VISTA 4140XMPT2 PARTITIONED SECURITY SYSTEM with SCHEDULING INSTALLATION INSTRUCTIONS and PROGRAMMING GUIDE N5944-9 4/96
CONGRATULATIONS! On Your Purchase Of The Ademco 4140XMPT2 The purpose of these Installation Instructions is to give you a complete overview of the system, and provide instructions for installing a basic system. CONTACTING TECHNICAL SUPPORT PLEASE, Before you call Technical Support, be sure you: • READ THE INSTRUCTIONS! • Check all wiring connections. • Determine that the power supply and/or backup battery are supplying proper voltages. • Verify your programming information where applicable.
TABLE OF CONTENTS PART 1. INSTALLATION INSTRUCTIONS ................................................. 6 Section 1. GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 SUMMARY OF SYSTEM FEATURES.......................................................................................................... 7 System Features...................................................................................
PART 2. PROGRAMMING GUIDE ............................................................. 4 2 Section 1. SYSTEM LAYOUT WORKSHEETS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3 Section 2. GENERAL PROGRAMMING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 0 Communication Default Programming ......................................................................................
PART 3. SYSTEM OPERATION and TESTING....................................... 1 0 5 Section 1. SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 0 6 SECURITY ACCESS CODES ................................................................................................................106 User Codes & Levels Of Authority.....................................................................................
PART 1 INSTALLATION INSTRUCTIONS –6–
Section 1. GENERAL INFORMATION SUMMARY OF SYSTEM FEATURES General Information The following table lists the major features of the 4140XMPT2 system. System NOTE: At least one 6139 addressable alpha display console must be used with this system. The 4140XMPT2 Control is a microprocessor based, programmable, partitioned system, and features EEROM memory technology (power loss does not result in the loss of information). Zones Supported • Supports up to 9 traditional wired zones of protection.
System Features The following table lists the special system features of the 4140XMPT2 system. Global Arming • Allows users to easily arm multiple partitions via console prompts. Polling Loop • Built-in polling loop interface, with polling loop terminals located on the panel's terminal block, allows expansion up to 87 zones. Glass Break Detector • Supports up to 50 latching type 2-wire glass break detectors on zone 8.
Programming Features Communication Features The following table lists the programming features of the 4140XMPT2 system. User Codes • Up to 128 user security codes (max. 99 per partition) can be programmed, each with various levels of authority. Installer Code • Installer code override feature. Installer code will disarm system only if it was used to arm the system. Alpha Descriptors • All zones and partitions can be assigned alpha descriptions. • The letter "s" or " 's " can be added to descriptors.
INTRODUCTION TO THE PARTITIONED SYSTEM This section is intended to give you an overview of partitioning concepts. For specific questions on programming or using specific aspects of the panel, please refer to the SYSTEM OPERATION section of this manual and the PROGRAMMING GUIDE. Introduction Basic Partitioning Features – 10 – The partitioned system represents the latest in security protection technology.
Examples Of Partitioning In surveying dealers throughout the country, we have learned of two global applications for partitioned control panels. One is a typical two family house (residential), the other a Factory/Office environment. These broad classifications can better be understood by way of examples. Two Family House: You've just arrived at a job site to quote a security system.
SCHEDULING OVERVIEW Major Features Of Scheduling Scheduling is an exciting new feature of the 4140XMPT2 and provides the following functions. Arm/Disarm control Scheduling can be used to automate some of the system operation: _ Auto arming and disarming at predetermined times.
Section 2. ZONE CONFIGURATIONS ZONE TYPES & APPLICABLE SENSORS The 4140XMPT2 supports up to 87 zones of hard-wire, polling loop and/or wireless protection, distributed among up to 8 partitions. The following table lists the zone numbers and the types of sensors that can be used with each in this system: Zone Sensors 1 7 8 1-9 1-63 1-87 10-87 95 96 99 Type 00 Zone Not Used Type 01 Entry/Exit #1 Burglary. Type 02 Entry/Exit #2 Burglary. Type 03 Perimeter Burglary. Type 04 Interior, Follower.
Type 06 24-hour Silent Alarm. Type 07 24-hour Audible Alarm. Type 08 24-hour Auxiliary Alarm. Type 09 Supervised Fire. (No Verification) Type 1 0 Interior w/Delay. Type 20 Arm-Stay* This zone type sends a report to the Central Station but provides no console display or sounding. This zone type is usually assigned to a zone containing an Emergency button. This zone type sends a report to the Central Station, and provides an alarm sound at the console, and an audible external alarm.
BASIC 9 HARD-WIRED ZONES Zone 1 The following table summarizes zone 1 characteristics. Applications Can be used for EOLR supervised or closed circuit unsupervised devices. It is the only zone that supports 2-wire smoke detectors. Zone Response Type: Any Response Time 350 msec Max. Zone Resistance 100 ohms, excluding EOLR Unsupervised Usage • Cut red PCB jumper. • Only closed circuit devices can be used. EOLR Supervised • Leave red PCB jumper intact. • Supports both open circuit and closed circuit devices.
Zones 2 - 8 The following table summarizes zones 2-8 characteristics. Applications Can be used for EOLR supervised or closed circuit unsupervised devices. Can also support 4-wire smoke detectors. Zone 8 can support latching glass break detectors. Zone Response Type Any Response Time 350 msec Max. Zone Resistance • Zones 1-7: 300 ohms, excluding EOLR • Zone 8: 100 ohms, excluding EOLR Unsupervised Usage • EOLR disabled in field *41 (enter 1). • Only closed circuit devices can be used.
2-WIRE POLLING LOOP EXPANSION (Zones 10 through 87) General Information The following table summarizes polling loop expansion characteristics. Applications • Built-in 2- wire polling loop interface allows the number of zones to be expanded from the basic 9 zones to up to 87 zones using various Remote Point Modules (RPMs). See ADVISORIES below. • The polling loop provides power to sensors and serves as communication path between the panel and sensors.
Important! Fault Annunciation Since the polling loop and the RF receiver(s) are shared among the 8 partitions, the scheme for annunciating their failure is as follows: Respective faults (for zones 88-91 & 97) will report as trouble conditions only, and as such, should be assigned either zone type 00 if no annunciation is desired, or zone type 05 if annunciation as trouble condition is desired.
