 transmitters 5883H: accepts up to system maximum transmitters 6128RF: accepts up to 16 transmitters plus 8 wireless keys 6150RF: accepts up
Specifications & Accessories 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). LOOP 3 LOOP 2 LOOP 2 (REED) LOOP 1 LOOP 1 (TERMINALS) LOOP 1 5802MN2 ENROLL AS "UR" OR "RF" 5801 ENROLL AS "UR" OR "RF" LOOP 3 LOOP 4 YOU MUST ENROLL THIS BUTTON ON O F F LOOP 2 (AUX.
Installation and Setup Guide Compatible 5800 Series Transmitters Table (cont’d) Model Product 5804BD Bi-Directional Wireless Key 5806 5807 5808LST Wireless Photoelectric Smoke Detectors RF 5809 Heat Detector RF 5816 5816MN Door/Window Transmitters RF 5816TEMP Low-Temp. Sensor RF 5817 Multi-Point Universal Transmitter RF 5818 Recessed Transmitter RF 5819 Shock Processor Transmitter 8-4 Input Type BR Only RF Description • House ID must be set.
Specifications & Accessories Compatible 5800 Series Transmitters Table (cont’d) Model 5819WHS 5819BRS Product Shock Processor Transmitter Input Type RF 5827 Wireless Keypad Uses House ID only 5827BD Wireless Two-Way Keypad Uses House ID only 5849 5852 Glassbreak Detector 5890 5890PI PR Detector 5899 Magnets RF RF or RM Description • Has built-in shock sensor. • Has built-in tampered cover switch.
Installation and Setup Guide 8-6
S E C T I O N 9 Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
Installation and Setup Guide • Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms.
Limitations and Warranty LIMITED WARRANTY Honeywell International Inc.
Installation and Setup Guide 9-4
S E C T I O N 1 0 Index • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 1321 .......................................2-5 1321X10......................2-16, 2-17 24-Hour Audible Alarm ...........3-6 24-Hour Auxiliary Alarm..........3-6 24-Hour Silent Alarm ..............3-6 3+1 and 4+1 Standard Formats ............................6-2 4204 .1-2, 1-3, 2-7, 2-9, 2-15, 3-1, 5-12, 5-13, 6-8, 8-2 4219 ..1-1, 1-2, 1-3, 2-7, 2-10, 8-2 4229 .
Installation and Setup Guide Pager Programming Fields ..4-13 Pager Report Options ..........4-14 Paging .................................4-12 Panic Keys.............................6-8 Partitions................................3-2 Perimeter Burglary.................3-5 Phone Line ..........................2-18 Phone Module…….1-1, 2-4, 2-7, 2-19, 4-13 Power Failure .............5-16, 6-12 power supply ...........2-3, 2-5, 9-1 Power Up In Previous State...4-4 Powerline Carrier Device (X-10) House ID .........
N219 2 + 3 ALL OUTPUTS ARE POWER LIMITED. 4 + NOTE: KEYPAD (S) CURRENT (IN ALL PARTITIONS) AND ALL OTHER DEVICES DRAWING POWER FROM TERMS 4 & 5 MUST BE INCLUDED IN AUX CURRENT DRAIN CALCULATIONS. USE TRIGGER MODULE AUX POWER TERMINALS FOR SUPERVISED AUX POWER CONNECTION AUX. POWER OUTPUT 10.5-13.8VDC 700mA MAX INCLUDING TRIGGERS 1 AND 2 FOR COMPLETE INFORMATION, SEE INSTRUCTIONS K10022-1 ALARM OUTPUT 10.5–13.8VDC, 2A MAX. STEADYFOR BURGLARY/PANIC, TEMPORAL PULSE SOUNDING FOR FIRE.
165 Eileen Way, Syosset, New York 11791 Copyright © 2005 Honeywell International Inc. www.honeywell.com/security ÊK10022-1V1CŠ K10022-1V1 10/05 Rev.