Installation Manual
8
ISU # ISU Name ISU Options (defaults in bold) Notes
165 Lockout Setpoint 0 = Disabled
1 = Enabled
If user attempts to modify the setpoint, flash Locked segment and revert to
current setpoint if lockout is enabled.
167 Lockout Vane
Direction
0 = Disabled
1 = Enabled
If user attempts to modify the vane direction, flash Locked segment if lockout
is enabled.
170 Hide Indoor
Temperature
0 = Disabled
1 = Enabled
If enabled, indoor temperature is not shown in the display.
171 Hide Indoor
Humidity Display
0 = Disabled
1 = Enabled
If enabled, indoor humidity is not shown in the display.
172 Hide Outdoor
Temperature
Display
0 = Disabled
1 = Enabled
If enabled, outdoor temperature is not shown in the display.
173 Hide Outdoor
Humidity Display
0 = Disabled
1 = Enabled
If enabled, outdoor humidity is not shown in the display.
180 Max Heat Setpoint 40 to 90°F (4.5 to 32°C)
181 Min Cool Setpoint 50 to 99°F (10 to 37°C)
190 Indoor Temperature
Source
0 = Thermostat
1 = Wall Unit
2 = Sensor
3 = Average
Options 2 and 3 not shown if the IAS is not enrolled.
191 Indoor Temperature
Display Offset
-5°F to 5°F (-2.5°C to 2.5°C)
195 Indoor Humidity
Source
0 = Thermostat
1 = Sensor
2 = Average
Options 1 and 2 will not be shown if the IAS is not enrolled.
196 Indoor Humidity
Display Offset
-10 % RH to 10% RH
Installer Setup options (ISU) – advanced menu