WIRELESS EXPANSION (Zones 1-63) General Information (Receivers) Transmitters Supported by various receivers Receiver 4280 4280-8 4281H 4281M 4281L 5881H 5881M 5881L Transmitter 63 8 63 8 4 64 16 8 The following table summarizes wireless expansion characteristics. Zones Supported • The system supports up to 63 wireless transmitters (5700 or 5800 series), plus a wireless keypad. • To expand the system using wireless, one or two of the same type of RF Receivers can be used.
The following table highlights the features of each receiver. 4280 Series Receiver 4280 is not recommended for new installation; receiver is scheduled to be discontinued. FEATURE 4280 series 4281 series 5881 series Wiring Connects to polling loop Connects to console lines Connects to console lines House ID set via DIP switches programmed via #93 programmed via #93 Menu Mode. Menu Mode. Receiver Address Set by cutting blue jumper in 2nd receiver. Enabled via fields 1*26 & 1*27.
Transmitters NOTE: After replacing a low or dead battery, activate the transmitter and enter the security code + OFF to clear its memory of the "Low Battery" signal. The following table summarizes wireless transmitter characteristics. Transmitters (General) • Supports 5700 or 5800 series transmitters. • Each transmitter has its own unique transmitter ID number (Zone #). 5700 series transmitters use DIP switches to set the ID. 5800 series transmitters must have their ID numbers "learned" by the system.
Note On RF Keys (5801, 5803, etc.) 5800 series RF keys can be used to arm and disarm the system. These transmitters include the 5801, 5803, 5804, and any other 5800 series transmitter if programmed for one of zone type responses 20-22. These transmitters are tied to a user in order to provide a record of who armed or disarmed the system.
Important Battery Notice The wireless transmitters are designed to provide long battery life under normal operating conditions. Longevity of batteries may be as much as 4-7 years depending on the environment, usage, and the specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation.
Compatible 5800 Series Wireless Devices 5801 4-Button Transmitter 5802 Pendant Panic Transmitter 5802CP Belt Clip Panic Transmitter 5802MN Belt Clip or Pendant Panic Transmitter 5803 3-Button Transmitter 5804 4-Button Transmitter 5806 Photoelectric Smoke Detector 5807 Photoelectric Smoke Detector 5816 Miniature Transmitter 5817 3-Point Transmitter 5818 Recessed Transmitter 5827 Wireless Keypad 5849 Glass Break Detector 5890 Dual Element PIR – 24 – • • • • • • • • • • • • • • Four button hand held or
VOLTAGE TRIGGERS (Connector J7) (Ground Start Module, Keyswitch, Remote Console Sounder) Connector J7, located on the right hand side of the main PCB provides 4 trigger outputs for operating the 675 Ground Start Module, the 4146 Keyswitch, a remote console sounding piezo, and for triggering auxiliary alarm signaling equipment. Note that these output triggers can be enabled by partition via programming field 2*20. The pin assignments of this connector are shown below.
Remote Keyswitch If the keyswitch option is selected (field *15), the alarm trigger outputs are disabled. An optional Remote Keyswitch can be used for remote arming and disarming of the system. Note that keyswitch arming may only be used in one partition. If used, program field *15 must be set to the desired partition to enable the keyswitch option, and the 4146 keyswitch's normally open momentary switch and LEDs must be connected to Zone 7 and to the J7 connector trigger outputs respectively.
Ground Start Module An optional 675 Ground Start module can be used for installations having telephone lines which require ground start instead of loop start operation to obtain dial tone from the telco central office. If used, program field 1*46 must be set to "0" (factory default) and the 675 Ground Start Module must be connected to the panel's J7 connector trigger output 1, to auxiliary power, and to the "RING" side of the telephone line as shown in the diagram below.
OUTPUT CONTROL (4204 Relay Module/X-10 Devices) General Information 4204 Relay Module 4300 Transformer & X-10 Devices The 4140XMPT2 supports up to 16 relay outputs. These outputs may consist of relay outputs from the 4204 output relay module (4 relay outputs per module) or X-10 device outputs. Outputs can be activated and deactivated by predetermined events such as turning on lights in the event of an alarm condition and/or closing a fire door in the event of a fire alarm condition.
EXAMPLES OF USES FOR RELAYS The following table lists examples of some possible uses for relays. Refer to the Relay Programming section of the PROGRAMMING GUIDE for detailed information. L IST OF S T A R T A = Action 0=No Response; 1=Close for 2 seconds; 2=Close and stay closed; 3=Pulse on and off EV = Event 0=Not used; 1=Alarm; 2=fault; 3=Trouble; 4=Restore AND S T O P ZL = ZONE List 1 to 8 (from Field *81) or 0=Not Used. Upon restore of all zones on RESTORE of ZONE LIST, relay action will STOP.
START ACTION DESIRED STOP A EV ZL ZT P ZL ZT P 1 0 0 38 X 0 00 X 1 2 X 00 X 0 00 X Zones in zone list (x) close relay for 2 seconds on alarms 1 1 X 00 X 0 00 X Zones in zone list (x) close relay for 2 seconds on troubles 1 3 X 00 X 0 00 X Zones in zone list (x) close relay on alarms and reset at bell timeout or when disarmed by any either partition.
START ACTION DESIRED STOP A EV ZL ZT P ZL ZT P Close relay on Burg alarm, reset with entry of security code + # + 7 + 1 2 1 X 33 X X 34 X Close relay on Fire alarm, reset with entry of security code +#+7+1 2 1 X 09 X X 34 X 1 0 0 41 X 0 00 X 3 0 0 32 X 0 22 X U NLOCK E XIT D O O R S T URN ON E MERGENCY L IGHTING An AC loss detection causes relay to close for 2 seconds.* *The relay will not reset on restoral of low battery or AC power.
Section 3. REMOTE CONSOLES, SOUNDERS & PHONE CONNECTIONS REMOTE CONSOLES General The Control supplies up to 750 mA of auxiliary power for remote consoles, polling loop devices and/or other auxiliary devices such as motion detectors or 4-wire smoke detectors*. The Controls support, independent of auxiliary power considerations, up to 16 addressable remote consoles (6128, 6139).
Consoles may be wired to a single wire run or individual consoles may be connected to separate wire runs. The maximum wire run length from the panel to a console which is homerun back to the panel must not exceed: Wire Gauge #22 gauge (0.64mm) 450 feet (137m) #20 gauge (0.80mm) 700 feet (213m) #18 gauge (1.0mm) 1100 feet (335m) #16 gauge (1.
