Installation manual

13
80 OUTPUT DEFINITIONS
NOTES: 1. For Relays, 4229, 4204 and 6164 devices are programmed in *79, *80, and *81 modes.
2. For Powerline Carrier devices (plcd), field
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Zone Types:
00 = Not used 08 = 24-Hr Aux 21 = ArmAWAY*
01 = Entry/exit #1 09 = Fire 22 = Disarm*
02 = Entry/exit #2 10 = Interior w/Delay 23 = No Alarm Resp
03 = Perimeter 12 = Monitor Zone 24 = Silent Burglary
04 = Interior Follower 14 = Gas 77 = Keyswitch
05 = Trouble Day/Alarm Night 15 = Medical 81 = AAV Monitor Zone
06 = 24-Hr Silent 16 = Fire w/Verify 82 = Blockschloss Keyswitch
07 = 24-Hr Audible 20 = ArmSTAY* 90-93 = Configurable *5800 button-type transmitters only
Choices for System Operation are: ** Use 0 (Any) for Partition No. (P) entry.
20 = ArmingStay 38 = Chime 60 = AAV Trigger *** Or at Disarming, whichever occurs earlier.
21 = ArmingAway 39 = Any Fire Alarm 66 = Function key (use *57 Menu Mode to assign the function key, function 07,)
22 = Disarming (Code + OFF) 40 = Bypassing 67 = Siren Failure
31 = End of Exit Time 41 = **AC Mains Failure 68 = Telecom Line Fault
32 = Start of Entry Time 42 = **System Battery Low 69 = Telecom Line Fault Restore
33 = Any Burglary Alarm 43 = Communication Failure 70 = AC Mains Restore**
36 = **At Siren Timeout*** 46 = System Low Battery Restore** 71 = System Startup/Clock Not Set
52 = Kiss off 72 = Clock Set
54 = Fire Zone Reset 78 = Keyswitch red LED (device action not used for this option)
58 = Duress 79 = Keyswitch green LED (device action not used for this option)
80 = any tamper in the system
OUTPUT DEFINITION WORKSHEET
Activation Type and Detail Event (for zone list/activated by)Output
Function
Number
(1-12)
Activated by
0=delete
1=zn list
2=zn type
3=zn no.
Zone List
(ZL)
1-12 = list
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
01-06, 09-
24, 49-64
Partition
Number
(P)
(if using ZT trig)
0 = any
1 = partition 1
2 = partition 2
3 = common
By Zone List
0 = restore
1 = alarm
2 = fault
3 = trouble
By Zone No.
0 = restore
1 = alarm
2 = fault
3 = trouble
4 = off-normal
Action
0 = off
1 = close 2
secs
2 = stay closed
3 = pulse
4 = toggle
5 = duration 1
††
6 = duration 2
††
Output
Number
1-18= dev
Device
Type
R = relay
T = trigger
X = X10
1
2
3
4
5
6
7
8
9
10
11
12
†† Duration is set in program field *177. Duration 1 (action 5) is from 15 seconds to 15 minutes. Duration 2 (action 6) is from 1 day to 7 days.