Technical information
C:
\
UFFICIO TECNICO
\
MANUALI
\
ML2
00
\
ML200 INGLESE
\
44
(POS.13) Pulse duration channel 2 [TPUL2=ms XXXX.XX]
Setting of the duration of the pulse generated on channel 2. Its value is expressed in milliseconds and has to be
between 0.4 and 9999.99. When the high frequency output is present, then the minimum value can go down to 0.04
milliseconds.
ATTENTION: be careful to what mentioned in the previous function
This function is active only when the pulse emission function on channel 2 is enabled.
(POS.14) Full scale frequency channel 1 [FRQ1=Hz XXXXX.X]
Full scale frequency set for channel 1.Its value is expressed in Hertz and is between 1.0 and 1000.0. When the high
frequency output is present the maximum value may go up to 10000.0.
ATTENTION: be careful to what mentioned in the previous function.
This function is enabled only when the frequency generation mode on channel 1 is active.
(POS.15) Full scale frequency channel 2 [FRQ2=Hz XXXXX.X]
Full scale frequency set for channel 2.Its value is expressed in Hertz and is between 1.0 and 1000.0. When the high
frequency output is present the maximum value may go up to 10000.0.
ATTENTION: be careful to what mentioned in the previous function.
This function is enabled only when the frequency generation mode on channel 2 is active.
(POS. 16) Specific gravity [SW=Kg/dm³ XX.XXXX]
Specific gravity set. Its value is expressed in Kilogram per cubic decimetre and has to be within the range from 0.0001
to 99.9999.
This function is active only if a mass unit of measure has been selected.