EXTERNAL SOUNDERS Relay Output Compatible Sounders 702 Outdoor Siren (not CE approved) 719 Compact Outdoor Siren (not CE approved) 747 Indoor Siren (not CE approved) ABB1031 Motor Bell & Box PA400B (beige)/PA400R (red) Indoor Piezo Sounder The Control provides a wet bell relay output which is used to power external alarm sounders. Connections are made to terminals 4 (positive output) and 5 (negative return). See SUMMARY OF CONNECTIONS Diagram. The total current drawn from this output can be up to 2.
Section 4. MOUNTING THE CONTROL, PC BOARD & LOCK General Mounting The 4140XMPT2 PC Board Advisory The 4140XMPT2 is supplied with a 12.5"W x 14.5"H x 3"D cabinet suitable for use in residential and non-certified commercial burglary installations. Mount the Control cabinet to a sturdy wall using fasteners or anchors (not supplied) in a clean, dry area which is not readily accessible to the general public. The back of the Control cabinet has 4 holes for this purpose.
Section 5. POWERING THE SYSTEM POWERING THE SYSTEM Primary Power Power to the Control panel is supplied by model No. 1361* Plug-in Transformer which is rated at 16.5VAC, 40VA. Caution must be taken when wiring this transformer to the panel to guard against blowing the fuse inside the transformer (non-replaceable). * NOTE: Use 1361CN Transformer in Canadian installations. Back-Up Power In the event of an AC power loss, the Control panel is supported by a back-up, rechargeable gel cell battery.
POLLING LOOP CURRENT DRAIN WORKSHEET RPM DEVICE CURRENT # UNITS TOTAL CURRENT 4194 Contact 4192SD Photo Smoke 4192SDT Smoke w/Heat 4192CP Ion Smoke 4275EX Dual PIR 4278EX Quad PIR 4190 2-Zone RPM 1 mA 0.4 mA 0.4 mA 0.4 mA 1 mA 1 mA 1 mA (LOW) 2 mA (HIGH) 4208 8-Zone RPM 16 mA 4280 63 Zone RF 40 mA 4280-8 8 Zone RF 40 mA TOTAL ** ** If the total current draw exceeds 64 mA, a 4297 Loop Extender module must be used.
Section 6. SETTING THE REAL-TIME CLOCK Procedure Important: This method is different from the previous method of setting the clock. NOTE: A 6139 alpha console must be used to set the real-time clock, or the clock can be set via the Downloader software. Only users with installer or master authority level can set the real-time clock. To enter real-time clock mode, enter installer or master code + #63.
Section 7. AUDIO ALARM VERIFICATION (AAV) This section provides the following information: • General information about the AAV option • AAV operation • Connecting an Eagle AAV Module • AAV programming requirements General Information An Audio Alarm Verification (AAV) module (also known as two-way voice), such as the Eagle 1241, is an add-on accessory that permits voice dialogue between an operator at a central station and a person at the alarm installation, for the purpose of alarm verification.
NOTES: 1. 685 Receiver software must be rev. 4.6 or higher. Earlier versions will not hold the phone line connection. 2. Contact ID code for "listen-in to follow" audio alarm verification is "606." Contact ID is the only reporting format that will send a "listen-in-to-follow.
Section 8. VIDEO ALARM VERIFICATION (VAV) This section provides only general information about the VAV option. Detailed information is contained in the manual provided with the VAV Transmitter. A Video Alarm Verification (VAV) transmitter, such as the AT100 (or VT-1000), is an add-on accessory that permits video imagery of the area where an alarm was detected to be transmitted on standard switched network telephone lines to the monitoring location for the purpose of alarm verification.
PART 2 PROGRAMMING GUIDE – 42 –
Section 1. SYSTEM LAYOUT WORKSHEETS As with any security system, you should first define the installation. This includes determining how many partitions will be used, how many zones per partition, and how many users per partition. You will also need to determine what peripheral devices will be needed, and basic system options such as exit/entry delays, etc.
SYSTEM DEFINITIONS BY PARTITION (enter values or yes/no) Option Entry Delay #1 (15-225 seconds): part 1 part. 2 part. 3 part. 4 part. 5 part. 6 part. 7 part. 8 Exit Delay #1 (15-225 seconds): Entry Delay #2 (15-225 seconds): Exit Delay #2 (15-225 seconds): Quick Arming Multiple Alarms per Arming Console Panic for zone 95 (* + 1) Console Panic for zone 96 (# + 3) Console Panic for zone 99 (* + #) Allow Sign-on (GOTO function) Non-Bypassable Zone* Sounder Timeout Duration (2 min.
ACCESS CODES 4-digit Security Code Access Group 2-digit 0; 1-8 user # 4-digit Security Code Access Group 2-digit 0; 1-8 user # 4-digit Security Code Access Group 2-digit 0; 1-8 user # Partition 1 Global Auth. Arm? level ACCESS CODES Partition 4 Global Auth. Arm? level ACCESS CODES Authority Levels: Partition 7 Global Auth. Arm? level & USER DEFINITIONS FOR PARTITIONS 1-3 open/ close 2-digit user # Partition 2 Global Auth. Arm? level open/ close 2-digit user # Partition 3 Global Auth.
ZONE DEFINITIONS FOR ZONES 1-24 DIP DIP _ Enter loop number on module Zone No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 – 46 – Parti- RF Trans. Type_ RPM RPM Zone tion RF UR BR left right Ser. Hard Report Type (1-8) (3) (4) (5) loop loop RPM_ Wired Code Loop number must be 1 for hardwire and DIP devices) Zone Information (part numbers) & Alpha Descriptor (3 words max.
ZONE DEFINITIONS FOR ZONES 25-48 DIP DIP _ Enter loop number on module Zone No. 25 Parti- RF Trans. Type_ RPM RPM Zone tion RF UR BR left right Ser. Hard Report Type (1-8) (3) (4) (5) loop loop RPM_ Wired Code Loop number must be 1 for hardwire and DIP devices) Zone Information (part numbers) & Alpha Descriptor (3 words max.
