Installation manual

14
Start Output Definition mode by pressing
80 while in Data Programming mode.
Output Funct. #
(00 = Quit) 01
Enter the output function number to be defined
01-12 = output function number
[] to continue
00 = exit
01 A E P Trig
?00 0 0 ZL=1
This screen displays a summary of the current output programming
A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type
Question mark indicates the device shown has not been mapped. Use *79 Menu mode to map the device.
[] to continue
01 Activated By:
Zone List
Select where the initiating event for this output definition is to occur.
0 = delete (deletes the output function and any previous programming)
Delete? To delete this output definition, press 1.
0 = NO, 1 = YES If you do not want to delete this output,. press 0.
1 = zone list (go to A prompt)
2 = zone type (go to B prompt)
3 = zone number (go to C prompt)
[] to continue
A
01 Zn List
1
If zone list was selected, this screen appears. Otherwise skip to the next row.
Enter the desired zone list number associated with this output number:
01-12 = zone list (Do not use zone lists 09-11 in output definitions if they are being used for paging)
Enter the zone list event that will activate this output:
Enter Event 0 = restore; 1 = alarm;
Alarm 1 2 = fault; 3= trouble
[] to continue
NOTE: For alarm, fault, and trouble, an event on ANY zone in the list activates the output.
Press [] to continue and skip to the Output Action prompt.
B
01 Enter Zn type
Perimeter 03
If zone type was selected, this screen appears. Otherwise skip to the next row.
Enter the desired zone type for this output number. See list above *80 Worksheet for zone types.
Enter the partition in which this zone type will occur.
01 Partition 0 = any partition; 1 = partition 1;
Any partition 0 2 = partition 2; 3 = common partition
Press [] to continue and skip to the Output Action prompt.
C
01 Enter Zn No.
12
If zone number was selected, this screen appears.
Enter the desired zone number associated with this output number.
Press [] to continue.
Enter the zone event that will activate this output.
01 Enter Event 0 = restore; 1 = alarm;
Restore 0 2 = fault; 3= trouble
Press [] to continue to the Output Action prompt
01 Output Action
Close for 2 sec 1
Enter the desired device action as listed below.
0 = off 4 = Change Device State
1 = Close for 2 seconds 5 = Duration 1 (see data field *177 entry 1, from 15 secs to 15 minutes)
2 = Close and Stay Closed 6 = Duration 2 (see data field *177 entry 2, from 1 to 7 days)
3 = Continuous Pulse on & off (1 sec ON, 1 sec OFF)
Press [] to continue.
Enter Output No.
R02 02
Enter the device output number (programmed in *79 Menu Mode) you want associated with this output.
01-04 = output no.
17-18 = on-board triggers
Press [] to continue.
02 A E P TRIG
R02 1 1 3 ZL=1
A summary screen appears showing the programmed settings.
Press [] to return to output function number prompt.