5.3.13 Power Supply Monitoring Rule
This rule can be used to monitor the status of the power suplies of each ePowerSwitch 8XM and
ePowerSwitch 8XS.
Rule ID
The ePowerSwitch 8XM automatically creates an ID Code to clearly identify each rule. All the ID Codes used
to identify rules start with the character "R" followed by a number.
Rule Name
In this field, enter the name you want to give to the rule. The name can be from 1 to 32 characters long, and
can contain alphanumeric characters.
Rule Type
In this Drop-Down list, choose Power Supply Monitoring Rule.
Rules are used to control actions according to specific events. First you will have to configure the choosen
event as follows, then you will choose the actions to execute.
Device to monitor
In this Drop-Down list, choose the device for which you want to monitor the power supply.
Each device name is preceded by the ID Code of the device (M0 for the Master, S1 for the Satellite 1, S2 for
the Satellite 2...).
A character between brackets can follow this ID Code:
- The "X" character means that the corresponding satellite is physically not connected.
- The "!" character means that the corresponding satellite is physically connected but not activated. If you
want to activate it, go to the "Settings/Power Outlets" tab.
- The " " character (blank) means that the corresponding satellite is physically connected and activated.