ZONE DEFINITIONS FOR ZONES 49-72 DIP DIP _ Enter loop number on module Zone No. 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 – 48 – Parti- RF Trans. Type_ RPM RPM Zone tion RF UR BR left right Ser. Hard Report Type (1-8) (3) (4) (5) loop loop RPM_ Wired Code Loop number must be 1 for hardwire and DIP devices) Zone Information (part numbers) & Alpha Descriptor (3 words max.
ZONE DEFINITIONS FOR ZONES 73-87 DIP DIP _ Enter loop number on module Zone No. 73 Parti- RF Trans. Type_ RPM RPM Zone tion RF UR BR left right Ser. Hard Report Type (1-8) (3) (4) (5) loop loop RPM_ Wired Code Loop number must be 1 for hardwire and DIP devices) Zone Information (part numbers) & Alpha Descriptor (3 words max.
Section 2. GENERAL PROGRAMMING PROCEDURES General Information Review the global and specific partitioning features listed in the GENERAL INFORMATION section of the Installation Instructions before programming the system. NOTE: A programming form has been included at the centerfold of this manual. The system is shipped with a set of pre-programmed default values that are designed to meet the needs of many installations.
Programming Steps 1. 2. 3. Set the consoles to the appropriate addresses. Set factory defaults by pressing *97. This will automatically enable console addresses 00-03, so be sure at least one console is set to one of these addresses.
Section 3. DATA FIELD PROGRAMMING PROGRAMMING SYSTEM-WIDE (GLOBAL) DATA FIELDS General Procedure The global (i.e. non partition-specific) programming fields are grouped into three sets (referred to as "pages"), as represented in the diagram below. The first page is accessed as soon as programming mode is entered. To access the other pages of fields (indicated on the programming form by a "1" or "2" in front of the 2-digit field address), press *94.
INDEX TO PROGRAMMING FIELDS In the following pages, the programming fields have been arranged by functional group. reference the numerical ordered fields on the programming form with the text.
DATA FIELD DESCRIPTIONS Refer to the programming form provided at the center of this manual while reviewing the following programming sections.
Control Options (continued) 4208 Zone #s available when: *86=1 *86=0 10-17 Precludes use of any other polling loop expansion. 10-16 33-40 41-48 49-56 57-64 65-72 73-80 74-87 * 2 6 Intelligent Test Reporting Enter 1 if it is desired that no test report be sent if any other type of report was sent since the last test report. Enter 0 if test reports are to be sent at the set intervals, regardless of other reports having been sent.
Downloader Options *35 Download Phone No. This field is applicable only if downloading will be utilized. Enter the downloading phone number, up to 12 digits (0-9). Do not fill unused spaces. * 3 6 Download ID No. Enter 00-09; A-F (10-15). Only applicable if downloading will be utilized.
Dialer Options (continued) *42 Dial Tone Pause This field sets the delay time for the Dial Tone Detect option, if true dial tone is not selected in that field. Enter the desired wait time for dial tone detection as follows: Enter single digit, 0 = 5 seconds; 1 = 11 seconds; or 2 = 30 seconds. Must be 0 for UL.
Dialer Options (continued) * 5 2 Standard/Expanded Report Primary Enter 0 for standard or 1 for expanded reporting for the primary phone line. Note: Expanded overrides 4+2 format. *53 Standard/Expanded Report Secondary Enter 0 for standard or 1 for expanded reporting for the secondary phone line. Note: Expanded overrides 4+2 format. *54-*78 Report Codes For Zones 1-64 & 81-87 Enter the appropriate report codes for each zone used in the system.
Wireless Options 1 * 2 8 RF TX Low Battery Annun. Enter 0 if audible beep and display annunciation upon RF transmitter low battery condition is desired only in disarmed state. Enter 1 if audible beep and display is desired in both armed and disarmed states. Must be 1 for UL. 1 * 2 9 RF TX Low Battery Report Enable 1*30 1*31 1*32 1*44 1*48 1*49 1*57 1*58 Partitioning Options 2*17 Enter 1 if a trouble message for RF transmitter low battery conditions is to be sent to the central station.
2 * 1 9 Use Partition Descriptors Enter 1 if partition descriptors will be programmed. If enabled, the normal console display will include a partition number and the partition descriptor (if programmed in #93 Menu Mode). Entering 0 causes the consoles to display a non-partitioned system type of display (no partition no. appears).
PROGRAMMING PARTITION-SPECIFIC DATA FIELDS General Procedure Values for some programming fields are system wide (global), and some can be different for each partition (partition-specific). Note that the partition-specific programming fields are automatically skipped when programming the global fields. The table below lists the partition-specific fields that can be defined for each partition. To access partition-specific fields, 1. Press *91, which will prompt you for the partition number desired. 2.
Partition-Specific Field Descriptions (continued) * 2 2 Console Panic Enables Enter 1 to enable the appropriate console panics used in this partition. Otherwise enter 0. * 2 3 Multiple Alarms Determines whether or not more than one alarm can be sounded in a given zone during an armed period. Note that multiple alarm soundings will not occur more frequently than allowed by the programmed alarm sounder duration.
Partition-Specific Field Descriptions (continued) 2nd Page Fields 1 * 4 3 Enable Permanent Display Backlighting Enter 1 if it is desired that backlighting for the console display remain on at all times. Enter 0 if the display should remain unlit unless a key is pressed. The backlighting then turns off again after a period of keypad inactivity. Note that when a key is pressed, display backlighting turns on for all consoles in that partition. 1 * 4 5 Enable Console Annun.
Section 4. PROGRAMMING WITH #93 MENU MODE General Information NOTE: The following fields should be preset before beginning: 1*26 First RF Expander; 1*27 Second RF Expander; 2*00 Number of Partitions; 1*32 receiver type. In addition, receivers should be programmed via Device programming.
Zone Programming Important!: Note that before programming zone characteristics, fields 1*26 & 1*27 (RF Expander Selects) and field 2*00 (number of partitions) and field 1*32 must be programmed. This identifies the use of RF Receivers and the number of partitions being used in the system. Enter Programming mode, then press #93 to display "ZONE PROG?". Press 1 to enter ZONE PROGRAMMING mode. The ZONE PROG? following screens will appear. Press * to display the 1=Yes 0=No next screen.
Serial Number Learning/Deleting SERIAL # PROG? 0=no 1=yes To learn or delete a device's serial number, enter 1 (yes). Enter 0 to move to the D e v i c e Programming menu. Enter zone no. 00=QUIT Enter the zone number of the device to be learned or deleted. Press * to move to the next prompt. Enter 00 to quit Serial Number programming. If the device for that zone number was not programmed as a serial number input device in the Zone Programming menus, a prompt indicating such will appear.
