Installation manual

48
IMPORTANT
MANUAL RESET HI-LIMIT INSTRUCTIONS
FOR PHASE 6 MODELS
(STEAM MODELS ONLY)
This dryer was manufactured with a manual reset tumbler/lint chamber hi-limit thermostat which is monitored by
the Phase 6 computer. If the manual reset thermostat is open prior to start of the drying cycle, the dryer will start
momentarily and then shut down, displaying dRUM SAFETY FAIL with an audio indication.
If the manual reset hi-limit thermostat opens during a drying cycle, the display will read dRUM SAFETY FAIL
with an audio indication. If the drum temperature is above 100º F (38º C), the dryer will continue to run with no
heat for three (3) minutes or until the drum temperature has flattened below 100º F (38º C). The clear/stop button
on the Phase 6 keyboard (touchpad) must be pressed to clear this dRUM SAFETY FAIL condition. The open
manual reset hi-limit thermostat must be reset manually prior to the start of the next cycle.
This hi-temperature condition may be caused due to a restricted exhaust, poor airflow or improper burner operation.
The tumbler manual reset hi-limit is locked in the chamber area.
WARNING: Discontinue power to dryer before attempting to reset hi-limit.
IMPORTANT
This dryer is equipped with a lint
chamber hi-limit thermostat which must
be reset manually.
WARNING: Discontinue power to dryer
before attempting to reset hi-limit.
ADC P/N: 114501