Operating instructions

2XXX X=1..128 delete Preset position X from the Patrol sequence
3XXX X=0..255 assign a pause (dwell time) in seconds when the position is reached
Example 1000 delete the previously defined sequence
1001 insert preset position 1 in the sequence
1005 insert position 5 in the sequence
1006 insert position 6 in the sequence
2005 remove position 5
To start the Patrol sequence see (see § 6.4.9 -Patrol, pag.117).
OTHER FUNCTIONS
4XXX The dome can be configured to move automatically to a “return position” after a set
period of inactivity.
The first two digits indicate the return position to be considered (only positions from 01
to 99 are accepted, positions from 100 to 128 cannot be selected)
the third digit indicates the return time:
0: 10 seconds, 1: 20 seconds, 2: 30 seconds,
3: 40 seconds, 4: 1 minute, 5: 2 minutes,
6: 5 minutes, 7: 10 minutes, 8: 20 minutes,
9: 40 minutes
For example, the code 4216 will configure the dome to return to position 21 (21) after 5
minutes (6) of inactivity.
The code4000” disables the return position.
400 Text shown/hidden (toggle)
500 Backlight compensation on/off (toggle)
9999 Reset dome internal memory