Device Programming This menu is used to program consoles, receivers and relay modules. From Data Field Programming mode, press #93 to display "ZONE PROG?". Press 0 repeatedly to display "DEVICE PROG?". DEVICE PROG? 1=yes 0=no Press 1 to enter DEVICE PROGRAMMING mode. DEVICE ADDRESS? 01-31 Enter the 2-digit ID number as set by the device's DIP switches (01-31). Press [*] to accept entry.
Relay Programming These relay output actions are performed in response to a programmed condition. The system can also activate relays to initiate and action at programmed times by using the #80 Scheduling Menu Mode–Time Driven Events function. – 68 – The 4140XMPT2 supports up to sixteen (16) X-10 and/or relay outputs. The X-10 interface is made via a 4300 plug-in transformer. Relay and X-10 devices are interchangeable in functionality.
The following is a list of choices for (ZT): CHOICES FOR SYSTEM CHOICES FOR ZONE OPERATION: TYPES: 00 = No Response (Not Used) 20 = Arming-Stay 21 = Arming-Away 01 = Entry/Exit #1 22 = Disarming (Code+Off) 02 = Entry/exit #2 31 = End of Exit Time 03 = Perimeter 32 = Start of Entry Time 04 = Interior Follower 05 = Trouble Day/Alarm Night 33 = Any Burglary Alarm 34 = Code + # + 71 Key Entry 06 = 24 Hr Silent 35 = Code + # + 72 Key Entry 07 = 24 Hr Audible 36 = At Bell Timeout ** 08 = 24 Hr Aux 37 = 2 Times Be
Relay Programming Menus From #93 Menu Mode, select Relay Programming Menu. Press * to advance to next screen. Press # to backup to previous screen. Enter Relay No. (00=Quit) 01 02 A EV ZL ZT P STT 0 0 0 00 02 A EV ZL ZT P STOP 0 0 0 00 The console displays a summary STOP screen. 02 Relay Action No Response Enter the desired relay action as follows: 0=not used; 1=closed for 2 secs.
Zone List Programming After entering all relay menu items, up to eight (8) zone lists can be entered by entering 00 at the ENTER RELAY No. prompt. Enter Zone LIST 00=QUIT 00 Enter the zone list number 1-8. 01 Enter Zn Num. 00=QUIT 00 Enter each zone to be included in this zone list, pressing * to enter each zone number. 01 Del Zn LIST? Enter 0 to save the zone list entered. Enter 1 to delete that zone list. 01 Delete Zone? 0=No 1=Yes Enter 1 to delete one or more zones in that zone list.
Alpha Programming If using a 6139 alpha console in the system, a user friendly word description/location of all protection zones, partitions' keypad panics, polling loop short and RF receiver supervision faults can be programmed into the system. Each description can be composed of a combination of words (up to a maximum of 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an "s" or " 's " added to it.
Entering Zone Descriptors (continued) 5. When all desired words have been entered, press key [8] to store the description in memory. 6. To review the zone descriptions, key [#] plus zone number (e.g., #01). To edit zone descriptions, key [*] plus zone number (e.g., *01) 7. To exit the zone description mode, key 00 then press *. NOTE: Alpha descriptor entry can be entered locally at the alpha console or remotely using a V-LINK Downloader.
Creating A Custom Message Display (Installer's Message) Normally, when the system is in the disarmed state, the following display is present on the Console. ****DISARMED**** READY TO ARM Part or all of the above message can be modified to create a custom installer message for each partition. For example, ****DISARMED**** on the first line or READY TO ARM on the second line could be replaced by the installation company name or phone number for service.
ALPHA VOCABULARY (For Entering Alpha Descriptors. To select a word, press [#] followed by the word's 3-digit number.
Section 5. SYSTEM COMMUNICATION COMMUNICATION FORMATS Split/Dual Reporting Dual reporting (*51) sends all reports to both primary and secondary phone numbers. Split reporting allows reports to be divided between the phone numbers according to the field's (1*34) selections. Split/Dual reporting can be selected by enabling dual reporting and enabling one of the split reporting options in field 1*34.
4+2 Express Ademco High Speed Reporting ADEMCO's Express format provides the same information as the 4+2 format, but with three differences: 1. The data is transmitted in DTMF (Dual Tone Multi-Frequency, known as "TouchTone", at the rate of 10 characters per second). This greatly decreases the time it takes a report to go through to central station. An average 4+2 Low Speed report might take as long as 20 seconds to complete its report, but 4+2 Express takes under 3 secs. 2.
Contact ID Reporting This is the only format that can identify all 87 protection zones by their unique zone (Contact) ID numbers, and provides a 1-digit event qualifier and 3-digit, specifically defined event code which quickly identifies the condition being reported. Contact ID reports in DTMF (Dual Tone Multi-Frequency @ 10 characters per second) and responds to a 1400 Hz followed by 2300 Hz handshake, and a 1400 Hz kissoff. This format also uses checksum instead of two message verification.
COMMUNICATION PROGRAMMING General Information To help expedite the installation, the system provides 4 different communication defaults (Low Speed, Ademco Express, Ademco High Speed & Ademco's new Contact ID). These defaults automatically program industry-standard code assignments for zones, keypad panics, non-alarm and supervisory conditions, and can be loaded at any time without affecting non-communication program fields.
COMMUNICATION PROGRAMMING GUIDE Field # *46, *48 *52, *53 *79, *80 *49 *81, *82 *54, *56, *59, *61, *64, *66, *69, *71, *74, *76 *55, *57, *60 *62, *65, *67, *70, *72, *75, *77 *58, *63, *68, *73, *78 Low Speed Choose transmission speed and frequency Send as either 4+2 or expanded Enables alarm restores Add checksum digit Define codes and selects 4+1 or 4+2 Defines alarm event code Contact ID No effect High Speed No effect Express No effect No effect No effect No effect Enables alarm restores No eff
COMMUNICATION DEFAULTS for LOW SPEED FORMAT (*94*80) *45 PRIMARY FORMAT 0 Ademco Low Speed *51 DUAL REPORTING *46 LOW SPEED FORMAT (Primary) 0 Ademco Low Speed *52 STANDARD/EXPANDED REPORT FOR PRIMARY *47 SECONDARY FORMAT 0 Ademco Low Speed *48 LOW SPEED FORMAT (Sec.
