(POS.10) Pulse value channel 1 and unit of measure of the totalizers [IMP1=dm³ X.XXXXX]
Setting of the volume corresponding to each pulse of channel 1 and totalizers unit of measure. There are three fields
to fill in to set this parameter, from left to right: 1) unit of measure, 2) type of unit of measure and 3) numeric value.
The selection is performed positioning the cursor on the field to modify. To change the type of unit of measure
(metric, British or American, mass or volume) just position the cursor on the blank space between the unit of measure
and the numeric value. Then the nominal diameter is set to zero, it is possible to modify only the numeric field since
the unit of measure stays at metre (m). the possible units of measure are those above described.
This function is active only if the pulse emission on channel 1 has been set as enabled.
(POS.11) Pulse value channel 2 and unit of measure of the totalizers [IMP2=dm³ X.XXXXX]
Setting of the volume corresponding to each pulse of channel 2 and totalizers unit of measure.
This function is identical to the previous one and is active only if the pulse emission on channel 2 has been set as
enabled.
(POS.12) Pulse duration channel 1 [TPUL1=ms XXXX.XX]
Setting of the duration of the pulse generated on channel 1. Its value is expressed in milliseconds and has to be
between 0.4 and 9999.99. When the high frequency output is present, then the minimum value can go down to 0.04
milliseconds.
ATTENTION: since the instrument cannot detect which type of device it is connected to, it is up to the user to verify
the set pulse duration is compatible with the external device processing such pulses. If, by example, an electro-
mechanical pulse counter is connected, then two kind of problems may occur: if the pulse is too long than the totalizer
coils may burn or, if it too short, the counter may not count, even damaging the converter output.
This function is active only when the pulse emission function on channel 1 is enabled.