Technical data

50
Number of unsuccessful Requests before Action:
In this field, define the number of Ping commands to be sent to the IP device before executing the actions.
The number can be set between 1 and 65535 seconds.
Delay before First Request after Power up:
In this field, define the time in seconds before restarting the monitoring after the reboot action.
The delay can be set between 30 and 65535 seconds.
Configuring the Actions:
For the Event defined above, you can choose and configure following actions:
Set Group:
This type of action appears and can be configured only if you have already created at least one
group (Settings/Groups Tab).
Check this box and in the corresponding drop-down list choose the power outlet group the rule will apply
to. In the next corresponding drop-down list, choose the action to execute.
Each power outlet group can be switched On/Off and restarted. If you choose "restart" you will also be
able to define a restart delay between 0 and 65535 seconds.
- If you choose 0 second for the delay, the delay will be the delay defined in the power outlets settings.
- If you choose a delay different from 0, it will replace the delay defined in the power outlets settings.
Set Power Outlet:
Check this box and in the corresponding drop-down list, choose the power outlet the rule will apply to. In
the next corresponding drop-down list, choose the action to execute. Each power outlet can be switched
On/Off and restarted. If you choose "restart" you will also be able to define a restart delay between 0 and
65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the ePowerSwitch power outlets settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the ePowerSwitch
power outlets settings.
Set Digital Output:
Check this box and in the first corresponding drop-down list, choose the device from which one you want
to switch a digital output. In the second drop-down list, choose the digital output the rule will apply to. In
the next corresponding drop-down list, choose the action to execute. Each digital output can be open,
close, pulse open or pulse close. If you choose "pulse...", you will also be able to define a pulse delay
between 0 and 65535 seconds.
- If you choose 0 second, the delay will be the delay defined in the digital output settings.
- If you choose a delay different from 0, the delay will replace the delay defined in the digital output
settings.
Send Syslog Message:
This type of action appears and can be configured only if you have already created at least one
destination Syslog Server (Misc/Log Settings Tab).
Check this box if you want to send a message to a Syslog server. In the following drop-down lists choose
the facility and the severity of the message to send. The address of the Syslog server has to be defined in
the "Log Settings Page".
Send Trap Message
This type of action appears and can be configured only if you have already specified at least a
destination SNMP Server (General/SNMP Tab).
Check this/these box(es) and specify one or two SNMP addresses in the corresponding field if you want to
send SNMP messages to one or two SNMP Servers.
Mail to:
This type of action appears and can be configured only if you have already created a destination
SMTP Server (General/SMTP Tab).
Check this/these box(es) and specify one or two e-mail address(es) in the corresponding field if you want
to send an e-mail to one or two specific user(s). To send e-mails, you will need a SMTP server on the
network and you will have to configure its parameters in the "SMTP Page".
Syslog / Trap / Mail Message
This field appears only if you have already configured at least one destination Syslog Server
(Misc/Log Settings Page) or a destination SMTP Server (General/SMTP Page).
Up to 255 characters may be entered in this free text field. The text will appear in the Syslog, the Trap and
the e-mails.