User's Manual

CHAPTER 3
Advanced Functions
36
PORT
DESCRIPTION Acts upon the I/O ports of a remote device.
PARAMETERS The RTU’s ID, the byte code, and parameters (for some forms of
the command). All parameters are in decimal form (pay particular
attention to the byte code because it must be translated to deci-
mal).
RETURNS Status result, depends on command.
REMARKS This command is currently supported only by the A720 (series 2)
and A723 (series 3) addITs and A733 addWAVE RTUs.
EXAMPLE port 9473 0
Dev 9473: incoming RF 255, outgoing RF 255
Value: 255, Error level: 0
OK
ANALOG
DESCRIPTION Acts upon the analog input ports of a remote device.
PARAMETERS The RTU’s ID, the byte code, and parameters (for some forms of
the command). All parameters are in decimal form (pay particular
attention to the byte code because it must be translated to deci-
mal).
RETURNS Status result, depends on command.
REMARKS This command is currently supported only by the A723 (series 3)
addITs and the A733 addWAVE RTUs.
EXAMPLE analog 9473 0
Dev 9473: incoming RF 255, outgoing RF 255
Average method: 1 2 3 4 5 6 7 5 5 5 5 5 0 0 0 0
Error level: 0
OK
B
DESCRIPTION Issues a broadcast request frame that forces all listening devices to
answer.
PARAMETERS None.
RETURNS A list of devices that answered.
REMARKS None.
EXAMPLE b
From 2003: incoming RF 255, outgoing RF 255