Technical information
C:
\
UFFICIO TECNICO
\
MANUALI
\
ML2
00
\
ML200 INGLESE
\
46
(POS. 18) Acceleration threshold [SKIP THR=% XXX]
Acceleration threshold set. The acceleration threshold stands for the limit beyond which a flow rate variation
determines an immediate response at the output, without being filtered by the time constant. This system allows the
instrument to have an immediate response in case of big variations of the flow rate, filtering (and delaying) the
response to small variations. The result of that is a very stable measure, ready to follow the process. The value is set
as percentage of the full scale value from 0 to 125%. If such a value is set to zero any flow rate variation bigger than
0.5% of the full scale value will immediately effect the outputs.
The following diagram shows the instrument response in two cases: a flow rate variation from 0 to 10% completely
absorbed by the time constant effect and a variation form 10% to 100% exceeding the acceleration threshold and
then immediately sent to the output. In actual fact there is always a minimum time between the measure acquisition
and the outputs update. For the ML190 and ML200 this time in the worst case is around 140 ms as far as the 0/4…20
mA output is concerned.
0
t
%
100
100
0
0
PORTATA
MISURA
%
10
10
5T