Technical data
5
100 (LED)
Off = 10 Mbits/sec connection
On = 100 Mbits/sec connection
RS232 (SUB-D 9F Connector)
Serial port RS232 with DB-9 female connector
Pinout
2 = TxD
3 = RxD
5 = Gnd
xBus
The RJ45 connector is used for cascading ePowerSwitch devices and xBus peripherals
Maximal TOTAL line length: 200 meters
Term (RS485 Termination DIP Switch)
The xBus interface (RS485) has built-in termination resistors. To enable these resistors slide the two
DIP Switch to the ON position (down).
Termination should be enabled at the two end stations on an RS485 network.
No more than two stations should be terminated on an RS485 network.
S B 5 6 7 8 1 2 3 4 (LEDs)
S Status
On = ePowerSwitch 8XM software is loaded and functional
Off = power default
1 time repeatedly = power on but not ready
2 times repeatedly = waiting on IP address from DHCP server
3 times repeatedly = SSL key computing in progress (takes several minutes
!!!)
4 times repeatedly = System error (contact the manufacturer)
B Green. Lights up when power applied on Group B
5 Red. Status of power outlet 5 (On/Off)
6 Red. Status of power outlet 6 (On/Off)
7 Red. Status of power outlet 7 (On/Off)
8 Red. Status of power outlet 8 (On/Off)
1 Yellow. Status of dry contact output 1 (Open/Closed)
2 Yellow. Status of dry contact output 2 (Open/Closed)
3 Yellow. Status of dry contact output 3 (Open/Closed)
4 Yellow. Status of dry contact output 4 (Open/Closed)
I/O (SUB-D 25F Connector)
Dry Contacts: 4 Outputs and 8 Inputs
Do NOT exceed 24VDC – 20 mA
(see Annexe Table for the Pin configuration)
12 VDC AUX Power Supply
The Web server can be powered either by power input A or power input B.
To increase the operational safety of the Web server, an auxiliary power supply (12 VDC / 300 mA) can
be connected to this input (double insulated, ie. not connected to ground).