User manual

7LST700 SERIES USER MANUAL • Approved Document No. DFU7001003 Rev 4
LST700 SERIES FIRE ALARM PANEL
1 to 8
1 to 8
Testing the Indicator Lights
To test the panel’s indicator lights are working correctly, press the Lamp Test button when the panel is in the
Accessed state. The panel’s internal beeper will also sound when pressing the button to show it is working correctly.
What the Indicators mean
The table below summarises the various indicators available on the Fire Alarm Panel and what they mean in their
various States. The final column highlights the page(s) you should turn to for further information.
INDICATOR STATUS OF LIGHT WHAT THIS MEANS FURTHER READING
(General Fire) Flashing Red The Panel has detected a fire alarm condition
Page 8 (Fire Conditions)
or the Activate Sounders button has been
pressed to evacuate the building
Steady Red There is a silenced fire alarm condition
Page 8 (Fire Conditions)
on the system.
Fire Zones Flashing Red A fire alarm condition has been detected on
Page 8 (Fire Conditions)
the zones which are flashing
Steady Red There is a silenced fire alarm condition on
Page 8 (Fire Conditions)
the zones which are lit steady
Zone fault/disabled/test Flashing Yellow Faulty wiring has been detected on the zones
Page 9 (Fault Conditions)
(in sync. with the which are flashing
gen. fault indicator
Flashing Yellow The zones which are flashing are in test mode
(in sync. with the
Test indicator)
Steady Yellow The zones which are lit steady have been disabled
Page 10 (Disablements)
supply present Steady Green The panel is supplied with power
Page 4 (Overview)
remote output Steady Red The remote output has been activated
Page 4 (Overview)
test Flashing Yellow The panel is in test mode
accessed Flashing Yellow The access code is in the process of being entered
Page 6 (Accessing the Controls)
Steady Yellow The panel is in access level two
Page 6 (Accessing the Controls)
general disablement Flashing Yellow The panel is in the disablement selection state
Page 10 (Disablements)
Steady Yellow Part of the system has been manually disabled
Page 10 (Disablements)
and/or one or more of the fire zones have had
Page 12 (Notes on Delays)
a delay applied to them
fault output status Flashing Yellow Faulty wiring has been detected on the fault
Page 9 (Fault Conditions)
output’s transmission path
Steady Yellow The fault output has been disabled
Page 10 (Disablements)
remote output status Flashing Yellow Faulty wiring has been detected on the remote
Page 9 (Fault Conditions)
output’s transmission path
Steady Yellow The remote output has been disabled
Page 10 (Disablements)
general fault Flashing Yellow A fault has been detected on the system
Page 9 (Fault Conditions)
power supply fault Flashing Yellow The panel has detected a fault with its power
Page 9 (Fault Conditions)
supply, battery charger or back-up batteries
system fault Flashing Yellow The panel has detected a microprocessor fault
Page 9 (Fault Conditions)
repeater fault Flashing Yellow The panel has detected a wiring/communication
Page 9 (Fault Conditions)
fault on the repeater network
sounder status Flashing Yellow Faulty wiring has been detected on the panel’s
Page 9 (Fault Conditions)
sounder circuits
Steady Yellow The alarm sounders have been disabled
Page 10 (Disablements)
auxiliary output status Steady Yellow The panel’s auxiliary output has been disabled
Page 10 (Disablements)
Flashing Yellow Faulty wiring has been detected on the auxiliary
Page 9 (Fault Conditions)
output’s transmission path
output delays Steady Yellow Delays have been programmed into the panel
Page 12 (Notes on Delays)
Flashing Yellow A delay is running
Page 12 (Notes on Delays)