Technical data

62
- The "X" character means that the corresponding sensor is physically not connected.
- The "!" character means that the corresponding sensor is physically connected but not activated. If you
want to activate it, go to the "Settings/Power Outlets" tab.
- The " " character (blank) means that the corresponding sensor is physically connected and activated.
According to the device you use, choose the Analog Input in the second Drop-Down (temperature,
humidity, light, current, energy...).
Action Condition:
The options "higher than" and "lower than" enable you to define when the rule has to be executed.
- Choose "higher than" if you want to execute the rule when the environment value exceeds the value you
defined in the field on the right of "higher than".
- Choose "lower than" if you want to execute the rule when the environment value is below the value you
defined in the field on the right of "lower than".
For temperature, you can define values between -25°C and 60°C, +/- 2°C.
For relative humidity, you can define values between 20 RH and 80 RH, +/- 3%.
For ambient light, you can define values between 0 and 1000 Lux.
For the effective current (rms), you can define values between 1 and 10 Amps.
Configuring the Actions
For the Event defined above, you can choose and configure the following actions:
Set Group:
This type of action appears and can be configured only if you have already created at least one
group (Settings/Groups Tab).
Check this box and in the corresponding drop-down list choose the power outlet group the rule will apply
to. In the next corresponding drop-down list, choose the action to execute.
Each power outlet group can be switched On/Off and restarted. If you choose "restart" you will also be
able to define a restart delay between 0 and 65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the ePowerSwitch power outlets settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the ePowerSwitch
power outlets settings.
Set Power Outlet:
Check this box and in the corresponding drop-down list choose the power outlet the rule will apply to. In
the next corresponding drop-down list, choose the action to execute. Each power outlet can be switched
On/Off and restarted. If you choose "restart" you will also be able to define a restart delay between 0 and
65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the ePowerSwitch power outlets settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the ePowerSwitch
power outlets settings.
Set Digital Output:
Check this box and in the first corresponding drop-down list, choose the device from which one you want
to switch a digital output. In the second drop-down list, choose the digital output the rule will apply to. In
the next corresponding drop-down list, choose the action to execute. Each digital output can be open,
close, pulse open or pulse close. If you choose "pulse...", you will also be able to define a pulse delay
between 0 and 65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the digital output settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the digital output
settings.