COMMUNICATION DEFAULTS for ADEMCO EXPRESS FORMAT (*94*81) *45 PRIMARY FORMAT 3 *46 LOW SPEED FORMAT (Primary) 0 *47 SECONDARY FORMAT 3 *48 LOW SPEED FORMAT (Sec.
COMMUNICATION DEFAULTS for ADEMCO HIGH SPEED FORMAT (*94*82) *45 PRIMARY FORMAT 2 *46 LOW SPEED FORMAT (Primary) 0 *47 SECONDARY FORMAT 2 *48 LOW SPEED FORMAT (Sec.
COMMUNICATION DEFAULTS for ADEMCO's CONTACT ID FORMAT (*94*83) *45 PRIMARY FORMAT 1 *46 LOW SPEED FORMAT (Primary) 0 *47 SECONDARY FORMAT 1 *48 LOW SPEED FORMAT (Sec.
Section 6 DOWNLOADING What Is Downloading? How Does Downloading Work? Downloading allows the operator to remotely access, program, and control the security system over normal telephone lines. Anything that can be done directly from the keypad can be done remotely, using DOWNLOADING. UL NOTE: Downloading is not permissible for UL installations. To Download, the following is required: 1. An IBM PC, or compatible computer with MS DOS 3.1 or higher, to run the DOWNLOADING program.
What Can Be Done Once Panel Is "OnLine"? How Secure Is Downloading? NOTES: – 86 – • • • • Arm the System in the Away Mode; Disarm the System Bypass a Zone Force the System to Accept a New Program Download Shut Down Communication (dialer) Functions (non-payment of monitoring fees in an owned system) • Shut Down all Security System Functions (non-payment for a leased system) • Inhibit Local Keypad Programming (prevents takeover of your accounts) • Leave a message for customer (6139 ONLY) • Command the Sy
DIRECT WIRE DOWNLOADING Direct Wire Downloading Connections The 4140XMPT2 can be downloaded without using a modem or telephone line by using V-LINK Downloading Software and a 4100SM Serial Module. The direct wire downloading connection is to be temporary, and is not part of the permanent installation. Direct wire downloading is meant as a tool for the installer during the installation process.
Section 7. SCHEDULING PROGRAMMING INTRODUCTION TO SCHEDULING General Information UL Note for Auto-Arming: Program bypass reports and fields 2*13 & 2*14 auto-arm fail report for UL installations. UL Note for Auto-Disarming: Auto-disarming not for use in UL installations. – 88 – Scheduling allows the system to automate some of its operation, and provides a means of reporting openings and closings by exception. It can also activate relay outputs at pre-determined times (see Time Driven Events section).
General Information (continued) Open/close by exception Scheduling provides a means of reporting openings/closings by exception, which means: _ The system sends open/close reports only if arming or disarming does not occur during the pre-determined time window. _ The system sends early to open/close reports if done earlier than window • The system sends late to open/close reports if window is missed.
When programmed, employees can arm and disarm the system within the open and close time windows respectively without causing as report to be sent to the central station (reporting by exception). At the end of these windows, the system will automatically arm/disarm if an employee fails to arm/disarm manually (auto arm/auto disarm). Time windows can also be used to program time driven relay output or X-10 device events.
Open/Close Reports by Exception The system can help reduce communication traffic to the central station by using the exception reporting feature, set in partition-specific program field 2*09. The Open/Close by exception option suppresses these reports from being sent to central station if an arm or disarm is done within the expected time window. Reports are only sent if the open/close does not occur within the assigned time window.
#80 SCHEDULING MENU MODE General Information Steps To Programming Scheduling Options – 92 – The #80 Scheduling Menu Mode is used to program most of the scheduling and timed event options. To enter this mode, the system must first be in normal operating mode. Enter installer code + # + 80.
Time Windows Definitions Worksheet The system provides 20 time windows that are defined with start and stop times. These windows are used for open/close schedules, as well as for output controls, and are the basis of the scheduling system. These windows are shared among all 8 partitions. The following worksheets will help you define time windows and scheduling aspects of this system before programming the time window definitions for this installation. Note that time windows can span midnight.
Open/Close Scheduling Worksheets Holiday Definitions & Schedule Worksheet The Open/Close scheduling is controlled by one of three individual schedules. The list of schedules, in precedence order, is: a) Temporary schedule The temporary schedule provides a method for the end user to override the daily and holiday schedules. It consists of one opening window and one closing window for each day of the week. The schedule takes effect for up to one week, after which it is deactivated.
Limitation of Access by Time Worksheet Limitation of access determines the times a particular user code is active in the system. The system provides 8 Access Schedules, each of which consists of two time windows for each day of the week and two time windows for holidays. If access schedules have been assigned, when a user is assigned, that user's access to the system can be limited by specifying an Access Schedule number in the range of 1-8. If no limitations apply, enter 0.
Bypass commands NOTE: Activation times 1 (Begin), 2 (End), 3 (During) are the only valid choices for these commands. Note the following if 3-During activation time is selected: Auto bypass will bypass the zone(s) at the beginning of the window and unbypass the zone(s) at the end of the window. Auto unbypass will remove the bypass of the zone(s) at the beginning of the window and will restore the bypass of the zone(s) at the end of the window.
Basic Scheduling Menu Structure To enter scheduling program mode, enter the installer code + # + 80. Once the worksheets are completed, you can begin to program the scheduling features. There are 5 sets of scheduling menus as shown below. Entering "1" at a displayed main menu prompt will select that menu set. Prompts for programming that scheduling feature will then appear. Enter "0" to skip a menu screen and display the next menu.
Open/Close Schedule Each partition can be assigned one daily open/close schedule, plus a holiday open/close schedule. Temporary schedules are programmed separately, using the #81 Temporary Schedule Menu Mode. To program additional open/close schedules, see the Time Driven Events section. After entering Scheduling Menu Mode, press 0 until the O/C Schedules prompt appears. O/C Schedules ? 1 Yes 0 = No 0 Enter 1 to program opening and closing schedules.
