BATCH FUNCTION.
ENABLE BATCH
Enable one of the following functions to enable and program the batch on the converter:
Menu: 5.INPUT:
- BATCH (page 52 pos. 37)= Enable this function (on)
Menu 6.OUTPUT:
- OUT.1/OUT.2 (page 52 pos. 38-39) = BATCH AND PRE-BATCH
The value of batch (quantity batch) is setting from visualizzation page (see page 63)
Output for pre-batch:
6.Output: OUT.1= END BATCH*/PREBATCH*
OUT.2= END BATCH*/PREBATCH*
END BATCH = output signal of end batch, PREBATCH = output signal of pre-batch
When the “batch outputs” are enable is possible to set the values of pre-batch and compensation:
VPRE= pre-batch value: set the volume of liquid at which you want to enable the pre-batch.
At the pre-batch volume “V Pre” the output (if enabled) is de-energised.
This value is constant for all quantity to batch and must be set in current unit of measure of volume
The pre-batch function is useful when you need fast and accurate fillings.
VCOM= Compensation value: set the volume dosed in excess because of
system delays, like valve closure, pump stop, motor stop, etc.. It is recommended to run some test batch to learn this
value.
N.B.: the output functions, for batch (batch and prebatch) can be also associate to the additonal module outputs