(POS. 41) Choice of the function corresponding to on/off output 3 [OUT4= XXXXXX]
Choice of the function corresponding to digital Output 4. The functions are listed in the table below.
This is the only output which can reach a 12.5 KHz frequency.
Attention: Output 4 is Optional and is mounted on an optional add on module.
FUNCTION FOR OUTPUT 1, 2,3,4
OFF: DISABLED
#1PULS+: PULSE ON CHANNEL 1 FOR POSITIVE FLOW RATE
#1PULS-: PULSE ON CHANNEL 1 FOR NEGATIVE FLOW RATE
#1PULS±: PULSE ON CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE
#2PULS+: PULSE ON CHANNEL 2 FOR POSITIVE FLOW RATE
#2PULS-: PULSE ON CHANNEL 2 FOR NEGATIVE FLOW RATE
#2PULS±: PULSE ON CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE
#1FREQ+: FREQUENCY CHANNEL 1 FOR POSITIVE FLOW RATE
#1FREQ-: FREQUENCY CHANNEL 1 FOR NEGATIVE FLOW RATE
#1FREQ±: FREQUENCY CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE
#2FREQ+: FREQUENCY CHANNEL 2 FOR POSITIVE FLOW RATE
#2FREQ-: FREQUENCY CHANNEL 2 FOR NEGATIVE FLOW RATE
#2FREQ±: FREQUENCY CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE
SIGN: FLOW DIRECTION OUTPUT (ENERGISED = -)
RANGE: RANGE INDICATION OUTPUT (ENERGISED = SCALE 2)
MAX AL: MAX FLOW RATE OUTPUT(ENERGISED = AL. OFF)
MIN AL: MIN FLOW RATE OUTPUT(ENERGISED = AL. OFF)
MAX+MIN: MAX AND MIN FLOW RATE ALARM OUTPUT (ENERGISED = AL. OFF)
EMPTY PIPE: EMPTY PIPE ALARM OUTPUT (ENERGISED = FULL PIPE)
OVERFLOW.: OUT OF RANGE ALARM OUTPUT (ENERGISED = FLOW RATE OK)
HARDW.AL: CUMULATIVE ALARM OUTPUT (ENERGISED = NO ALARMS)
END BATCH: END BATCH OUTPUT (ENERGISED = BATCH IN PROGRESS)
PREBATCH: PREBATCH OUTPUT (ENERGISED = PREBATCH IN PROGRESS)