Holiday Programming Up to 16 holidays can be defined for the system. After entering Scheduling Menu Mode, press 0 until the Holidays ? prompt appears. Holidays ? 1 Yes 0 = No Enter 1 to program holiday schedules. 0 HOLIDAY NUMBER ? 01-16,00=Quit 01 Enter the 2-digit holiday number to be programmed and press * to accept entry. Enter 00 then * at the Holiday Number prompt to quit the Holiday menus and display the Quit ? prompt.
Time-Driven Event Programming (continued) 01 ACTION ? none 00 Enter the action code for the desired action for this event number from the list at the left. This could be an output command, an arming command, or any other time-driven event.
Access Control Schedules Access Control schedules are the schedules used to govern whether a given user may arm or disarm a system during a particular time window. Up to 8 schedules can be programmed, and up to 2 access control windows per day can be programmed (typically one for an opening time and the second for a closing time window). After entering Scheduling Menu Mode, press 0 until the Access Sched. ? prompt appears. Access Sched. ? 1 Yes 0 = No 0 Enter 1 to program access schedules.
#81 TEMPORARY SCHEDULE MENU MODE Temporary schedule Worksheet To enter this mode, enter the security code and press # + 81. – 102 – Each partition can be assigned a temporary schedule which will override the regular schedule (and the holiday schedule) for up to one week. This schedule takes effect as soon as it is programmed and remains active for up to one week.
Programming Temporary Schedules Temporary schedules override normal schedules. Enter user code + # + 81 to enter this mode. Note that only users with authority level of manager or higher can program temporary schedules. Temporary schedules only affect the partition from which it is entered. Temporary schedules can also be reused at later dates simply by scrolling (by pressing #) to the DAYS? prompt (described below) and activating the appropriate days.
#83 USER SCHEDULING MENU MODE General Information The system provides up to 20 "timers" which will be available to the end user for the purpose of controlling output devices (4204 or X-10). These timers are analogous to the individual appliance timers that might be purchased at a department store. The typical uses for this feature could be control of lights or appliances , typically via X-10 modules. These modules are programmed into the system by the installer during #93 Menu Mode–Device Programming.
PART 3 SYSTEM OPERATION and TESTING – 105 –
Section 1. SYSTEM OPERATION SECURITY ACCESS CODES General Information The System allows up to 128 security access codes to be assigned (maximum 99 per partition), each identified by a user ID number. In addition, the Quick Arm feature can also be programmed, which enables the [#] key to be pressed instead of entering the security code when arming the system. The code must still be entered when disarming the system.
User Codes & Levels Of Authority (cont.) Manager (Level 2) • Can perform all system functions (Arm, Disarm, Bypass, etc.) programmed by Master. • May create other users of the system below this level (Manager cannot assign anybody a level of 0, 1, or 2). • May change his own code. • May add, delete, change operators. • Open/close reporting of added users will be same as his own (enabled or disabled as assigned by installer or master). • May operate a partition.
General Rules on Authority Levels and changes The following rules apply to users when making modifications within the system based on the user code authority levels: • Master Codes and all lower level codes can be used interchangeably when performing system functions within a partition (a system armed with a user's temporary code can be disarmed with the Master Code or another user's temporary code), except the Operator Level C Code described above.
Once there, the current display becomes attached to that partition and status requests, etc. are now displayed for that partition, unless a period of 120 seconds elapses with no key entries. To return to your original partition, you may enter the same key sequence and end it with your normal partition number or "0". You're now back to where you started. It's that simple! You may view this operation as a big selector switch and you are at the switch at the console.
Part. 2 – SHOP ? 0 = NO , 1 = YES Part. 1 S WHSE User 03 Auth=3G. To CHANGE a Master, Manager or Operator code To Delete a Master, Manager or Operator code To EXIT The User Code Entry Mode – 110 – Press 0 (NO) or 1 (YES), depending on whether or not this user will have access to the displayed partition number. If NO, the console displays this prompt for the next partition number in sequence.
KEYPAD FUNCTIONS General Information Note that user related scheduling functions and programming is described in the Programming guide (setting temporary schedules, programming timed events, etc.) Arming Functions Note that if QUICK ARM is enabled (field *29), the [#] key can be pressed instead of entering the security code, for any of the arming procedures (Away, Stay, Instant, Maximum, etc.).
Mode AWAY STAY INSTANT MAXIMUM SUMMARY OF ARMING MODES Features For Each Arming Mode Exit Entry Perimeter Interior Delay Delay Armed Armed Yes Yes Yes Yes Yes Yes Yes No Yes No Yes No Yes No Yes Yes Access Control If programmed, one relay may be used for access control. To activate this relay, the user enters his user code + [0]. The relay will pulse for 2 seconds. Delay Closing Time If open/close schedules are used, end users can manually extend the closing window by up to 2 hours.
Displaying Descriptors Panic Keys Trouble Conditions "Check" Messages Other Trouble Conditions Power Failure The Alpha Consoles can display all programmed descriptors, which is useful to the installer when checking entries, and can be helpful to the user when there is a need to identify zones. To display descriptors, press and hold the READY key until the built-in instructions for that key appear, then release the key. The zone descriptors will appear one at a time, for about 2-3 seconds each.
Section 2. EVENT LOGGING (Connector J8) Event Logging Printer Connections UL NOTE: A UL Listed EDP printer must be used for UL installations. Connector J8, located above connector J7 on the right side of the main PC board, is intended to be interfaced to a local serial printer via the 4100SM serial interface module, in applications where it is desired to print the event log on a local printer. Mount the 4100SM using its clip bracket to attach it to the side wall of the control cabinet.
Event Logging Procedures IMPORTANT: In order for time and date stamping to occur, the system's real-time clock must be set. Refer to the SETTING THE REAL TIME CLOCK section. The system has the ability to record various events in a history log (224 event capacity) wherein each event is recorded in one of five categories (alarm, check, bypass, open & system), with the time and date of its occurrence (if real-time clock is set).
To display the events in a particular category, press [8] at the desired category screen. If in Display Mode, events will appear one at a time from the most recent to the oldest. Press [8] again to display each subsequent event. If in Print Mode, the first press of [8] will cause the printer to print all events in that category, with each event automatically scrolled on the display console.
Section 3. TESTING THE SYSTEM Using Test Mode After the installation is completed, the Security System should be thoroughly tested on a partition by partition basis as follows: 1. With the System in the disarmed state, check that all zones are intact. If DISARMED - Press [*] to show faults is displayed, press the [*] key to display the descriptors of the faulted zone(s). Restore faulted zone(s) if necessary, so that ****DISARMED*** READY TO ARM is displayed. 2.
Turning The System Over To The User 1. Fully explain the operation of the system to the user by going over each of its functions as well as the User's Manual supplied. 2. In particular, explain the operation of each zone (entry/exit, perimeter, interior, fire, etc.). Be sure the user understands how to operate any emergency feature(s) programmed into the system.
Section 4. REGULATORY AGENCY STATEMENTS IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS In the event of telephone operational problems, disconnect the control panel by removing the plug from the RJ31X (CA38A in Canada) wall jack. We recommend that you demonstrate disconnecting the phones on installation of the system. Do not disconnect the phone connection inside the Control Panel. Doing so will result in the loss of your phone lines.
Section 5.
DIP SWITCH TABLES FOR ADDRESSABLE CONSOLES AND POLLING LOOP DEVICES Addressable Consoles (e.g. 5137AD) 4208 Zone Expander 4192SD/4192SDT/ 4192CP Smoke Detectors 4190WH Zone Expander DIP + - DIP ➞ DIP UP UP † IMPORTANT: USE ID 31 FOR APPLICATIONS NOT REQUIRING ADDRESSABLE CONSOLES. dn APPLIES TO TABLES A & B SHOWN SET FOR ID 10(A) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 UP ➞ dn APPLIES TO TABLE A ONLY SIDE VIEW SHOWN SET FOR ID 10 (UP) POS.
DIP SWITCH TABLES FOR POLLING LOOP DEVICES MIRROR SHOWN SET FOR ID 10 (A) 1 2 3 4 5 6 7 1 2 3 4 5 6 DN DN — } } UP A DIP SWITCH POSITION 1 2 3 4 5 — — — — — — UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP — — — — — — — — UP UP UP UP UP UP UP UP — — UP UP UP UP — — — — UP UP UP UP — — — — UP UP UP UP UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP THIS TABLE FOR DIPS WITH WORD “ON” - 122 - SIDE VIEW (DN
DIP SWITCH TABLES FOR 5700 RF SYSTEM WIRELESS DEVICES HOUSE ID SWITCH SETTING FOR ALL DEVICES EXCEPT 5716 2 3 4 5 UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP — — — — — — — — — — — — — — — — UP UP UP UP UP UP UP — — — — — — — — UP UP UP UP UP UP UP UP — — — — — — — — UP UP UP — — — — UP UP UP UP — — — — UP UP UP UP — — — — UP UP UP UP — — — — UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — 16
Section 6. SPECIFICATIONS 4140XMPT2 CONTROL Physical: 12-1/2"W X 14-1/2"H X 3"D (318mm x 368mm x 76mm) Electrical: VOLTAGE INPUT: From Ademco No. 1361 Plug-In Transformer (use 1361CN in Canada) or 4300 transformer (for X-10 installations) rated 16.5VAC, 40 VA. ALARM SOUNDER OUTPUT: 10VDC-13.8VDC, 2.8 amps max. (UL1023, UL609 installations), 750mA less aux. current drain (UL985 installations). AUXILIARY POWER OUTPUT: 9.6VDC-13.8VDC, 750mA max. BACK-UP BATTERY: 12VDC, 4AH or 7AH gel cell.
INDEX (ASCII) CHART 75 12/24 Hour Time Stamp Format 60 1361 36, 124 1361CN 36 24-hour Audible Alarm 14 4+1 80 4+2 80 4+2 Express 50, 77 4+2 Reporting 76 4100SM 7, 50, 87, 114 4137AD 7, 32, 37 4139SN 18 4142TR 28 4146 7 4190 37 4190WH 18 4191SN 18 4192CP 18, 37 4192SD 18, 37 4192SDT 18, 37 4194 18, 37 4197 18, 37 4204 7, 28 4208 18, 37 4208 Module Zone Assignment 55 4275 18, 37 4278 18, 37 4280 8, 19, 20, 37 4280 63 37 4280-8 19, 37 4281 8, 20 4281/5881 19 4281H 19 4281L 19 4281M 19 4300 28 464 24 5700 8 570
expanded reporting 76 Express 80 factory defaults 51 FCC REGISTRATION NO 124 First 4280 Receiver Select 55 First Page of fields 52 First Test Report Time 55 Force arm 92 form C 28 Glass Break Detectors 8, 16 Global Arming 8, 111 Global Disarm 111 Go To 11 Go/No Go Mode 20, 21 GOTO Function 10,108, 112 Ground Start Module 25, 27 HARD-WIRED ZONES 15 High Speed Reporting 77, 80 Limitations 77 Holiday Definitions & Schedule Worksheet 94 Holiday Programming 99 holiday schedules 92, 94 House Code 70 house ID 19,
Deleting a Master Manager or Operator 109 General Information 106 User Scheduling Menu Mode 92 User's Manual Using the Built-In 112 Video Alarm Verification 41 Voltage Triggers 9, 25 Wireless 8 Advisories 22 Wireless Keypad Assignment 59 Wireless Keypad Tamper Detect 59 Wireless Options 59 X-10 7, 12, 28, 68, 104 ZL 68, 69 Zone 1 15 Zone 1 Advisories 15 Zone 9 15 Zone 9 Advisories 15 Zone 9 Fast/Slow Response 54 ZONE CONFIGURATION 13 Zone Cust Deleting a zone in 71 ZONE DESCRIPTOR 72 ZONE LIST 68 Deleting 7
NOTES – 128 –
NOTES – 129 –
WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. • Intrusion detectors (e.g.
TRANSFORMER 16.5VAC, 40VA ADEMCO No.1361 (IN CANADA USE No. 1361CN) or 4300 TRANSFORMER IF X-10 DEVICES WILL BE USED Connect to 24-hr. 120VAC, 60 Hz Outlet 1 - 3 4 + - 5 Blk - 7 9 Yel 8 Grn See Installation Instructions for type & max # of keypads, and for max wire run length. REMOTE KEYPAD (Use 6128/6139 only) (Addressable keypads) Red + 6 Data in COMPLIES WITH FCC RULES, PART 68 FCC REGISTRATION NO. AC398U-68192-AL-E RINGER EQUIVALENCE: 0.7B AUXILARY POWER OUTPUT 9.6VDC - 13.
ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 18 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchas